MR-0136, 1x CAN, with its own power supply, galvanic isolationTXN 101 36

MR-0136, 1x CAN, with its own power supply, galvanic isolation

DI
DO
AI
AO
COM 1x CAN
SENSOR
Submodule MR-0136 contains 1x CAN interface.
Internal wiring ensures galvanic separation of the interface from the system and power circuits. At the same time, the module contains identification circuits
The user has the option to identify the type of submodule used in the development environment.
Order num. TXN 101 36
Teco code TXN 101 36
Categories Foxtrot 2 - Accessories for basic modules, TC800 - Positioning and counter modules
Tags -
COM - Serial channels
Max. baud rate 1 MBd
Number of internal CAN ports 1
Power supply
Supply voltage, tolerances The submodule is powered from the power supply the terminal device in which it is installed.
Maximum power input 1,2 W
Insulation voltage of galvanic separation 1 000 VDC
Size and weight
Weight approx. 25 g
Product dimensions (width x height x depth) 15,5 × 42 × 3,5 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Submodule
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Installation
Attention! Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to touch the printed circuit boards directly without protective measures.
Connection
Description Terminal communication interfaces are typically equipped with connectors. The connection of the connectors is specified in the documentation of the respective system where the submodule is used.
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Warning All conditions of this documentation must be met before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery of which the Foxtrot system is a part complies with the requirements of Directive 89/392 / EEC, in so far as it applies to them. Documentation subject to change.

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)

No data available.

No data available.