C-IR-0303MTXN 133 60
C-IR-0303M; CIB, 3x AI/DI, 2x RO-5A, 1x RO-16A
DI | 3x AI/DI |
---|---|
DO | 3x RO |
AI | 3x AI / DI see DI |
AO | |
COM | 1x CIB slave |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
C-IR-0303M |
The C-IR-0303M is a module on the CIB bus that it contains
- 3x AI / DI inputs
- 3x relay outputs with switching contact (2 with common input and 1 separately connected to the terminal board).
Use:
- Valve control, addition of heating circuit control for common installations in the field of HVAC,
- Switching of lighting, general loads and appliances
- Measurement of up to three quantities by passive / resistance sensors
- 3x AI / DI inputs
- 3x relay outputs with switching contact (2 with common input and 1 separately connected to the terminal board).
Use:
- Valve control, addition of heating circuit control for common installations in the field of HVAC,
- Switching of lighting, general loads and appliances
- Measurement of up to three quantities by passive / resistance sensors
Order num. | TXN 133 60 |
---|---|
Teco code | TXN 133 60 |
Categories | CFox - Modules on DIN rail |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
RO - Parameters of binary relay outputs (group A) | |
Number of relay outputs | 2 |
Number of output groups | 2 |
Number of outputs in group | 2 |
Output type | electromechanical relay, unprotected output |
Contact type | NO - Normally Open |
Diagnose | Alarm signaling on panel module |
Switching current | 3 A max., 100 mA min. |
Switching voltage | 250 V AC max., 5 V AC min., 30V DC max. |
Contact closing time | typ. 15 ms |
Contact opening time | typ. 5ms |
Mechanical life | min. 5,000,000 cycles |
Short-circuit protection | No |
RO - Parameters of binary relay outputs (group B) | |
Number of relay outputs | 1 |
Number of output groups | 1 |
Number of outputs in group | 1 |
Contact type | NO - Normally Open |
Diagnose | Alarm signaling on panel module |
Switching current | 16 A max., 100 mA min. |
Switching voltage | max. 250 V AC; max. 30 V DC; min. 5 V |
Short-circuit protection | No |
Contact closing time | typ. 10 ms |
Contact opening time | typ. 4 ms |
Mechanical life | min. 5,000,000 cycles |
AI - Analog Input Ranges (Group A) | |
Voltage | 0 to 2 V / 805.9 μV |
Passive sensor | Pt1000, W100 = 1,385 (-90 to +400 ° C) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Ni1000, W100 = 1.617 (-60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-100 kOhm |
DI: Voltage-free contact | 0 when> 1.5 kOhm, 1 when <0.5 kOhm |
Power supply | |
Power supply from CIB - voltage | 24/27 V DC |
Module thermal/power loss | 1,5 W |
Power supply from CIB - maximum current consumption (mA) | 60 mA |
Galvanic separation of power supply from internal circuits | No |
Power supply from CIB - Galvanic separation of power supply from internal circuits | No |
Size and weight | |
Weight approx. | 100 g |
Product dimensions (width x height x depth) | 35 x 92 x 40 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes) |
Protection class of electrical object | I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Operating areas | Normal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | In the installation box, under the cover |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating temperature maximum (° C) | +55°C |
Operating temperature minimum (° C) | -20°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | A, according to EN 55022: 1999 (mod CISPR22: 1997) |
Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Attention! | The device may contain parts with dangerous voltages, covers being removed, or cabling manipulated, or disconnect the appropriate circuits or turn off the power !. |
Connection | |
Connection of power and system communication | terminal block with screw terminal 2.5 mm2 |
Connection of inputs / outputs | terminal block with screw terminal 2.5 mm2 |
Connection description | An example of module connection is shown in the following figure. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-IR-0303M - Basic documentation
831.32 kB, (EN)
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- C-IR-0303M - C-IR-0303M is a module on the CIB bus, which contains 3 AI / DI inputs, 3 relay outputs with a switching contact (2 with a common input and 1 separately connected to the terminal board). The module is suitable, for example, for supplementing the...
- Power dissipation of modules for calculation of switchboard heating - ...O switching contacts 230V/16A, 1x AO 0-10V/PWM C-IR-0203M 1,5 W TXN 133 60 C-IR-0303M; CIB, 3x AI/DI, 2x RO-5A, 1x RO-16A C-IR-0303M 1,5 W TXN 133 67...
- IOConfig and RFox1 - ...ules to CIB. The PLC is CP-1001. The RFox devices are: R-HM-113M, R-RC-0001R, R-HC-0101F and RF-1131 master. I want to add a C-IR-0303M to CIB....
- Analog input - Can I use AI of CP-1000 PLC with input 0-10V? Can I use AI of C-IR-0303M with input 0-10V? In case it is not possible which module I could buy? Regards
- Analog input - ...n/product/c-am-0600i). In the assortment of CIB peripheral modules are some types like https://catalog.tecomat.cz/en/product/c-ir-0303m#params that supports 0 - 2 V input range, but not 0 - 10 V. It depends on the solution of inputs circuits and it c...