IT-8602TXN 186 02
IT-8602; 16xAI, 16 bit resolution, 0-10V, RTD (even inputs only) standard ranges, 60ms/channel
| DI | |
|---|---|
| DI/AI | |
| DO | |
| AI | |
| AO | |
| COM | |
| SENSOR |
| Picture | Variant | Variant description |
|---|---|---|
|
|
IT-8602 |
The IT-8602 peripheral module contains 16 analog inputs. All inputs are galvanically
isolated from other PLC circuits.
The module is equipped with a screwless removable connector of 34 terminals with locking after insertion into the module.
The module input circuits require a 24 V DC power supply, which is connected (separately or
together with the main power supply) to the power supply module of the PLC assembly.
isolated from other PLC circuits.
The module is equipped with a screwless removable connector of 34 terminals with locking after insertion into the module.
The module input circuits require a 24 V DC power supply, which is connected (separately or
together with the main power supply) to the power supply module of the PLC assembly.
| Order num. | TXN 186 02 |
|---|---|
| Teco code | TXN 186 02 |
| Categories | TC800 - I / O expansion modules |
| Tags | - |
| AI - Analog Input Ranges (Group A) | |
|---|---|
| Max. permissible permanent overload of analog input (without damage) | ±60V maintaining accuracy, ±100V/1000h: 0.2% accuracy reduction, ±140V/1000h: 0.45% accuracy reduction |
| Power supply | |
| Supply voltage UVM, UVIO, nominal value | 24 V DC |
| Supply voltage UVM, UVIO, allowed range | 20 - 30 V DC |
| IVM supply current at UVM = 24 V | 9 mA |
| Size and weight | |
| Weight approx. | 125 g |
| Product dimensions (width x height x depth) | 24 x 118 x 118 mm |
| Operating conditions, product standards | |
| Product standard | ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units |
| Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
| IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
| Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
| Degree of pollution | 2, according to ČSN EN 60664-1 ed.2: 2008 (idt IEC 60664-1: 2007) |
| Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
| Type of device | Built-in |
| Working position | Vertical |
| Type of operation (operating frequency) | Continuous |
| Ambient operating temperatures | -20 °C to + 55 °C |
| Operating relative humidity | from 10 % up to 95 % without condensation |
| Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
| Storage temperatures | –25 °C to +70 °C |
| Storage relative humidity | Max. 80% without vapor condensation |
| Storage environment | Dry, clean areas without conductive dust, aggressive gases or acid vapors for a period not exceeding the warranty period. |
| Transport temperatures | -25°C to -70°C |
| Transport environment | Covered means of transport, transport packaging must not be exposed to the effects of rain and snow |
| Electromagnetic compatibility, Mechanical endurance | |
| Electromagnetic compatibility / Emission | A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
| Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
| Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
| Sinusoidal vibration endurance | 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis . |
| Packaginng, transportation, storage | |
| Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
| Installation | |
| Assembly description | The installation of the TC800 system module is carried out by sliding it perpendicularly onto the DIN rail ČSN EN 50022 with busbar and locking latch in the lower part of the module. A more detailed description and mechanical drawings with dimensions are given in the documentation TXV 004 72. |
| Attention! | The modules contain components sensitive to electrostatic charge, so we observe them principles for working with these circuits! We handle only on the module disconnected from the power supply! When replacing the submodules, the correctness of the deployment must be carefully checked of the submodule cavities against the tips on the motherboard. The tubes have no coding position and incorrect installation, may occur when the power is turned on again damage to the submodule or even the motherboard !!! |
| Connection | |
| Warning | All external circuits connected to the module must meet the conditions for SELV circuits! |
| Power connection | Via the system bus |
| Connection of inputs / outputs | Connector with screwless terminals 0.2 ~ 1.5 mm2 |
| Module installation tools | (-) 2 mm, flat screwdriver |
| Connection description | An example of module connection is shown in the following figure. |
| Module operation | |
| Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
| Commissioning | On the module, the DIP switch in the left part of the case sets a unique address within one frame. The module is fully ready for operation after inserting it into the frame and turning on the power supply. |
| Module diagnostics | The basic diagnostic system of the module is a part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled |
| Maintenance | |
| Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
| Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
| Warranty | |
| Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
| Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
IT-8602 - Basic documentation
1.92 MB, (EN)
Files for designers
TC800 - library of elements in DXF and DWG formats, v. 2025/01
493.14 kB
TC800 - element library for SchemataCAD, v. 2025/01
130.34 kB
EC - Declaration of Conformity
TC800 - CE declaration of conformity (cs)
292.20 kB
TC800 - CE Declaration of Conformity (en)
709.29 kB
- TC800 power supply sizing calculation and heat loss - ...IT-8601 TXN 186 01 2 0,3 W 0,8 W 1,4 W 1,4 W IT-8602 TXN 186 02 2 0,28 W 0,9 W 1,2 W 1,2 W IT...
No data available.