C-AQ-0006R-CO2TXN 133 88.02

C-AQ-0006R-CO 2; CIB, Spatial CO2 concentration sensor

DI
DO
AI
AO
COM 1x CIB slave
SENSOR
  • CO2
  • Temperature and humidity
  • Smoke
  • iVOC - volatile organic compounds
According to the variant
Picture Variant Variant description
C-AQ-0006R-CO2 Sensor: CO2
C-AQ-0006R-iVOC Sensor: iVOC (volatile organic compounds)
C-AQ-0006R-RHT Sensor: RHT (humidity and temperature)
C-AQ-0006R-SMOKE Sensor: Smoke
C-AQ-0006R-xxx are room sensors for indoor air quality measurement.

They detect
- carbon dioxide CO2,
- relative humidity RH,
- volatile organic compounds iVOC
- air temperature T.

Built-in autocalibration functions of the sensors guarantee long-term measurement stability. It is connected via the CIB - Common Installation Bus®.
Order num. TXN 133 88.02
Teco code TXN 133 88.02
Categories CFox - Interior modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
Parameter des Temperatursensors
Temperature - Measurement range 0°C ÷ 40°C
Temperature - Resolution 0,1 °C
Temperature - Measurement accuracy typ. ±0,4 °C
Humidity sensor parameters
Relative humidity - Sensor type capacity polymeric
Relative humidity - Measurement range 0 ÷ 100 %RH
Relative humidity - Resolution 0,1 % RH
Relative humidity - Measurement accuracy type. ± 3.5% RH (for RH 20 ÷ 80%); ± 6% RH (for RH 0 ÷ 100%)
CO2 sensor parameters
CO2 - Sensor type infrared radiation (NDIR)
CO2 - Measurement range 0 ÷ 2000 ppm / 0 ÷ 5000 ppm
CO2 - Resolution 1 ppm
CO2 - Measurement accuracy ± 35 ppm + ±5%
CO2 - Sensor start-up Max. 1 min
iVOC sensor parameters
Sensor resolution 1 ppm
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Maximum power input 2 W
Power supply from CIB - typical current consumption (mA) 80 mA
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Internal protection No
Size and weight
Weight approx. 100 g
Product dimensions (width x height x depth) 90 x 80 x 31 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP22
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 2, according to ČSN EN 60664-1 ed.2: 2008 (idt IEC 60664-1: 2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device On the wall
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The C-AQ-0006R module is mounted in a vertical position in an installation box or panel. Installation of the assembly (basic module and possibly peripheral modules) is performed according to TXV 004 16 CFox, RFox and Foxtrot Design Guide.
Connection
Connection description The power supply of the module is from the CIB bus. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The maximum consumption of all modules in one CIB branch is limited to 1A. The mounting dimensions and an example of the module connection are shown in the following figures.

The CIB connection terminal block is located under the top cover of the module. The procedure for removing the cover is shown in the following figures.
Connection of power and system communication terminal block with screw terminal 1.5 mm2
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Commissioning Das Modul wird über die MOSAIC-Programmierumgebung oder eine andere Parametrierungssoftware bedient, eingestellt und diagnostiziert. Das Modul ist betriebsbereit, nachdem die Versorgungsspannung und der CIB-Bus angeschlossen wurden. Die HW-Adresse ist auf dem Etikett neben dem Anschlussklemmenblock angegeben. Die Beschreibung des Modulbetriebs finden Sie im Handbuch TXV 004 13 Peripheriemodule am CIB-Bus.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-AQ-0006R- Basic documentation (cs,en)

295.14 kB

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.15 kB, (EN, RU, DE, UA)
  • C-AQ-0006R - The C-AQ-0006R module is used to monitor the air quality in the interior of buildings and replaces the older generation of modules C-AQ-0001R to C-AQ-0004R. Built-in sensors can measure carbon dioxide (CO2), relative humidity (RH), volatile organic...
  • Measurement of smoke, CFox module C-AQ-0003R - The module is no longer for sale, it is replaced by the C-AQ-0006R  module. The C-AQ-0003R module is a spatial sensor sensitive to the gaseous pollutants in the air. The sensor exhibits a high sensitivity to low concentrations of gaseous...
  • Measurement of CO2 , CFox module C-AQ-0001R - The module is no longer for sale, it is replaced by the C-AQ-0006R  module.   The C-AQ-0001R module is a spatial sensor of concentration of carbon dioxide (CO 2 ) in the air. The principle of CO 2 measurement is based on...
  • Measuring the quality of air, CO2, RH, VOC - From 2019, sensors C-AQ-0001R to C-AQ-0004R are replaced by a new generation of sensors C-AQ-0006R . On the CFox and RFox buses are available modules for measuring CO 2 , smoke, volatile compounds (VOC) and RH (relative humidity). Modul...

No data available.