OT-8651TXN 186 51
OT-8651, 12 bit; 4xAO, 0-10 V, ±10 V, 0(4)-20 mA
DI | |
---|---|
DO | |
AI | |
AO | 4x AO |
COM | TCL3 |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
OT-8651 |
OT-8651 - expansion module contains 4 analog outputs AO0 to AO3. The outputs have separate terminals and are output as voltage with a range of 0 ÷ 10 V, as well as current with a range of 0 ÷ 20 mA. However, the output cannot be connected as both voltage and current at the same time. Loads of both types are connected against the ground. The resolution is 12 bits, the output value can be set in percent of the maximum value, in engineering units or fullscale (0-30000). The current outputs have an indication of the disconnection of the current loop (open circuit) on the front panel. Current loop disconnection detection is only functional when the output current is set to at least 100 µA.
The analog outputs are galvanically isolated from the internal circuits and from each other. The module is equipped with a removable screwless connector with 17 terminals and with locking after insertion into the module.
The analog outputs are galvanically isolated from the internal circuits and from each other. The module is equipped with a removable screwless connector with 17 terminals and with locking after insertion into the module.
Order num. | TXN 186 51 |
---|---|
Teco code | TXN 186 51 |
Categories | TC800 - I / O expansion modules |
Tags | - |
COM - System buses | |
---|---|
TCL3 - system I/O bus | 1x TCL3 slave |
AO - Analog output parameters | |
The number of groups of analogue outputs | 1 |
Number of outputs in group | 4 |
Organization of outputs in groups | 4x AO (AO0-AO3) |
Parameters valid for the terminals | AO0-AO3 |
Common wire of group | AGND terminal |
Galvanic isolation from internal circuits | Yes |
Galvanic isolation of outputs from each other | Yes |
Output type | active voltage output |
Diagnostics | LED on panel, flag in status to indicate disconnected output |
Disconnected output detection | Yes current loop from 0.1 mA |
Overload signaling | No |
Maximum output value | 105% of the upper limit of the output range |
Max. permissible permanent overload (without damage) | (-1 V) to (+ Vao + 1V) each terminal against AGND |
Converter resolution | 12 bit |
Analog output error - maximum error at 25 ° C | ± 0.3% of full scale |
Output repeat setting time | typ. 0,5 ms |
Analog output error - temperature coefficient | ± 0.05% of full scale/K |
Analog output error - linearity | ± 0.1% of full scale |
Analog output error - repeatability under steady state conditions | ± 0.5% of full scale |
External power supply | typ. 24 V DC |
External power supply - tolerance | - 25 ÷ +20% |
External power supply - max. Current consumption | 135 mA |
Voltage output - voltage | ±10,5 V |
Voltage output - maximum output current | 10 mA |
Voltage output - short-circuit output current | 12 mA |
Current output - range | 0 ÷ 20 mA |
Current output - 1 LSB resolution | 6,1 µA |
Current output - current loop resistance | 0 ÷ 600 Ω |
Power supply | |
Supply voltage UVM, UVIO, nominal value | 24 V DC |
Supply voltage UVM, UVIO, allowed range | 20 - 30 V DC |
IVM supply current at UVM = 24 V | 12 mA |
IVIO supply current at UVIO = 24 V | max. 135 mA |
Max. power consumption at the VM level | 0,2 W |
Max. input power at VIO level | 3,2 W |
Module thermal/power loss | 4 W |
Galvanic separation of power supply from internal circuits | Yes |
Size and weight | |
Weight approx. | 85 g |
Product dimensions (width x height x depth) | 24 x 118 x 97 mm |
Packaging dimensions (width x height x depth) | 27 х 119 х 108 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units |
Protection class of electrical object | II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Built-in |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Storage relative humidity | Max. 80% without vapor condensation |
Storage environment | Dry, clean areas without conductive dust, aggressive gases or acid vapors for a period not exceeding the warranty period. |
Transport temperatures | -25°C to -70°C |
Transport environment | Covered means of transport, transport packaging must not be exposed to the effects of rain and snow |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis . |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description | The installation of the TC800 system module is carried out by sliding it perpendicularly onto the DIN rail ČSN EN 50022 with busbar and locking latch in the lower part of the module. A more detailed description and mechanical drawings with dimensions are given in the documentation TXV 004 72. |
Connection | |
Warning | All external circuits connected to the module must meet the conditions for SELV circuits! |
Power connection | Via the system bus |
Connection of inputs / outputs | Connector with screwless terminals 2.5 mm2 |
Module installation tools | (-) 2 mm, flat screwdriver |
Connection description | An example of module connection is shown in the following figure. |
Module operation | |
Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
Commissioning | On the module, the DIP switch in the left part of the case sets a unique address within one frame. The module is fully ready for operation after inserting it into the frame and turning on the power supply. |
Module diagnostics | The basic diagnostic system of the module is part of its standard software. It has been in operation since the module power was turned on and works independently of the user. Diagnosed error states of the module and connected peripheral modules of the assembly are signaled in the status word of the module and on the module panel |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 2006/42 / EC for machinery, in so far as it applies to them. |
HW documentation
OT-8651 - Basic documentation
1.46 MB, (EN)
Files for designers
TC800 - library of elements in DXF and DWG formats, v. 2024/01
487.65 kB
TC800 - element library for SchemataCAD, v. 2024/01
116.21 kB
EC - Declaration of Conformity
TC800 - CE Declaration of Conformity (en)
709.29 kB
TC800 - CE declaration of conformity (cs)
292.20 kB
- Examples of power connections for TC800 modules - ...lay coils of the OR-8450 module and providing power for galvanically isolated sources for the analog part of the IT-8601 and OT-8651 modules. The required power of the source must be calculated according to the consumption from the VIO level of the i...
- TC800 power supply sizing calculation and heat loss - ...IT-8605 TXN 186 05 2 0,24 W 0,76 W 1 W 1 W OT-8651 TXN 186 51 2 0,2 W 3,2 W 3,4 W 3,4 W Notes:...
No data available.