C-HM-0308MTXN 133 24
C-HM-0308M; CIB, 3x AI/DI, 2x AO, 6x RO/5A
DI | 3x AI/DI |
---|---|
DO | 6x RO |
AI | 3x AI / DI see DI |
AO | 2x AO |
COM | 1x CIB slave |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
C-HM-0308M |
C-HM-0308M; CIB, 3x AI/DI, 2x AO, 6x RO/5A
Order num. | TXN 133 24 |
---|---|
Teco code | TXN 133 24 |
Categories | CFox - Modules on DIN rail |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
DI - Parameters of binary inputs DC (group A) | |
Parameters valid for inputs on the terminals | see AI |
Number of inputs in group | 3 |
Common wire | plus |
Combined input type | DI/AI Active, for sensing potential-free contacts and measuring resistance sensors |
Galvanic isolation of inputs from internal/peripheral circuits | No |
Diagnostics | signaling of excited input in Mosaic |
Pulse input overload capacity | max. 30 V (t < 10 ms) |
Input current at log. 1 (typ.) | 2,5 mA typ. |
Delay from log. 0 to log. 1 | 500 μs |
Delay from log. 1 to log. 0 | 500 μs |
The minimum width of the captured pulse | 500 μs |
RO - Parameters of binary relay outputs (group A) | |
Number of relay outputs | 6 |
Number of output groups | 2 |
Number of outputs in group | 3 |
Output type | electromechanical relay, unprotected output |
Contact type | NO - Normally Open |
Diagnose | Alarm signaling on panel module |
Switching voltage | 250 V AC max., 5 V AC min., 30V DC max. |
Current through common clamp | 10 A max. |
Contact closing time | typ. 15 ms |
Limit values of switched resistive load | max. 3A at 30 V DC or 230 V AC |
Short-circuit protection | No |
AI - Organization of analog inputs | |
Total number of analog inputs | 3 |
Number of inputs per group | 3 |
Number of analog input groups | 1 |
Galvanic separation from internal circuits | No |
External power supply | No |
Digital resolution | 12 bit |
Converter type | Approximation |
conversion time | 20 μs |
AI - Analog Input Ranges (Group A) | |
Voltage | 0 to 2 V / 805.9 μV |
Voltage | 0 -1 V |
Open input detection | No |
Passive sensor | Pt1000, W100 = 1,385 (-90 to +400 ° C) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Ni1000, W100 = 1.617 (-60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-600 kOhm |
Passive sensor | Resistance transmitter 0-6 MOhm |
Passive sensor | KTY81-121; PTC thermistor (-55 to + 125 °C) |
Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
AO - Analog output parameters | |
The number of groups of analogue outputs | 1 |
Common wire of group | GND terminal |
Galvanic isolation from internal circuits | No |
Output type | active voltage output |
Power supply | |
Nominal supply voltage (V) | 24 V DC |
Maximum power input | 2 W |
Module thermal/power loss | 2,1 W |
Power supply from CIB - maximum current consumption (mA) | 90 mA |
Galvanic separation of power supply from internal circuits | No |
Internal protection | No |
Size and weight | |
Product dimensions (width x height x depth) | 52 x 90 x 58 mm |
Module width | 52 mm |
Module height | 90 mm |
Module depth | 58 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Module on DIN rail |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description | Hotel module C-HM-0308M is mounted in a vertical position on the U-rail ČSN EN 50022. Installation of the set (basic module and possibly peripheral modules) is performed according to TXV 004 13. |
Connection | |
Connection description |
Hotel modules are implemented as standard units on a two-wire CIB bus, which ensures communication and power supply of the entire module. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the FOXTROT basic unit or the MI2-02M module. Further information can be found in the manual Peripheral modules on the CIB TXV 004 13. |
Connection of power and system communication | connector with 2.5 mm2 screw terminal |
Connection of inputs / outputs | connector with screw terminal 2.5 mm2 |
Module operation | |
Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
Commissioning | The module is ready for operation after connecting the supply voltage. The MODE button is available on the module panel to display the currently set Ethernet IP address. The parameters of all interfaces are set in the Mosaic development environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 2006/42 / EC for machinery, in so far as it applies to them. |
HW documentation
C-HM-0308M - Basic documentation
1.42 MB, (EN)
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- C-HM-0308M - ...minute. This must be taken into consideration when using relay outputs. Fig. 1 The basic connection of the C-HM-0308M module Notes: The analogue inputs AI1 to AI3 are intended for connecting the temperature sensors...
- Measuring solar radiation by the S-SI-01I sensor with the C-HM-0308M module - ...solar radiation can be done by the S-SI-01I module, which should be connected to the analogue inputs of the modules C-HM-0308M , C(R)-HM-1113M or C(R)-HM-1121M. The solar radiation sensor uses for its own measurement of intensity a mon...
- Power dissipation of modules for calculation of switchboard heating - ...for measuring transformers with 100mA output C-EM-0401M-S 4,0 W TXN 133 24 C-HM-0308M; CIB, 3x AI/DI, 2x AO, 6x RO/5A C-HM-0308M 2,1 W TXN 133 45 C-DM...
- Measurement of soil moisture (irrigation systems) - ...ation and as per the documentation [ 11 ] . Fig. 1. Wiring the soil moisture sensor to the C-HM-0308M module. Notes: The standard length of the supply cable is 2m. Other l...
- The separate temperature sensor S-TS-01R, connected to the AI of the system - ...ith an appropriate range, e.g. the AI1 to AI4 inputs of the C-IB-1800M module , the AI1 to AI3 inputs of the modules C-HM-0308M , C (R) -HM-1113M and C (R) -HM-1121M . Fig. 1. An example of connecting the S-T...
- Measurements of dewing (condensation of air humidity) - ...ap.11.4. 3 ) can be attached to the AI5 input of the C-AM-0600I module, or to the inputs AI1 to AI3 of the modules C-HM-0308M , HM-C-1113M and C-HM-1121M . In order for the dew sensor to function properly, it must hav...
- Dew point monitoring (condensation on the distribution system of fan-coils, etc.) - ...raps to the bottom part of the piping. Fig. 1. An example of connecting the condensation sensor to the C-HM-0308M module. Notes: The condensation sensor can be connected to any input of the module (AI1...
- Point level monitoring of water level in the well or in a tank - ...done by conductive probes (e.g. the CNP-18) connected to analogue inputs intended measuring condensation, e.g. the C-HM-0308M . Monitoring the minimum and maximum levels requires three probes with sufficient lengths of stems to allow eval...
- Defrosting outdoor spaces, the ESF 524 001 sensor - ...les can be controlled by any relay output of the control system (according to the switching power). The connection to the C-HM-0308M module is shown in the following figure. Fig. .1 A wiring example – defrosting of sm...
- Defrosting gutters, the ESD 524 03 sensor - ...an appropriate range (the humidity sensor is connected to the input for condensation measurement). The connection to the C-HM-0308M module is shown in the following figure. Fig. 1. A wiring diagram – defrosting gutte...
- Flood monitoring – utility room, cellar - ...actual DS sensor should be connected to the module with a respective input for flooding, e.g. the C-AM-0600I or the C-HM-0308M. Parameters of the DS flood sensor Ambient temperature...
- Control of the 24 V TORO valves for the irrigation systems - ...alves by relay outputs of the CP-1006 basic module. The relay outputs of other modules can be used in the same way, e.g. the C-HM-0308M, etc. Thanks to the small initial and trickle currents, relay outputs fitted with a 5 A and 16 A contacts can be u...
- Flood control – the bathroom, kitchen (water leakage from appliances) - .... The strip may be connected either to special condensation measurement inputs, e.g . the C-AM-0600I or the C-HM-0308M (these two have a high sensitivity even for liquids with low conductivity, of a very short pieces of the...
- The 5A relays, the Foxtrot basic modules and the peripheral CFox modules - These relays are fitted in e.g. the Foxtrot basic modules (CP-1005, CP1006, etc.), the peripheral modules ( C-HM-0308M , C-IR-0202S ) and others (see information on the individual modules ). The parameters of t...
- Water underfloor heating - ...m can be used for the control function. The following figure demonstrates the control of 6 actuators in the manifold. The C-HM-0308M module used in the example can be mounted directly in the manifold. For detailed information on suitable...
- Fan-coils - control - ...ition heating drives and cooling, with an example of connection of a condensation sensor and two temperature sensors. The C-HM-0308M module used in this case offers a possibility of controlling e.g. analogue-controlled drives, or controlling th...
- Connecting the CARRIER 30AWH__H heat pump - ...connection, see the heat pump instruction manual. The following figure shows an example of possible connection to the C-HM-0308M module (heat pump control) and measuring the heat pump current by the ED11.M electricity meter ....
- Ventilation and recuperation units - ...discreet speed control of 230 V motor revolutions relay modules, e.g. C-HM-0308M Continuous regulation of 230 V asynchronous motors, built-in version...
- Switching of LED lighting, light bulbs, fluorescent lamps, etc. - .... We can use any relay outputs of the Foxtrot system for switching classic light bulbs . E.g. relay outputs of the C-HM-0308M module are equipped with a relay with 5A contact, continuous switching current 3A, so we can switch up to 600W wi...
- Fan speed control, heat recovery units - The figure shows an example of controlling heat recovery units with two fans with EC motors, an actuator and a valve, up to three temperature sensors, and all connected to the C-HM-0308 module. Fig. 1. An example of connecting a heat rec...
- Electric underfloor heating - The direct electric underfloor heating can be designed similarly to hot water underfloor heating. The heating elements are in this case electric heating cables (the installation is similar to hot water systems), heating mats (a more convenient inst...