C-IS-0504MTXN 133 49

C-IS-0504M; CIB, 3x AI/DI, 3x RO, 1x PWM (4W), 2x AI resistance measuring by AC)

DI 3x AI / DI see AI
DO 1x RO 16A
2x RO 3A
1x DO (PWM)
AI 3x AI / DI see DI
2x AI (AC resistance measurement <1MΩ)
AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-IS-0504M
C-IS-0504M is a module on the CIB bus with a total of 9 inputs / outputs in combination
  • 3x combined AI / DI input for sensing contacts and measuring resistance thermometers,
  • 2x analog input specialized for measuring AC resistances
  • (excluding long-term electrolysis in a humid environment - icing, precipitation, level probes)
  • 1x semiconductor output with pulse width modulation (PWM from 100 Hz to 2 kHz and load capacity max. 4W)
  • 2x relay output 5 A,
  • 1x relay output 16A, with resistance to inrush current up to 80 A
  • The individual relay outputs have a status LED indication and can be manually controlled locally by buttons on the module panel.
Use
  • Inputs and outputs can be used as general AI / DI and RO
Specialized use:
  • Controlled heating supply and measurement of precipitation detector S-RS-01I,
  • Heating supply and measurement of icing sensors with a nominal voltage of 24 V.
  • Up to 2 probes for level measurement, eg for limit monitoring of water in the tank.
Order num. TXN 133 49
Teco code TXN 133 49
Categories CFox - Modules on DIN rail
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DO/RO - Organization of binary outputs
Total number of binary outputs 4
Number of binary output groups 3
Organization of binary outputs into groups 1x RO 16A
2x RO 3A
1x PWM 24V/83mA
DO - Parameters of binary transistor outputs (group A)
Number of transistor outputs 1
Common group conductor minus
Output type Semiconductor
Galvanic separation from internal circuits No
Resting output level 24 V DC +-10%
Switching current, output load 83 mA max.
Short circuit protection No
Special functions (A) PWM
Operating frequency 100 Hz ÷ 2 kHz
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminals DO1
Number of relay outputs 1
Output type electromechanical relay, unprotected output
Contact type NO - Normally Open
Diagnose Alarm signaling on panel module
Switching current 16 A max., 100 mA min.
Switching voltage 400 V AC max., 300 V DC max.
Short-term output overload - inrush 80 A max. (20 ms max.)
Contact closing time typ. 15 ms
Contact opening time typ. 5ms
Mechanical life min. 20 000 000 cycles
Short-circuit protection No
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 4000 V AC
Isolation voltage between groups of outputs to each other 4000 V AC
RO - Parameters of binary relay outputs (group B)
Parameters valid for the terminals DO2, DO3
Number of relay outputs 2
Output type electromechanical relay, unprotected output
Contact type NO - Normally Open
Diagnose Alarm signaling on panel module
Switching current 3 A max., 100 mA min.
Switching voltage max. 250 V AC; max. 30 V DC; min. 5 V
Short-circuit protection No
Short-term output overload 5 A max. (20 ms max.)
Contact closing time typ. 10 ms
Contact opening time typ. 10 ms
Mechanical life min. 5,000,000 cycles
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 4000 V AC
Isolation voltage between groups of outputs to each other 4000 V AC
Insulation voltage between contacts 750 V AC
AI - Organization of analog inputs
Total number of analog inputs 5
Number of analog input groups 2
Organization of analog inputs into groups 3 (AI/DI 1 - 3) + 2 (AI4, AI5)
Input type With common clamp
Common wire GND terminal
Galvanic separation from internal circuits No
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals AI/DI1-AI/DI3
Voltage 0 to 2 V / 805.9 μV
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-100 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input 2x 1k1 (tamper/0/1/tamper)
Resistance measurement error - maximum error at 25 ° C ± 2% of full scale
AI - Analog Input Ranges (Group B)
Parameters valid for inputs on the terminals AI4, AI5
Passive sensor 0 - 1MOhm
Measuring current alternating current
Resistance measurement error - maximum error at 25 ° C ± 3% of full scale
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Maximum power input 2,5 W
Module thermal/power loss 2 W
Maximum current consumption (mA) 110 mA
Galvanic separation of power supply from internal circuits No
Size and weight
Weight approx. 125 g
Product dimensions (width x height x depth) 52 x 90 x 58 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 3:2012 (mod IEC 60730-1:2010)
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55022: 1999 (mod CISPR22: 1997)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The module is mounted in a vertical position on the U-rail ČSN EN 50022. Installation of the assembly (basic module and possibly peripheral modules) is performed according to TXV 004 13.
Connection
Connection description The power supply of the module is from the CIB bus. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The maximum consumption of all modules in one CIB branch is limited to 1A.
Only a resistive element can be connected to analog inputs AI4, AI5. These inputs are suitable for resistance sensors sensing humidity or level, as they protect the sensors against galvanic corrosion. The maximum length of the wires for connecting the humidity sensor is 3m. An example of module connection is shown in the following figure.
Connection of power and system communication connector with 2.5 mm2 screw terminal
Connection of inputs / outputs connector with screw terminal 2.5 mm2
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. The module contains an indication LED for checking the status of inputs / outputs. By pressing the Manual Control button, the module can be switched to manual mode and the individual outputs can be controlled.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IS-0504M - Basic documentation

1.17 MB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-IS-0504M - ...s only intended to power these sensors with a power input about 2 W; the output circuits have no overload protection. The C-IS-0504M module is also equipped with 3 relay outputs, 1 x 16 A and 2 x 5 A, e.g. for switching heating cables for defrosti...
  • The S-RS-01I precipitation detector with the C-IS-0504M module - ...ctor is designed to detect precipitation for automatic drawing of awnings or closing roof windows; it is connected to the C-IS-0504M module, which provides the power supply for the heating and measurement of the detector. The unused inputs and...
  • Rain detector S-RS-01I with module C-IS-0504M - The S-RS-01I rain detector connected to the  C-IS-0504M  module, which provides power to the heating and the measurement of the detector, is intended for the detection of precipitation, eg for automatic retraction of awnings, closing of ro...
  • Power dissipation of modules for calculation of switchboard heating - ...le for LED chips, controlled power supply C-DM-0006M-ILED 5,0 W TXN 133 49 C-IS-0504M; CIB, 3x AI/DI, 3x RO, 1x PWM (4W), 2x AI (AC resistance measurement) C-IS-0504M 2,0 W...
  • Defrosting gutters, the ETOR-55 sensor - ...approx. 2.5 W at 24 V supply. Heating of the ETOR sensor can be switched by the system relay output, e.g. the output of the C-IS-0504M module, to which the ETOR sensors are also connected (a maximum of 2 sensors per separate module inputs) - see th...
  • Defrosting outdoor spaces, the ETOG-55 sensor - ...wer input of approx. 2.5 W at 24 V supply. Heating of the ETOG-55 sensor can be connected directly to the DO4 output of the C-IS-0504M module , which is primary intended to power the heating.If the heating of the ETOG-55 sensor is powered from anoth...
  • Submersible conductivity sensors - sensing of water level of electrically conductive liquids - The C-IS-0504M module can be used for monitoring water levels in the tanks, e.g. for control of irrigation systems, etc. Monitoring of level in water tanks by DC measurement of resistive sensor is not recommended due to the destruction of ele...
  • Immersion conductivity probes - sensing the water level of electrically conductive liquids - The C-IS-0504M module can be used for monitoring the water level in tanks, eg for controlling irrigation systems, etc. For monitoring the water level in the tank, it is inappropriate to measure the conductivity (resistance) with direct current (as...