C-IR-0202STXN 133 25
C-IR-0202S; CIB, 2x AI/DI - RTD or contact, 1x RO 3 A, 1x AO (1-10 VDC)
DI | 2x DI/AI |
---|---|
DO | 1x RO (3A) |
AI | 2x DI / AI see DI |
AO | 1x AO (0-10V) |
COM | 1x CIB slave |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
C-IR-0202S |
The C-IR-0202S module is a dimensionally minimalist module on the CIB bus for relay contact control or for continuous control via voltage analog output. At the same time, it is intended for connection of two passive temperature sensors or binary signals from contacts and their conversion into data for the CIB wiring bus.
- The resistance from the optional Pt1000, Ni1000, NTC 12k, KTY81-121 sensors against the common GND conductor is linearized in the module and converted directly to a numerical temperature value and then transferred to the basic module via the CIB bus. It is possible to choose the measurement of other resistances in the range of 0 to 160 kΩ, but the conversion to temperature and linearization must be performed in the control panel at the level of the application program.
- Binary signals are connected to the inputs only as a free contact against the common GND conductor.
- The voltage of the analog output 0 - 10 V is connected on the conductor against the common conductor GND.
- The output switching contact of the relay is led out by two separate conductors with increased insulation.
- The resistance from the optional Pt1000, Ni1000, NTC 12k, KTY81-121 sensors against the common GND conductor is linearized in the module and converted directly to a numerical temperature value and then transferred to the basic module via the CIB bus. It is possible to choose the measurement of other resistances in the range of 0 to 160 kΩ, but the conversion to temperature and linearization must be performed in the control panel at the level of the application program.
- Binary signals are connected to the inputs only as a free contact against the common GND conductor.
- The voltage of the analog output 0 - 10 V is connected on the conductor against the common conductor GND.
- The output switching contact of the relay is led out by two separate conductors with increased insulation.
Order num. | TXN 133 25 |
---|---|
Teco code | TXN 133 25 |
Categories | CFox - Built-in modules |
Tags | Temporarily unavailable |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
DI - Parameters of binary inputs DC (group A) | |
Parameters valid for inputs on the terminals | DI/AI1, DI/AI2 |
Number of inputs in group | 2 |
Common wire | minus |
Combined input type | DI/AI Active, for sensing potential-free contacts and measuring resistance sensors |
Galvanic isolation of inputs from internal/peripheral circuits | No |
Balanced resistance input | 2× 1k1 (tamper/0/1/tamper) |
RO - Parameters of binary relay outputs (group A) | |
Parameters valid for the terminals | DO1 |
Number of relay outputs | 1 |
Output type | electromechanical relay, unprotected output |
Contact type | NO - Normally Open |
Switching current | 3 A max., 100 mA min. |
Switching voltage | 250 V AC max., 5 V AC min., 30V DC max. |
Mechanical life | min. 5,000,000 cycles |
Electrical life at maximum resistive load | min. 200,000 cycles |
Short-circuit protection | No |
Treatment of inductive load | External RC element, varistor (AC), diode (DC) |
Insulation voltage between outputs and internal circuits | 3750 V AC |
AI - Organization of analog inputs | |
Total number of analog inputs | 2 |
Number of inputs per group | 2 |
Number of analog input groups | 1 |
Input type | With common clamp |
Common wire | GND terminal |
Galvanic separation from internal circuits | No |
Diagnostics | overload signaling in status word |
Digital resolution | 10 bit |
AI - Analog Input Ranges (Group A) | |
Parameters valid for inputs on the terminals | DI/AI1, DI/AI2 |
Passive sensor | Pt1000, W100 = 1,385 (-90 to +400 ° C) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Ni1000, W100 = 1.617 (-60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-160 kOhm |
Passive sensor | KTY81-121; PTC thermistor (-55 to + 125 °C) |
Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
DI: Voltage-free contact | 0 when> 1.5 kOhm, 1 when <0.5 kOhm |
DI: Balanced resistance input | 2x 1k1 (tamper/0/1/tamper) |
Resistance measurement error - maximum error at 25 ° C | ± 0.5% of full scale |
AO - Analog output parameters | |
Galvanic isolation from internal circuits | No |
Output type | active voltage output |
Voltage output - voltage | 0 - 10 V |
Voltage output - Minimum resolution | 1 % |
Voltage output - Adjustable range | 0 ÷ 130 % Ujm |
Voltage output - Load resistance | >1 kΩ |
Voltage output - Load capacity | 250 nF |
Power supply | |
Supply voltage, tolerances | 24/27 V DC from CIB bus |
Power supply from CIB - typical current consumption (mA) | 18 mA |
Power supply from CIB - maximum current consumption (mA) | 25 mA |
Power supply from CIB - Galvanic separation of power supply from internal circuits | Relay output contact only |
Insulation voltage of galvanic separation | 4 000 VAC (50/60 Hz) 1 min. |
Insulation resistance | 1 MΩ min. (at 500V) |
Power supply from CIB - internal protection | Yes, returnable fuse |
Size and weight | |
Weight approx. | 7 g |
Module width | 55 mm |
Module height | 26 mm |
Module depth | 20 mm |
Product dimensions (width x height x depth) | 55 x 26 x 20 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | III, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod) |
Degree of pollution | 1, according to ČSN EN 60664-1: 2004 (mod IEC 60664-1: 1992) |
Overvoltage category installation | II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992) |
Type of device | In the installation box, under the cover |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 °C to + 55 °C |
Operating temperature minimum (° C) | 0°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55022: 1999 (mod CISPR22: 1997) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | Модуль упакован в антистатический пакет. Эта документация также является частью пакета. Внешняя упаковка осуществляется в соответствии с объемом заказа и способом транспортировки в транспортной упаковке, снабженной этикетками и другими данными, необходимыми для транспортировки. Продукт не должен подвергаться воздействию прямых погодных условий во время транспортировки и хранения. Соложение продукта разрешено только в чистых помещениях. без токопроводящей пыли, агрессивных газов и паров. Наиболее подходящая температура хранения - 20 ° C. |
Installation | |
Assembly description | The module is inserted freely into the installation box or attached with a suitable cable tie inside the device. The conductors of the supply ribbon cable can be separated and shortened as required. However, to prevent interference problems, the active conductors must be routed together with the common GND conductor to the sensor so that no interference loops form between the conductors. Best with twisted pair cables. |
Connection | |
Connection of power and system communication | Ribbon flat conductors 0.15 / 0.5 mm2 |
Module connection | Strip wires 0.15 mm2, relay 2x 0.5 mm2 |
Module operation | |
Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-IR-0202S - Basic Documentation
902.20 kB, (EN)
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- C-IR-0202S - The C-IR-0202S module is designed to connect two temperature sensors or binary signals, power relay contact control, and control analogue voltage directly on the CIB bus. The signals from the module are terminated by a strip conductor. The PT100...
- 0 ÷ 10 V ballast control by C-IR-0202S module - ...ectronic ballasts of fluorescent lights controllable by analog voltage 0 ÷ 10 V or 1 ÷ 10 V e.g. the C-IR-0202S module can be used, which is equipped with a relay output for switching off the ballast power supply (i.e. comp...
- Continuously controlled drives by the 0 ÷ 10V signal (Alpha AA 5004) - The drive can be controlled by any 0 ÷ 10 V analogue output of the Foxtrot system. It is recommended to use the C-IR-0202S module for control at the drive location; the module is fitted with a 0 ÷ 10 V analogue output, and also...
- On-off drives (Alpha AA) controlled by a relay output - ...m can be used for switching the drive (typical power consumption of the drive is about 3 W). It is recommended to use the C-IR-0202S module for switching at the drive location; the module is fitted with a 3 A relay output with a relatively quie...
- The 5A relays, the Foxtrot basic modules and the peripheral CFox modules - ...se relays are fitted in e.g. the Foxtrot basic modules (CP-1005, CP1006, etc.), the peripheral modules ( C-HM-0308M , C-IR-0202S ) and others (see information on the individual modules ). The parameters of the ac...