Picture | Variant | Variant description |
---|---|---|
C-BS-0001M |
The C-BS-0001M module is a single-channel CIB bus separator for increasing the current consumption (and thus also the number of modules) on the CIB bus for basic modules (CP-xxxx) with possible current consumption from the CIB up to 100mA.
That is, for all CP-xxxx except CP-1000, CP-1001 and CP-2000. It allows the connection of 32 modules up to a maximum current of 1A.
That is, for all CP-xxxx except CP-1000, CP-1001 and CP-2000. It allows the connection of 32 modules up to a maximum current of 1A.
Order num. | TXN 133 55 |
---|---|
Teco code | TXN 133 55 |
Categories | CFox - System Modules |
Tags | - |
Power supply | |
---|---|
Nominal supply voltage (V) | 27 V DC |
Supply voltage, tolerances | 27 V DC, +15%, -25% |
Typical power input | 27 W |
Maximum power input | 27 W |
Galvanic separation of power supply from internal circuits | No |
CIB branch power supply - parameters of the built-in master | 1x 1A / 24 V DC |
Size and weight | |
Weight approx. | 125 g |
Product dimensions (width x height x depth) | 18 x 90 x 58 mm |
Module width in multiples of M (17.5 mm) | 1M |
Module width | 18 mm |
Module height | 90 mm |
Module depth | 58 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units |
Protection class of electrical object | II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Operating areas | Normal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | I, according to ČSN EN 60664-1 ed_2:2008 (idt IEC 60641-1:2007) |
Type of device | Module on DIN rail |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating temperature maximum (° C) | +55°C |
Operating temperature minimum (° C) | -20°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55022: 1999 (mod CISPR22: 1997) |
Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Attention! | The device may contain parts with dangerous voltages, covers being removed, or cabling manipulated, or disconnect the appropriate circuits or turn off the power !. |
Connection | |
Connection of power and system communication | terminal block with screw terminal 2.5 mm2 |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-BS-0001M - Basic documentation
994.26 kB, (EN)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- Decoupling power supply to CIB – the C-BS-0001M decoupling module - ...source and the total consumption of all connected and powered CFox peripheral modules. Fig. 1. The basic C-BS-0001M connection with the Foxtrot basic module CP-1004 Notes: The power supply must be stabil...
- Power dissipation of modules for calculation of switchboard heating - ...064M; CIB-DALI converter, for 64 DALI ballasts C-DL-0064M 2,0 W TXN 133 55 C-BS-0001M; CIB bus separator, 1A C-BS-0001M 1,0 W TXN 133 58 C-DM-0402M-RL...
- Internal CIB master at the CP-10xx - ...lable - they have no power supply to CIB of the internal master. Whenever the CIB is used, the external separation module C-BS-0001M must be connected (maximum total current of the elements on bus 1A). The basic modules CP-10x4 and CP-10x...
- CIB power supply – principles, optimization - ...le Foxtrot basic module, which contains an internal master (e.g. the CP-1000 ) and an external decoupling module,the C-BS-0001M , should be connected directly in the power supply output ( PS2-60/27 or e.g the DR-60-24 ). &nbs...
- CIB characteristics - ...ource connected to the bus via internal separation circuits ( CP-1000 , CF-1141 ) or an external decoupling module C-BS-0001M . The power supply can also be used for powering the Foxtrot system. In addition to data transfer, the bus f...
- CIB bus – principles of design and installation - ...imization Internal CIB master at the CP-10xx CF-1141 external CIB master Decoupling power supply to CIB – the C-BS-0001M decoupling module CIB surge protection...
No data available.