CP-2005.11NSNN.50TXN 120 05.11NSNN.50

CP-2005, Mosaic Single lic. + iCOOL ready; CPU/1, 2xETH, ---, 128kB dbox, LCD-7, CH1-4, 6x AI/DI, 6x RO, 2x AO, 1xCIB, 1x TCL2

DI 3x DI/AI
3x DI/AI/HSC
DO 6x RO
AI 6x AI / DI
see DI
AO 2x AO
COM 2x ETH 10/100
4x Serial channel (2x free slot)
1x USB device
1x USB host
1x TCL2 master
1x CIB master
SENSOR
Picture Variant Variant description
CP-2005.11NSNN.50 Databox: 128 kB
Processor: 1 core, ARMv7 792 MHz
Display: OLED display small 26 x 7 mm
Media viscosity: ≤ 4 mm²/s
iCOOL ready: Yes
CP-2005.11NSLN.50 Databox: 128 kB
Processor: 1 core, ARMv7 792 MHz
Display: OLED display small 26 x 7 mm
Modem: LTE1 installed
iCOOL ready: Yes
CP-2005 is a second-generation Foxtrot basic module, which is an optimal combination of a central unit with an integrated combination of 12 digital and analog inputs and outputs, compact size occupying a width of 6 modules on a DIN rail. It is thus possible to have a variant with a built-in LTE modem for direct connection to the Internet via a mobile operator.
Of course, there are masters of both system expansion buses - TCL2 (up to 10 addressable modules) and two-wire CIB Common Installation Bus® (up to 32 addressable modules). It can therefore be extended in the same way as other basic modules.

It is equipped with a total of 12 I / Os:
  •     six multipurpose inputs, each of which can be used either as analog or as binary
  •     two analog outputs for proportional control of various connected devices.
  •     six separate relay outputs organized into two groups of three with their own common terminal

Communication capabilities of the basic module CP-2005:
  •     2x Ethernet interface 100 Mbit / s, each with up to 32 simultaneous connections (programming and general IP communication)
  •     USB micro (programming)
  •     USB A for Flas memory, WiFi adapter (client and AP - Access point) etc.
  •     Variant with built-in LTE modem for direct wireless connection to the Internet via a mobile network operator
  •     Slots for up to 4 optional serial interfaces RS-485, RS-232

24 V DC power supply, possibility of direct connection of a backup battery for uninterrupted operation in case of 230 V AC mains failures.

CP-2005 is equipped with a new powerful central unit (CPU series L) with memory
  •     1 MB for user program,
  •     128 MB internal disk for storing files with parallel access from the LAN as a network disk,
  •     16MB fast RAM disk
  •     128/256 kB Datalobox
  •     microSD card slot up to 1 TB
  •     File management is provided by a journaling file system
  •     Local communication with the user via OLED display (4 lines / graphic) and 6-key keyboard
Order num. TXN 120 05.11NSNN.50
Teco code TXN 120 05.11NSNN.50
Categories Foxtrot 2 - Basic modules
Tags -
System parameters of the central unit
Row of central unit I
User program memory 1 MB
Memory for user variables / including RETAIN variables 320 kB/48 kB
Instruction length 4 Byte
Backup of program source code in PLC Yes, optional in Mosaic
On-line program change in PLC Yes, including I / O configuration change
DataBox - additional internal data memory 128/257 kB, optional
File system - Internal Drive in PLC 128 MB, journaling file system
File system - RAM disk PLC 16 MB
File System - USB Flash Drive Supported
File system - Micro SD card supported (except for variants with WLAN1)
Optional memory card slot microSD - Card Slot (<= 1TB)
Cycle time per 1k of logic instructions 0,036 ms
Cycle time for 1k integer operations 0,044 ms
Cycle time for 1k floating point operations 0,043 ms
Development environment Mosaic v2018.2 or higher
Programming languages ST, IL, LD, FBD, SFC, CFC
RTC - Real time circuit No
RTC - Backup time typ. 500 hours
Integrated Web server Yes
Integrated Datalogger Yes
Access to PLC variables via web API Yes
COM - Communication - IP/Ethernet
Ethernet 10/100 Mb (ETHx) 2
WLAN1 (internal, optional) 1
WLAN2 (external via USB host, optional) 1
LTE interface (LTEx, optional) 1
Available system modes on ETH and WLAN UNI, PC, PLC, PLD
Available system modes on LTE UNI - Exchange over UDP, TCP and support SSL / TLS encryption PC - EPSNET UDP / EPSNET TCP
TCP / IP protocol Yes
UDP protocol Yes
HTTPS protocol Yes
HTTP protocol Yes
WebSocket protocol Yes
Protocol MODBUS/TCP Yes
SMTP protocol Yes
IEC 60870-5-104 protocol Yes
REST API Yes
COM - USB
USB devices interface 1x micro-USB
USB host interface 1x USB-A
Available system modes on USB PC
COM - Serial channels
max. number of optional serial channels in the basic module 4
number of slots for optional submodules with interface (MR-013x) 2
max. number of expanding serial channels on the TCL2 bus 6
Available system modes on CH5-10 UNI, CSJ (CAN)
Modbus RTU / ASCII master protocol Yes
Modbus protocol RTU/ASCII slave Yes
COM - System buses
TCL2 - system I/O bus 1x TCL2 master
TCL2 - Range of one branch of the system I/O bus 10 I / O modules + 4 operator panels + 6 serial channels
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB master (100 mA)
CIB - Address range of one branch of the installation bus 32 CFox I/O modules
DI - Parameters of binary inputs DC (group A)
Number of inputs in group 6
Common wire minus
Input type Type 1 (IEC)
Galvanic isolation of inputs from internal/peripheral circuits No
Diagnostics indication of energized input by LED on module panel
Input voltage for log. 0 0 V DC; -5 V DC min.; +5 V DC max.
Input voltage for log. 1 24 V DC; 15 V DC min.; 30 V DC max.
Input current at log. 1 (typ.) 5 mA typ.
Delay from log. 0 to log. 1 500 μs
Delay from log. 1 to log. 0 500 μs
The minimum width of the captured pulse 500 μs
Notice Note that the GND terminals in the 24 V DC and ANALOG OUTPUTS arrays they are connected inside the system. It is not desirable to connect the GND terminal in the ANALOG field OUTPUTS with a negative pole power supply system also inputs as it would cross the other the GND terminal has closed the loop and thereby potentially induced interfering signals.
HSC - Special functions of binary inputs / counters
Unidirectional counter (UP) 3x (DI3); (DI4); (DI5)
HSC - Counter input parameters
Counter: Input frequency / resolution 1 kHz
Pulse width min. 500 μs
Delay from log. 0 per log. 1 500 μs
Delay from log. 1 per log. 0 500 μs
Range of registers up to 32 bits, 0 to 4 294 967 296
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminals DO0 - DO5
Number of relay outputs 6
Number of output groups 2
Organization of relay outputs into groups 3x (DO0-DO2) + 3x (DO3-DO5)
Diagnose Alarm signaling on panel module
Switching current 3 A max., 100 mA min.
Switching voltage 250 V AC max., 5 V AC min., 30V DC max.
Short-term output overload - inrush 4 A max.
Current through common clamp 10 A max.
Contact closing time typ. 10 ms
Contact opening time typ. 4 ms
Limit values of switched resistive load max. 3A at 30 V DC or 230 V AC
Switching inductive load limits DC13 max. 3 A at 30 V DC
Switching inductive load limits AC15 max. 3 A at 230 V AC
Switching frequency without load max. 300 switching / min.
Switching frequency with rated load max. 20 switching / min.
Mechanical life min. 5,000,000 cycles
Electrical life at maximum resistive load min. 100,000 cycles
Electrical life at maximum load inductive DC13 min. 100,000 cycles
Electrical life at maximum load inductive AC15 min. 100,000 cycles
Short-circuit protection No
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 3750 V AC
Isolation voltage between groups of outputs to each other 3750 V AC
AI - Organization of analog inputs
Total number of analog inputs 6
Number of inputs per group 6
Number of analog input groups 1
Input type With common clamp
Common wire Minus
Galvanic separation from internal circuits No
Diagnostics overload signaling in status word
External power supply No
Digital resolution 12 bit
Converter type Approximation
conversion time 20 μs
Operating modes periodic input sensing
Filtration low pass filter, digital comb filter 50/60 Hz
Insulation potential 500 V DC between input and internal circuits
AI - Analog Input Ranges (Group A)
Voltage 0 to 10 V / 2,579 mV
Voltage 0 to 2 V / 805.9 μV
Input impedance in the voltage signal range > 20 kΩ
Voltage input error - max. error at 25 ° C ± 0.4% of full scale
Voltage input error - temperature coefficient ± 0.03% of full scale / K
Voltage input error - non-linearity ± 0.07% of full scale
Voltage input error - repeatability under steady state conditions 0.05% of full scale
Permissible continuous overload - voltage input -20 V to +30 V
Ccurrent 0 to 20 mA / 8,059 μA
Current 4-20 mA
Input impedance in the current signal range 100 Ω
Current input error - maximum error at 25 ° C ±0.4% of full scale
Error current input - temperature coefficient ± 0.03% of full scale / K
Error current input - nonlinearity ± 0.07% of full scale
Error current input - repeatability at steady-state conditions 0.05% of full scale
Permissible continuous overload - current input, resistance 100 R ± 5 V / 50 mA max
Open input detection Yes, in status word (under-range - only 4 - 20 mA range)
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-2 kOhm
Passive sensor Resistance transmitter 0-200 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 5k / 25 °C (–40 to + 125 °C)
Passive sensor NTC Thermistor 10k / 25 °C (-40 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
Passive sensor NTC Thermistor 15k / 25 °C (-40 to + 125 °C)
Passive sensor NTC Thermistor 20k / 25 °C (-40 to + 125 °C)
Input impedance in signal range RTD > 20 kΩ
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Resistance measurement error - temperature coefficient ± 0.05% of full scale / K
Resistance measurement error - non-linearity ± 0.09% of full scale
Resistance measurement error - repeatability at steady conditions 0.07% of full scale
Detection of disconnected sensor yes, in status word, range overflow
AO - Analog output parameters
Common wire of group minus
Galvanic isolation from internal circuits No
Output type active voltage output
Converter resolution 12 bit
conversion time 10 μs
Analog output error - maximum error at 25 ° C ± 2% of full scale
Analog output error - temperature coefficient ± 0.3% of full scale / K
Analog output error - linearity ± 0.7% of full scale
Analog output error - repeatability under steady state conditions ± 0.5% of full scale
Voltage output - voltage 0 - 10,5 V
Voltage output - Resolution 1 LSB 2,589 mV
Voltage output - maximum output current 10 mA
Power supply
Supply voltage, tolerances 24 V DC, +25%, -15%, SELV
Maximum power input 10 W
Module thermal/power loss 12 W
Internal protection Yes, PTC reversible fuse
CIB branch power supply - parameters of the built-in master 1x 100 mA/ 24 V DC
Power supply from ETH, passive PoE - input (appliance) ETH1/Power In
Power supply from ETH, passive PoE - output (source) ETH2 / Power out, jumper configuration
Power supply from ETH, passive PoE - injector parameters 24 V DC, 1A
Size and weight
Weight approx. 200 g
Product dimensions (width x height x depth) 105 x 90 x 62 mm
Module width in multiples of M (17.5 mm) 6M
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box according to the internal packing instructions. The package includes the following documentation. The outer packaging is carried out according to the scope of the order and the method of transport to the transport a package bearing the transport labels and other particulars necessary for transport. Transport from the manufacturer is carried out in the manner agreed upon when ordering. Product transport the customer's own means must be carried out by covered means of transport, in the specified position label on the packaging. The box must be stowed so as to prevent spontaneous movement a damage to the outer packaging. The product must not be exposed to direct weathering during transport and storage influences. Transport is allowed at temperatures from -25 ° C to +70 ° C, relative humidity 10% up to 95% (non-condensing) and a minimum atmospheric pressure of more than 70 kPa. Storage of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Switchboard mounting
Assembly description The basic module is mounted vertically on the U-rail ČSN EN 50022. The installation of the assembly (basic module and peripheral modules, if applicable) is performed according to TXV 004 50.
Exchangeable submodules The optional MR-013x submodules of the serial interface are mounted in the base module CP-2007 on the bottom plate, which is accessible after removing the bottom of the housing. We only handle the module without power supply!
Connection
Connection of power and system communication connector with 2.5 mm2 screw terminal
Connection of inputs / outputs connector with screw terminal 2.5 mm2
Ethernet RJ-45
Serial channels screw-type connector 9x 1.5 mm2
USB device connection type micro B
USB host connection type A
Module operation
Module configuration The module is operated, set and diagnosed from the MOSAIC programming environment. It is also possible to connect to the PLC using a web browser on port 8080. If the PLC has an IP address set eg 192.168.134.178 (default address on port ETH1, port ETH2 has DHCP enabled), just enter the address in the form http://192.168.134.178:8080 and the web browser displays the PLC configuration pages.
Commissioning The module is ready for operation after connection of the supply voltage. The MODE button is available on the module panel to display the currently set IP address of the Ethernet interface. Parameters of all interfaces are set in the Mosaic programming environment. The exact setup procedure is given in the TXV 004 50 documentation.
Module diagnostics The basic diagnostic system of the module is part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled on the module display and are available for processing by the master system. For more information, see TXV 004 50.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

CP-2005 - Basic documentation (en)

4.81 MB, (EN)

User manuals

PDF

CP-2005 - User's Guide (en)

2.69 MB, (EN, RU, DE)
PDF

Foxtrot 2 - Serial communication (en)

2.25 MB, (EN, RU, DE)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)

No data available.

No data available.