C-IR-0203MTXN 133 59

C-IR-0203M; CIB, 2x DI / AI, 2x RO switching contacts 230V / 16A, 1x AO 0-10V / PWM

DI 2x AI/DI
DO 2x RO (NO/NC 16/10A)
AI 2x AI / DI see DI
AO 1x AO/PWM
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-IR-0203M
C-IR-0203M is a module on the CIB bus with a total of 5 inputs / outputs in combination:
  • 2 AI / DI inputs
  • 2 relay outputs with changeover contact (each contact shown separately on the terminal board)
  • 1 AO output with a range of 0 to 10V, or with a PWM output with adjustable amplitude and frequency.
Use:
  • Closed loop control with proportional control (PWM output) or two-point control (relay)
  • Control of valves, motors, lighting switching, heating cartridges and other general loads and appliances
  • Simple measurement of two quantities by passive / resistance sensors
Order num. TXN 133 59
Teco code TXN 133 59
Categories CFox - Modules on DIN rail
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
RO - Parameters of binary relay outputs (group A)
Number of relay outputs 2
Number of output groups 2
Number of outputs in group 1
Output type electromechanical relay, unprotected output
Contact type NO / NC changeover contact
Diagnose Alarm signaling on panel module
Switching current 16 A max., 100 mA min.
Switching voltage 250 V AC max., 5 V AC min., 30V DC max.
Short-term output overload - inrush 80 A max. (20 ms max.)
Contact closing time typ. 15 ms
Contact opening time typ. 5ms
Mechanical life min. 20 000 000 cycles
Short-circuit protection No
Insulation voltage between outputs and internal circuits 3750 V AC
Isolation voltage between groups of outputs to each other 3750 V AC
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Number of analog input groups 1
Input type With common clamp
Common wire Minus
Galvanic separation from internal circuits No
Diagnostics overload signaling in status word
External power supply No
Digital resolution 12 bit
Converter type Approximation
Analog input error - Temperature coefficient ± 0,03% of full scale
Analog input error - Nonlinearity ± 0.07% of full scale
Analog input error - Steady state repeatability 0.05% of full scale
AI - Analog Input Ranges (Group A)
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input 2x 1k1 (tamper/0/1/tamper)
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Resistance measurement error - temperature coefficient ± 0.05% of full scale / K
Resistance measurement error - non-linearity ± 0.09% of full scale
AO - Analog output parameters
Number of outputs in group 1
Common wire of group AGND terminal
Galvanic isolation from internal circuits No
Output type active voltage output
Analog output error - maximum error at 25 ° C ± 0.3% of full scale
Analog output error - temperature coefficient ± 0.3% of full scale / K
Analog output error - linearity ± 0.7% of full scale
Analog output error - repeatability under steady state conditions ± 0.5% of full scale
Voltage output - maximum output current 10 mA
Power supply
Nominal supply voltage (V) 24 V DC
Supply voltage, tolerances 24/27 V DC from CIB bus
Typical power input 1 W
Maximum power input 2 W
Module thermal/power loss 1,5 W
Power supply from CIB - maximum current consumption (mA) 80 mA
Galvanic separation of power supply from internal circuits No
Description of power supply Difference between typical and maximum power input is given by possible load of CIB buses and number of switched outputs and CPU load
Size and weight
Weight approx. 100 g
Product dimensions (width x height x depth) 18 x 90 x 58 mm
Module width in multiples of M (17.5 mm) 1,5M
Module height 90 mm
Module depth 58 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, according to ČSN 33 2000-3: 1995 (mod IEC 364-3: 1993)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation I, according to ČSN EN 60664-1 ed_2:2008 (idt IEC 60641-1:2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Switchboard mounting
Attention! The device may contain parts with dangerous voltages, covers being removed, or cabling manipulated, or disconnect the appropriate circuits or turn off the power !.
Connection
Connection of power and system communication terminal block with screw terminal 2.5 mm2
Connection of inputs / outputs terminal block with screw terminal 2.5 mm2
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IR-0203M - Basic documentation

792.93 kB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)
  • C-IR-0203M - The C-IR-0203M is a module on the CIB bus, which comprises of two universal analogue or binary inputs, two relay outputs with a changeover contact (each is separately terminated) and one output optionally adjustable as analogue, with the range fr...
  • Power dissipation of modules for calculation of switchboard heating - ...2x dimmer RLC, 230V AC, 2x 500W, 4x DI/AI C-DM-0402M-RLC 5,0 W TXN 133 59 C-IR-0203M; CIB, 2x DI/AI, 2x RO switching contacts 230V/16A, 1x AO 0-10V/PWM C-IR-0203M 1,5 W...
  • Two-point controlled VZK zone ball valve - ...mple of electrical connection of the VZK 2xx - 230 - 1P – 001 zone valve produced by Regulus. It is controlled by the C-IR-0203M module together with the Wilo Yonos circulation pump .   Fig. 1. An example of connecting a two...
  • Measurement of radiant heat in halls (industrial heating) - ...es of connection of a number of peripheral modules, such as connecting the Pt1000 sensor to the AI1 and AI2 inputs of the C-IR-0203M module ....
  • An example of dimming the CREE power LED chips by the C-DM-0006M-ILED module - ...network and needlessly consume current, its input is switched by a 230VAC relay output; in this case the DO1 input of the C-IR-0203M module is used. The inrush current (so-called “cold start”) of the power supply DR-60-12...
  • Continuous power control el. TV heating, SSR module - ...s, eg for outputs up to approx. 3 kW module RGS1A23D25, controlled by PWM output of the system - in the example used module C-IR-0203M . The module allows you to switch 2 heating coils and control the third continuously with PWM output (thus obtaini...

No data available.