C-DL-2064MTXN 143 32

C-DL-2064M; CIB-DALI converter, for 64 DALI-2 ballasts

DI
DO
AI
AO
COM 1x CIB
1x DALI/DSI
SENSOR
Picture Variant Variant description
C-DL-2064M
The module C‑DL‑2064M(Order No.: TXN 143 32) is a converter of protocols CIB‑DALI. It is intended for lighting systems with DALI protocol specification NEMA Standards Publication 243‑2004 Digital Addressable Lighting Interface (DALI) Control Devices Protocol PART 2‑2004. From version FW v.1.5 module can be used as a protocol converter CIB‑DSI.
Signals of CIB and DALI/DSI buses are connected to screw terminals. The internal circuits of the module are powered from the CIB bus. The output circuits of the DALI/DSI bus are powered by an external 24 V DC source. Program control functions of modu­le is supported by fun­ction blocks from the DaliLib.mlb library.
Order num. TXN 143 32
Teco code TXN 143 32
Categories CFox - Modules on DIN rail
Tags -
COM - Serial channels
Communication interface DALI 1x DALI master
The scope of each DALI line 64 addresses / substations
Insulation voltage between buses 2,5 kV AC
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
Power supply
Nominal supply voltage (V) 24 V DC
Auxiliary power supply - voltage The DALI interface of the module is powered by an external 24 VDC source (terminals A3, A4) outside the CIB bus. The module provides galvanic isolation of the DALI bus from other circuits (CIB). The 24 V supply voltage of the module must be galvanically isolated (safe circuit separation) from the power supply of the Foxtrot system and the CIB bus.
Power supply from CIB - typical current consumption (mA) 30 mA
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 70 g
Product dimensions (width x height x depth) 35 x 90 x 58 mm
Module width in multiples of M (17.5 mm) 2M
Module width 35 mm
Module height 90 mm
Module depth 58 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Overvoltage category installation II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992)
Type of device Module on DIN rail
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 70 ° C
Operating temperature maximum (° C) +70°C
Operating temperature minimum (° C) 0°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Mounting on DIN rail 35 / 7.5 (U) in the switchboard
Connection
Connection of power and system communication terminal block with screw terminal 2.5 mm2
Cross-section of connected wires fixed (min) 0,35 mm2
Cross-section of connected wires fixed (max) 2,5 mm2
Cross-section of connected wires stranded (min) 0,35 mm2
Cross-section of connected wires stranded (max) 2,5 mm2
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-DL-2064M - Базовая документация (ru)

1.63 MB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.

No data available.