C-WG-0205STXN 143 36
C-WG-0205S; CIB, 2x AI/DI/EZS 5x DO (4x PWM), 1x interface for RFID reader SL031
DI | 2x AI/DI |
---|---|
DO | 5x DO |
AI | 2x AI / DI (R, binary, balanced) |
AO | Power output 12V / 60mA |
COM | 1x CIB |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
C-WG-0205S |
The module is intended for connecting the RFID reader SL031 (13.56MHz) with an integrated antenna for reading Mifare 1k, Mifare 4k, Mifare UltraLight and NFC NTAG203 tags. In addition to the signals for connecting the reader, the module contains 2 universal DI/AI inputs and 5 DO (4x PWM) outputs.
DI/AI inputs can be set as binary potential-free or balanced EZS or as analog for measuring temperature or resistance. Resistance sensors PT1000, Ni1000, NTC12k thermistor sensor, or KTY81-121 are used for temperature measurement.
DI/AI inputs can be set as binary potential-free or balanced EZS or as analog for measuring temperature or resistance. Resistance sensors PT1000, Ni1000, NTC12k thermistor sensor, or KTY81-121 are used for temperature measurement.
Order num. | TXN 143 36 |
---|---|
Teco code | TXN 143 36 |
Categories | CFox - Built-in modules |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
DI - Organization of binary inputs | |
Total number of binary inputs | 2 |
Number of groups of binary inputs | 1 |
Organization of binary inputs into groups | 2x DI (AI1 - AI2) |
DI - Parameters of binary inputs DC (group A) | |
Parameters valid for inputs on the terminals | AI1 - AI2 |
Number of inputs in group | 2 |
Common wire | GND - module ground |
Combined input type | DI / AI - measurement of resistance sensors, sensing of potential-free contacts and balanced loops |
Galvanic isolation of inputs from internal/peripheral circuits | No |
Max. measuring voltage on the connected contact | 3,3 V DC |
Internal input resistance | 2 kΩ |
Max. resistance for closed contact, log. 1 | < 0,5 kΩ |
Min. resistance for open contact, log. 0 | > 4,2 kΩ |
Balanced resistance input | 2× 1k1 (tamper/0/1/tamper) |
DO/RO - Organization of binary outputs | |
Total number of binary outputs | 5 |
Number of binary output groups | 2 |
Organization of binary outputs into groups | 4x (DO1 - DO4) 1x (DO5) |
DO - Parameters of binary transistor outputs (group A) | |
Parameters valid for the terminals | DO1-DO4 |
Number of outputs in group | 4 |
Organization of transistor outputs into groups | 3 (DO1-DO3) |
Output type | MOSFET (High-side switch) |
Galvanic separation from internal circuits | No |
Galvanic isolation of the outputs from CIB | No |
Diagnostics | No |
Switching voltage | 9 - 30 V DC |
Group current | 160 mА |
Output current | 160 mA |
Switching time | typ. 40 μs (12-24V, 60-160mA) |
Opening time | typ. 70 μs (12-24V, 60-160mA) |
Short circuit protection | Yes |
Special functions (A) | PWM |
Operating frequency | 100 Hz ÷ 2 kHz |
DO - Parameters of binary transistor outputs (group B) | |
Parameters valid for the terminals | DO5 |
Common group conductor | COM2 |
Output type | transistor output |
Galvanic separation from internal circuits | Yes |
Switching voltage | 0 - 48V DC |
Switching current, output load | 80 mA (160mA @ 25˚C) |
Short circuit protection | No |
AI - Organization of analog inputs | |
Total number of analog inputs | 2 |
Number of inputs per group | 2 |
Number of analog input groups | 1 |
Organization of analog inputs into groups | 2x (AI1, AI2) |
Input type | AI / DI - combined |
Common wire | GND terminal |
Galvanic separation from internal circuits | No |
Diagnostics | overload signaling in status word |
Digital resolution | 10 bit |
AI - Analog Input Ranges (Group A) | |
Parameters valid for inputs on the terminals | AI1, AI2 |
Passive sensor | Pt1000, W100 = 1,385 (-90 to +400 ° C) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Ni1000, W100 = 1.617 (-60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-100 kOhm |
Passive sensor | Resistance transmitter 0-160 kOhm |
Passive sensor | KTY81-121; PTC thermistor (-55 to + 125 °C) |
Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
Power supply | |
Supply voltage, tolerances | 24/27 V DC from CIB bus |
Auxiliary power supply - voltage | Supply output +22V OUT: U0 = CIB bus voltage -1 V, Iout max = 60mA, internal resistance R < 88 Ω |
Typical power input | 0,5 W |
Maximum power input | 2,2 W |
Module thermal/power loss | 0,4 W |
Power supply from CIB - typical current consumption (mA) | 20 mA |
Power supply from CIB - maximum current consumption (mA) | 80 mA |
Description of power supply | Difference between typical and maximum power input is given by possible load of CIB buses and number of switched outputs and CPU load |
Thermal/power loss of the module max. | 0.65W (at maximum consumption of outputs powered by auxiliary voltage +22V OUT) |
Size and weight | |
Weight approx. | 7 g |
Product dimensions (width x height x depth) | 55 × 26 × 16 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes) |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | In the installation box, under the cover |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 ° C to + 55 ° C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 ° C to + 85 ° C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | ČSN EN 55022 ed2:2007 (mod CISPR22:2005) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | Модуль упакован в антистатический пакет. Эта документация также является частью пакета. Внешняя упаковка осуществляется в соответствии с объемом заказа и способом транспортировки в транспортной упаковке, снабженной этикетками и другими данными, необходимыми для транспортировки. Продукт не должен подвергаться воздействию прямых погодных условий во время транспортировки и хранения. Соложение продукта разрешено только в чистых помещениях. без токопроводящей пыли, агрессивных газов и паров. Наиболее подходящая температура хранения - 20 ° C. |
Installation | |
Assembly description | The module C-DM-0001B-SL is mounted in arbitrary positioninto instalation box under a lid or under device located in box. |
Connection | |
Connection of power and system communication | terminal block with spring terminal 0.15-0.5 mm2, push-in |
Connection of inputs / outputs | terminal block with spring clamp 0.15-0.5 mm2, push-in |
Connection description | An example of module connection is shown in the following figure. |
Module operation | |
Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
HW documentation
C-WG-0205S- Basic documentation
390.82 kB, (EN)
- C-WG-0205S and SL031 reader connection example and EV-T2SOC-P socket LED indication - ...ith terminal blocks A, B and C on both sides, see Fig. 1. Fig. 1 Module C-WG-0205S, terminal block Fig. 2 Example of connecting the SL031 reader and the E...