C-DL-2064MTXN 143 32
C-DL-2064M; CIB-DALI converter, for 64 DALI-2 ballasts
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 1x CIB 1x DALI/DSI |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
C-DL-2064M |
The module C‑DL‑2064M(Order No.: TXN 143 32) is a converter of protocols CIB‑DALI. It is intended for lighting systems with DALI protocol specification NEMA Standards Publication 243‑2004 Digital Addressable Lighting Interface (DALI) Control Devices Protocol PART 2‑2004. From version FW v.1.5 module can be used as a protocol converter CIB‑DSI.
Signals of CIB and DALI/DSI buses are connected to screw terminals. The internal circuits of the module are powered from the CIB bus. The output circuits of the DALI/DSI bus are powered by an external 24 V DC source. Program control functions of module is supported by function blocks from the DaliLib.mlb library.
Signals of CIB and DALI/DSI buses are connected to screw terminals. The internal circuits of the module are powered from the CIB bus. The output circuits of the DALI/DSI bus are powered by an external 24 V DC source. Program control functions of module is supported by function blocks from the DaliLib.mlb library.
Order num. | TXN 143 32 |
---|---|
Teco code | TXN 143 32 |
Categories | CFox - Modules on DIN rail |
Tags | - |
COM - Serial channels | |
---|---|
Communication interface DALI | 1x DALI master |
The scope of each DALI line | 64 addresses / substations |
Insulation voltage between buses | 2,5 kV AC |
COM - System buses | |
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
Power supply | |
Nominal supply voltage (V) | 24 V DC |
Auxiliary power supply - voltage | The DALI interface of the module is powered by an external 24 VDC source (terminals A3, A4) outside the CIB bus. The module provides galvanic isolation of the DALI bus from other circuits (CIB). The 24 V supply voltage of the module must be galvanically isolated (safe circuit separation) from the power supply of the Foxtrot system and the CIB bus. |
Power supply from CIB - typical current consumption (mA) | 30 mA |
Power supply from CIB - internal protection | Yes, returnable fuse |
Size and weight | |
Weight approx. | 70 g |
Product dimensions (width x height x depth) | 35 x 90 x 58 mm |
Module width in multiples of M (17.5 mm) | 2M |
Module width | 35 mm |
Module height | 90 mm |
Module depth | 58 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | III, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Overvoltage category installation | II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992) |
Type of device | Module on DIN rail |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 ° C to + 70 ° C |
Operating temperature maximum (° C) | +70°C |
Operating temperature minimum (° C) | 0°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 ° C to + 85 ° C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | ČSN EN 55022 ed2:2007 (mod CISPR22:2005) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description | Mounting on DIN rail 35 / 7.5 (U) in the switchboard |
Connection | |
Connection of power and system communication | terminal block with screw terminal 2.5 mm2 |
Cross-section of connected wires fixed (min) | 0,35 mm2 |
Cross-section of connected wires fixed (max) | 2,5 mm2 |
Cross-section of connected wires stranded (min) | 0,35 mm2 |
Cross-section of connected wires stranded (max) | 2,5 mm2 |
Module operation | |
Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-DL-2064M - Базовая документация (ru)
1.63 MB, (EN)
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
No data available.
No data available.