C-IF-6400RTXN 133 87

C-IF-6400R; CIB; Module with GridEye sensor, matrix 8 x 8 temperature sensors

DI
DO
AI
AO
COM 1x CIB slave
SENSOR 8 x 8 = 64 temperature sensors
Picture Variant Variant description
C-IF-6400R
C-IF-6400R is a matrix of 8 x 8 temperature sensors (64 pixels) on the CIB bus - Common Instalation Bus®.
Sensor Grid-EYE is based on MEMS technology. Each pixel, independently of the others, transmits the temperature value directly in engineering units.
The range of measured temperatures is from 0 to 80 ° C. Thanks to the silicon lens, it is possible to actively monitor the angle of 60 °.
Fast measurement and transfer (1x or 10x per second) of all values to the basic Foxtrot module allows to prepare programs for static and dynamic decision and recognition functions above this field, it is possible to detect the presence, movement, speed and direction of moving objects
Order num. TXN 133 87
Teco code TXN 133 87
Categories CFox - Interior modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
AI - Organization of analog inputs
Organization of analog inputs into groups 8 x 8 proximity temperature sensor matrix
Parameter des Temperatursensors
Temperature - Sensor type Grid Eye
Temperature - Measurement range 0°C ÷ 80°C
Temperature - Resolution 0,25°C
Temperature - Measurement accuracy typ. ±2,5 °C
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Maximum power input < 0,5 W
Maximum current consumption (mA) < 20 mA
Power supply from CIB - typical current consumption (mA) 15 mA
Galvanic separation of power supply from internal circuits No
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Internal protection No
Size and weight
Weight approx. 40 g
Product dimensions (width x height x depth) 26 x 111 x 29 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device On the wall
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. Included the package is also this documentation. Outer packaging with performed according to the scope of the contract and method transport into a transport packaging provided labels and other particulars necessary for: transportation. The product must not be during transport and storage directly exposed weather conditions. Malting the product is allowed only in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C.
Installation
Assembly description The C-IF-6400R module is mounted horizontally or vertical position on the wall. Install the report (basic module and peripheral modules, if applicable) Performs according to the manual TXV 004 13.
Connection
Connection via connectors CIB - terminal block, conductor 2x max. 1,5 mm2
Connection of power and system communication terminal block with screw terminal 1.5 mm2
Module connection The module is powered from the CIB bus.
To connect the module to the CIB bus is
remove the back cover. Description of terminals
module see the following figure
Module operation
Commissioning The module is operated, set and diagnosed from the programming environment MOSAIC or other parameterization software. The module is connected to the power supply voltage and CIB bus ready for operation. HW address is stated on the label on the side.
Maintenance
Instructions In compliance with the general installation module does not require any maintenance. The sensor is cleaned with compressed air or cloth for optic. Do not use liquid cleaners! Operations in which it is necessary to mount or remove the module are executed whenever the power is off CIB bus.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IF-6400R- Basic documentation

376.09 kB

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Scheme

Visualization and evaluation of 8x8 array of temperature sensor C-IF-6300R

Visualization and evaluation of 8x8 array of temperature sensor C-IF-6300R

36.95 kB
Module connection diagram on CIB bus

Module connection diagram on CIB bus

3.24 kB

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)