C-IR-0203STXN 133 65

C-IR-0203S; CIB, 2x AI / DI Temperature / contact, 2x AO (0-10V); 1x RO, 230V / 16A (inrush 80A) make / break contact

DI 2x DI/AI
DO
AI 2x DI / AI see DI
AO 2x AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-IR-0203S
C-IR-0203S is a module designed for connection to the CIB bus. Contains
- two combined analog or binary inputs
- two analog outputs with a range of 0-10 V
- one relay output with changeover contact.

Inputs and analog outputs are connected to the terminal block with pen terminals, the relay output to the terminal block with screw cage terminals.

- The inputs allow direct connection of resistance sensors PT1000, Ni1000, sensor with thermistor NTC12k or KTY81-121 against a common GND wire. The resistance is converted in the module directly to a numerical temperature value.
- For another type of resistance sensor, resistance measurement in the range 0-160 kΩ can be selected, but the conversion to temperature and linearization must be performed only at the level of the user program.
- The binary signals are connected to the inputs only as a free potential-free contact against the common conductor GND, or the input can operate in balanced input mode.
- The 0-10 V analog outputs are connected to a common GND conductor.
Order num. TXN 133 65
Teco code TXN 133 65
Categories CFox - Built-in modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminals DO1
Number of relay outputs 1
Output type electromechanical relay, unprotected output
Contact type NO / NC changeover contact
Galvanic separation from internal circuits Yes
Diagnose Alarm signaling on panel module
Switching current 16 A max., 100 mA min.
Switching voltage 300 V max., 5 V min.
Contact closing time typ. 15 ms
Contact opening time typ. 5ms
Short-circuit protection No
Insulation voltage between outputs and internal circuits 3750 V AC
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Number of analog input groups 1
Input type With common clamp
Common wire Minus
Galvanic separation from internal circuits No
Diagnostics overload signaling in status word
AO - Analog output parameters
The number of groups of analogue outputs 1
Common wire of group minus
Galvanic isolation from internal circuits No
Output type active voltage output
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation I, according to ČSN EN 60664-1 ed_2:2008 (idt IEC 60641-1:2007)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Connection
Connection of power and system communication terminal block with spring clamp 1 mm2, push-in
Connection of inputs / outputs terminal block with spring clamp 1 mm2, push-in
Specific I / O Relay output
Connection of specific I / O terminal block with screw terminal 1.5 mm2
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IR-0203S - Basic documentation

873.45 kB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-IR-0203S - The C-IR-0203S module is designed to connect two temperature sensors or binary signals, controlled by the power relay contact; it is fitted with two analogue outputs directly on the CIB bus. The PT1000 or Ni1000 resistance sensors can be connecte...
  • HELVAR ballast control by C-IR-0203S module - To control the HELVAR electronic ballasts (and similar types of other manufacturers) designed to dim fluorescent lamps controllable by analog voltage 0 ÷ 10 V or 1 ÷ 10 V, it is possible to use e.g. the C-IR-020 3S module,...
  • Switching of LED lighting, light bulbs, fluorescent lamps, etc. - ...h short-term switching current up to 800 A C-HM-1121M 3 relay outputs with short-term switching current up to 800 A C-IR-0203S 1 relay output with short-term switching current up to 80 A R-OR-0001B 1 relay output with short-term switch...
  • 0 ÷ 10 V ballast control by C-IR-0202S module - For controlling the electronic ballasts of fluorescent lights controllable by analog voltage 0 ÷ 10 V or 1 ÷ 10 V e.g. the C-IR-0202S module can be used, which is equipped with a relay output for switching off the ballast...

No data available.