MR-0152TXN 101 52
MR-0152, PROFIBUS DP Slave, with its own power supply, galvanic isolation
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 1x PROFIBUS DP (RS-485) |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
MR-0152 |
The MR-0152 submodule contains PROFIBUS DP Slave controllers and an RS-485 interface, including galvanic isolation from the system and galvanic isolation power supply circuits. At the same time, the submodule contains identification circuits (the user has the possibility to identify the type of submodule used from the development environment).
Order num. | TXN 101 52 |
---|---|
Teco code | TXN 101 52 |
Categories | Foxtrot 1 - Accessories for basic modules, TC700 - Accessories for central modules |
Tags | Sales and production discontinued |
COM - Serial channels | |
---|---|
Number of internal RS-485 serial channels | 1 |
Max. baud rate | 9.6lbit/s -12 Mbit/s |
Line impedance | 135 to 165 ohmsОт 135 до 165 Ом |
Max. length of connected line (RS-485) | 1200/100m |
Power supply | |
Supply voltage, tolerances | The submodule is powered from the power supply the terminal device in which it is installed. |
Maximum power input | 1,2 W |
Galvanic separation of power supply from internal circuits | No |
Insulation voltage of galvanic separation | 1 000 VDC |
Size and weight | |
Weight approx. | 25 g |
Product dimensions (width x height x depth) | 35,6 x 52 x 10 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Type of device | Submodule |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Packaginng, transportation, storage | |
Description | The submodule is packed in a paper box according to the internal packing instructions. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with transport labels and other data necessary for transport. Transport from the manufacturer is carried out in the manner agreed upon when ordering. The transport of the product by the customer's own means must be carried out by covered means of transport, in the position specified by the label on the packaging. The box must be stored in such a way that it does not move spontaneously and the outer packaging is not damaged. The product must not be exposed to direct weather conditions during transport and storage. Transport is permitted at temperatures of 40 ° C to 70 ° C, relative humidity of 10% to 95% (non-condensing) and a minimum atmospheric pressure higher than 70 kPa. The product may only be stored in clean rooms free of conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C. |
Installation | |
Assembly description | The installation of the submodule into the central module of the TC700 system is performed according to TXV 004 02, chapter 2.3. The submodule is installed in positions accessible after removing the side door on the module cover. The submodule must be fitted on the connector side of the module with the full number of pins (the number of terminals on the submodule and the module must match), on the other side it is mounted on the inner row of the three-row connector. An unconnected tip remains on each side of the module connector strip - see. picture The installation of the submodule into the TEMPO system is performed according to the TXV 190 02 documentation. The installation of the submodule into the TC650 system is performed according to the documentation "Technical equipment of the TC650 series PLC" TXV 138 22. |
Attention! | The modules contain components sensitive to electrostatic charge, so we observe them principles for working with these circuits! We handle only on the module disconnected from the power supply! When replacing the submodules, the correctness of the deployment must be carefully checked of the submodule cavities against the tips on the motherboard. The tubes have no coding position and incorrect installation, may occur when the power is turned on again damage to the submodule or even the motherboard !!! |
Connection | |
Connection description | The communication interfaces of the central modules CP-700x and the communication modules SC-710x of the TC700 series are equipped with identical screwless connectors. See connector connection table. Detailed connection data, principles of correct installation, examples of interface connections and principles of increasing durability and reliability are given in the TXV 001 08.01 design manual. |
Connection via connectors | Hollow bar |
Module operation | |
Module configuration | The submodule is operated and diagnosed from the program of the system in which it is used. |
Commissioning | The submodule is ready for operation after inserting it into the position in the module and switching on the system power supply. |
Module diagnostics | The submodule itself is not equipped with any diagnostics. The status of the communication line (activity of transmitted and received data) is indicated on the module panel. |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
Files for designers
MR-0152 - basic documentation
290.39 kB
User manuals
OVERVIEW OF TECOMAT SUB-MODULES (en)
671.90 kB, (EN)
- MR-0152 - PROFIBUS DP interface, with galvanic isolation - The MR-0152 submodule allows the connection of PLC TECOMAT Foxtrot to the PROFIBUS DP network as a slave station (subordinate) at the data transfer rate up to 12MBd. It can only be used in the DPS mode (further see TXV 004 10 ). Since the PRO...
- MR-0152 - PROFIBUS DP interface, with galvanic isolation - The MR-0152 submodule enables the connection of the TECOMAT TC700 PLC to the PROFIBUS DP network as a slave station with a transfer rate of up to 12 MBd. It can only be used in PCB mode. Due to the fact that the physical interface of the PROFIBUS...
No data available.