C-DM-0002L-10V; CIB, 2x dimmer with 0-10V output for dimming ballasts LED or fluorescent lamps, 2x RO

DI
DO 2x RO
AI
AO 2x AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-DM-0002L-10V
The C-DM-0002L-10V module is designed for independent two-channel control of electronic LED ballasts or fluorescent lamps, controlled by 0-10 V DC or 1-10 V DC.
To completely disconnect the ballasts from the main power supply, the module contains 2 relay outputs, one with an NC contact and the other with changeover contacts.
Of course, analog inputs and relay outputs can also be used universally for other purposes.

The module is designed for a DIN rail switchboard, but it can also be built into the body of the luminaire. It is connected to the Foxtrot basic module via a two-wire CIB Common Installation Bus®.
Order num. TXN 133 78
Teco code TXN 133 78
Categories CFox - Modules on DIN rail
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
RO - Parameters of binary relay outputs (group A)
Number of relay outputs 1
Output type electromechanical relay, unprotected output
Contact type NO - Normally Open
Switching voltage max. 400 V AC
Switching power 4000 VA max., 384 W max.
Short-term output overload - inrush max. 800 A (max. 200 μs)
Contact closing time typ. 10 ms
Contact opening time typ. 5ms
Mechanical life min. 5,000,000 cycles
Electrical life at rated load min. 50,000 switchings
Short-circuit protection No
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 4000 V AC
Insulation voltage between contacts 1250 V AC
RO - Parameters of binary relay outputs (group B)
Parameters valid for the terminals DO2
Number of relay outputs 1
Output type electromechanical relay, unprotected output
Contact type NO / NC changeover contact
Switching current 16 A max., 100 mA min.
Switching voltage 440 V AC/ 300 V DC
Switching power 4000 VA
Short-circuit protection No
Short-term output overload 80 A max. (20 ms max.)
Contact closing time typ. 10 ms
Contact opening time typ. 5 ms
Mechanical life min. 10,000,000 cycles
Electrical life at rated load min. 10,000 switchings (inrush 80 A)
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 5000 V AC
Insulation voltage between contacts 1000 V AC
AO - Analog output parameters
Parameters valid for the terminals AO1
Galvanic isolation from internal circuits No
Output type active voltage output
Voltage output - voltage 0 - 10 V
Voltage output - Minimum resolution 1 %
Voltage output - Adjustable range 0 ÷ 125 % Ujm
Voltage output - Load resistance >1 kΩ
Voltage output - Load capacity 50 nF
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Power supply from CIB - maximum current consumption (mA) 60 mA
Galvanic separation of power supply from internal circuits No
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 200 g
Product dimensions (width x height x depth) 35 × 92 × 32 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 3:2012 (mod IEC 60730-1:2010)
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.3: 2012
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The module is mounted in a vertical position on the U-rail ČSN EN 50022. Installation of the assembly (basic module and possibly peripheral modules) is performed according to TXV 004 13.
Connection
Connection of power and system communication terminal block with spring terminal 1.5 mm2, push-in
Connection of inputs / outputs terminal block with spring terminal 1.5 mm2, push-in
Module installation tools (-) 2 mm, flat screwdriver
Module connection The connection of the module to the CIB bus, analog outputs and contacts of relay outputs is realized by two terminal blocks with spring terminals. This is done by inserting the wire directly into the wire hole on the terminal. These terminals are intended for the connection of a solid conductor. If it is necessary to connect the cable conductor, it is necessary to crimp suitable cable sleeves at its ends. The suitable stripping length of the conductor / sleeve is 8 mm. The wire is released from the clamp by pushing the tip of a flat-blade screwdriver (recommended size 0.4x2 mm) inserted into a groove in a bright target located near the hole for the wire. The CIB bus (terminals A1, A2) is connected to the upper terminal block. The number of modules on the CIB bus is limited by the maximum permitted bus current. Furthermore, the analog outputs AO1 and AO2 (terminals A3 to A6) are output here. The contacts of relay outputs DO1 and DO2 (terminals B1 to B6) are connected to the lower terminal board. An example of the module connection is shown in the following figure (terminal designations on the ballast used may differ depending on the specific type used).
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostic system of the module is part of its standard software. It has been in operation since the module power was turned on and works independently of the user. Diagnosed error states of the module and connected peripheral modules of the assembly are signaled in the status word of the module and on the module panel
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-DM-0002L-10V - Basic documentation

753.70 kB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Scheme

C-DM-0002L-10V

C-DM-0002L-10V

42.64 kB
C-DM-0002L-10V

C-DM-0002L-10V

44.49 kB
C-DM-0002L-10V

C-DM-0002L-10V

47.12 kB

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity