C-IF-6400RTXN 133 87
C-IF-6400R; CIB; Module with GridEye sensor, matrix 8 x 8 temperature sensors
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 1x CIB slave |
SENSOR | 8 x 8 = 64 temperature sensors |
Picture | Variant | Variant description |
---|---|---|
C-IF-6400R |
C-IF-6400R is a matrix of 8 x 8 temperature sensors (64 pixels) on the CIB bus - Common Instalation Bus®.
Sensor Grid-EYE is based on MEMS technology. Each pixel, independently of the others, transmits the temperature value directly in engineering units.
The range of measured temperatures is from 0 to 80 ° C. Thanks to the silicon lens, it is possible to actively monitor the angle of 60 °.
Fast measurement and transfer (1x or 10x per second) of all values to the basic Foxtrot module allows to prepare programs for static and dynamic decision and recognition functions above this field, it is possible to detect the presence, movement, speed and direction of moving objects
Sensor Grid-EYE is based on MEMS technology. Each pixel, independently of the others, transmits the temperature value directly in engineering units.
The range of measured temperatures is from 0 to 80 ° C. Thanks to the silicon lens, it is possible to actively monitor the angle of 60 °.
Fast measurement and transfer (1x or 10x per second) of all values to the basic Foxtrot module allows to prepare programs for static and dynamic decision and recognition functions above this field, it is possible to detect the presence, movement, speed and direction of moving objects
Order num. | TXN 133 87 |
---|---|
Teco code | TXN 133 87 |
Categories | CFox - Interior modules |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
AI - Organization of analog inputs | |
Organization of analog inputs into groups | 8 x 8 proximity temperature sensor matrix |
Parameter des Temperatursensors | |
Temperature - Sensor type | Grid Eye |
Temperature - Measurement range | 0°C ÷ 80°C |
Temperature - Resolution | 0,25°C |
Temperature - Measurement accuracy | typ. ±2,5 °C |
Power supply | |
Supply voltage, tolerances | 24/27 V DC from CIB bus |
Maximum power input | < 0,5 W |
Maximum current consumption (mA) | < 20 mA |
Power supply from CIB - typical current consumption (mA) | 15 mA |
Galvanic separation of power supply from internal circuits | No |
Power supply from CIB - Galvanic separation of power supply from internal circuits | No |
Internal protection | No |
Size and weight | |
Weight approx. | 40 g |
Product dimensions (width x height x depth) | 26 x 111 x 29 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes) |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | On the wall |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. Included the package is also this documentation. Outer packaging with performed according to the scope of the contract and method transport into a transport packaging provided labels and other particulars necessary for: transportation. The product must not be during transport and storage directly exposed weather conditions. Malting the product is allowed only in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C. |
Installation | |
Assembly description | The C-IF-6400R module is mounted horizontally or vertical position on the wall. Install the report (basic module and peripheral modules, if applicable) Performs according to the manual TXV 004 13. |
Connection | |
Connection via connectors | CIB - terminal block, conductor 2x max. 1,5 mm2 |
Connection of power and system communication | terminal block with screw terminal 1.5 mm2 |
Module connection |
The module is powered from the CIB bus. To connect the module to the CIB bus is remove the back cover. Description of terminals module see the following figure |
Module operation | |
Commissioning | The module is operated, set and diagnosed from the programming environment MOSAIC or other parameterization software. The module is connected to the power supply voltage and CIB bus ready for operation. HW address is stated on the label on the side. |
Maintenance | |
Instructions | In compliance with the general installation module does not require any maintenance. The sensor is cleaned with compressed air or cloth for optic. Do not use liquid cleaners! Operations in which it is necessary to mount or remove the module are executed whenever the power is off CIB bus. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-IF-6400R- Basic documentation
376.09 kB
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Scheme
Visualization and evaluation of 8x8 array of temperature sensor C-IF-6300R
36.95 kB
Module connection diagram on CIB bus
3.24 kB
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot 2 - EC Declaration of conformity (en)
590.59 kB, (EN, RU, DE, UA)
- People counting and averaged temperature map with C-IF-6400R Grid-Eye sensor - Here you can read more detailed information about the sensor itself , and in the article Using the C-IF-6400R sensor to detect the position of people you can read one of the examples of using the sensor. This article will descri...
- Use of the C-IF-6400R sensor for detecting the position of people - Principle and processing: The example used a C-IF-6400R module equipped with a Grid-EYE sensor, which is 64 precision thermal sensors arranged in an 8x8 matrix. Provides temperature map data at a viewing angle of 60 degrees, horizontally and ve...
No data available.