C-WG-0205STXN 143 36

C-WG-0205S; CIB, 2x AI/DI/EZS 5x DO (4x PWM), 1x interface for RFID reader SL031

DI 2x AI/DI
DO 5x DO
AI 2x AI / DI (R, binary, balanced)
AO Power output 12V / 60mA
COM 1x CIB
SENSOR
Picture Variant Variant description
C-WG-0205S
The module is intended for connecting the RFID reader SL031 (13.56MHz) with an integrated antenna for reading Mifare 1k, Mifare 4k, Mifare UltraLight and NFC NTAG203 tags. In addition to the signals for connecting the reader, the module contains 2 universal DI/AI inputs and 5 DO (4x PWM) outputs.
DI/AI inputs can be set as binary potential-free or balanced EZS or as analog for measuring temperature or resistance. Resistance sensors PT1000, Ni1000, NTC12k thermistor sensor, or KTY81-121 are used for temperature measurement.
Order num. TXN 143 36
Teco code TXN 143 36
Categories CFox - Built-in modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 2
Number of groups of binary inputs 1
Organization of binary inputs into groups 2x DI (AI1 - AI2)
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals AI1 - AI2
Number of inputs in group 2
Common wire GND - module ground
Combined input type DI / AI - measurement of resistance sensors, sensing of potential-free contacts and balanced loops
Galvanic isolation of inputs from internal/peripheral circuits No
Max. measuring voltage on the connected contact 3,3 V DC
Internal input resistance 2 kΩ
Max. resistance for closed contact, log. 1 < 0,5 kΩ
Min. resistance for open contact, log. 0 > 4,2 kΩ
Balanced resistance input 2× 1k1 (tamper/0/1/tamper)
DO/RO - Organization of binary outputs
Total number of binary outputs 5
Number of binary output groups 2
Organization of binary outputs into groups 4x (DO1 - DO4) 1x (DO5)
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals DO1-DO4
Number of outputs in group 4
Organization of transistor outputs into groups 3 (DO1-DO3)
Output type MOSFET (High-side switch)
Galvanic separation from internal circuits No
Galvanic isolation of the outputs from CIB No
Diagnostics No
Switching voltage 9 - 30 V DC
Group current 160 mА
Output current 160 mA
Switching time typ. 40 μs (12-24V, 60-160mA)
Opening time typ. 70 μs (12-24V, 60-160mA)
Short circuit protection Yes
Special functions (A) PWM
Operating frequency 100 Hz ÷ 2 kHz
DO - Parameters of binary transistor outputs (group B)
Parameters valid for the terminals DO5
Common group conductor COM2
Output type transistor output
Galvanic separation from internal circuits Yes
Switching voltage 0 - 48V DC
Switching current, output load 80 mA (160mA @ 25˚C)
Short circuit protection No
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Number of analog input groups 1
Organization of analog inputs into groups 2x (AI1, AI2)
Input type AI / DI - combined
Common wire GND terminal
Galvanic separation from internal circuits No
Diagnostics overload signaling in status word
Digital resolution 10 bit
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals AI1, AI2
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-100 kOhm
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Auxiliary power supply - voltage Supply output +22V OUT: U0 = CIB bus voltage -1 V, Iout max = 60mA, internal resistance R < 88 Ω
Typical power input 0,5 W
Maximum power input 2,2 W
Module thermal/power loss 0,4 W
Power supply from CIB - typical current consumption (mA) 20 mA
Power supply from CIB - maximum current consumption (mA) 80 mA
Description of power supply Difference between typical and maximum power input is given by possible load of CIB buses and number of switched outputs and CPU load
Thermal/power loss of the module max. 0.65W (at maximum consumption of outputs powered by auxiliary voltage +22V OUT)
Size and weight
Weight approx. 7 g
Product dimensions (width x height x depth) 55 × 26 × 16 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 55 ° C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description Модуль упакован в антистатический пакет. Эта документация также является частью пакета. Внешняя упаковка осуществляется в соответствии с объемом заказа и способом транспортировки в транспортной упаковке, снабженной этикетками и другими данными, необходимыми для транспортировки. Продукт не должен подвергаться воздействию прямых погодных условий во время транспортировки и хранения. Соложение продукта разрешено только в чистых помещениях. без токопроводящей пыли, агрессивных газов и паров. Наиболее подходящая температура хранения - 20 ° C.
Installation
Assembly description The module C-DM-0001B-SL is mounted in arbitrary positioninto instalation box under a lid or under device located in box.
Connection
Connection of power and system communication terminal block with spring terminal 0.15-0.5 mm2, push-in
Connection of inputs / outputs terminal block with spring clamp 0.15-0.5 mm2, push-in
Connection description An example of module connection is shown in the following figure.
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

HW documentation

PDF

C-WG-0205S- Basic documentation

390.82 kB, (EN)

No data available.