C-DM-0001B-SLTXN 133 81

C-DM-0001B-SL; CIB, control of a string of addressable RGB LEDs (WS2812)

DI
DO 1x DO (data)
1x SYN (in/out)
AI
AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-DM-0001B-SL
C-DM-0001B-SL is a module connectable to the CIB bus of the Foxtrot system. It contains one DO output for data addressable RGB LED chips type WS2812B, one IN / OUT terminal for synchronization of several modules in a row and a voltage source of 5 V / 1 A for powering a series of up to 16 LEDs.

It is equipped with a slot for a microSD card, on which data files for static and dynamic effects are uploaded. which the module "reads" and cyclically sends to a series of connected LED chips.
Order num. TXN 133 81
Teco code TXN 133 81
Categories CFox - Built-in modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals SYN - input and output terminal
Number of inputs in group 1
Galvanic separation of inputs from CIB bus No
Max. measuring voltage on the connected contact 3,3 V DC
Internal input resistance 10 kΩ
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals DO
Number of transistor outputs 1
Output type semiconductor output, half-bridge (push-pull)
Galvanic separation from internal circuits No
Diagnostics No
Output voltage 5 V DC
Output current 20 mA
Special functions (A) PWM / data - format WS2812B
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Auxiliary power supply - voltage The 5V terminal has an output of an integrated +5 V DC auxiliary power supply for powering the addressable WS2812B LED chips
Maximum power input 5,2 W
Power supply from CIB - maximum current consumption (mA) 210 mA
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 30 g
Product dimensions (width x height x depth) 50 x 50 x 30 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation I, according to ČSN EN 60664-1 ed_2:2008 (idt IEC 60641-1:2007)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -10°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Installation
Assembly description The module C-DM-0001B-SL is mounted in arbitrary position into instalation box under a lid or under device located in box. Installation of this   module is done as described in TXV 004 13 documentation.
Connection
Connection of power and system communication terminal block with screw terminal 1.5 mm2
Connection of inputs / outputs terminal block with screw terminal 1.5 mm2
Module installation tools (-) 3 mm, flat screwdriver
Module connection The C-DM-0001B-SL module has a CIB bus, one DO output terminal (PWM) for LED control and one SYN (digital) synchronization I / O terminal for synchronization control of other C-DM-0001N-SL modules. The SYN terminal type is selected by software. The CIB bus master is a basic Foxtrot module or an external module, such as the CF-1141. The maximum number of modules on the line is limited by taking the module from the line. Further information can be found in the TXV 004 13 manual "Peripheral modules on the CIB bus".

An example of the module connection is shown in the figure. The MICRO SD card is not part of the module.
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnosis is done internally and the result is availablein the relevant registers of Mosaic. After power on light greenRUN LED, when communication is start it stay flashing. State ofrelay ON is indicate by lighting of appropriate green LED.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-DM-0001B-SL - Basic documentation

1.21 MB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Scheme

C-DM-0001B-SL

C-DM-0001B-SL

99.62 kB
C-DM-0001B-SL

C-DM-0001B-SL

15.26 kB

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.