C-RF-0001M-ATXN 143 15.A

C-RF-0001M-A; RFox2 Mini Master, CIB / RFox2 interface, type A radio

DI
DO
AI
AO
COM 1x CIB slave
1x RFox2 Master
SENSOR
Picture Variant Variant description
C-RF-0001M-A
The C-RF-0001M-A peripheral module is the communication interface between the CFox bus and the RFox2 wireless network. It is referred to as the CFox MiniMaster. It allows you to connect up to 10 Rfox2 wireless elements to the system.
Order num. TXN 143 15.A
Teco code TXN 143 15.A
Categories CFox - System Modules, RFox2 - System Modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
COM - Wireless network
RFox2 wireless network RFox2 Master
RFox2 wireless network range up to 256 RFox2 slave nodes
Communication frequency band 868,1 MHz
Transmission power +14 dBm
Input sensitivity –108 dBm
Modulation type 2-GFSK
Communication speed 50 kbps
Power supply
Power supply from CIB - voltage 24/27 V DC
Maximum power input < 0,5 W
Module thermal/power loss 0,4 W
Internal protection Yes, PTC reversible fuse
Size and weight
Weight approx. 50 g
Module width in multiples of M (17.5 mm) 1M
Product dimensions (width x height x depth) 22,7 x 95 x 58 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 3:2012 (mod IEC 60730-1:2010)
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.3: 2012
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Connection
Connection description An example of module connection is shown in the following figure. Any type designed for the 868 MHz band can be used as an antenna by terminating with an SMA connector (pin).
Connection of power and system communication terminal block with screw terminal 2.5 mm2
Module operation
Module configuration The module is operated in the RFox2 radio network as a peripheral module, the settings are made using the IO Configurator tool in the Mosaic programming environment, see the TXV 003 93 manual in the RFox2Lib description.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Warning Because the module contains semiconductor components, it is necessary to follow the principles for working with components sensitive to electrostatic charges during handling. Repairs are performed exclusively by the manufacturer's service center or the manufacturer's authorized service.
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-RF-0001M-A - Basisdokumentation

568.98 kB, (EN)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)
  • C-RF-0001M-A Minimaster RFox2 - The C-RF-0001M-A module ensures the communication of RFox2 wireless peripherals with the basic Foxtrot module using the CIB bus. I.e. it is a master bus (radio network) RFox2, which is connected via the CIB bus. It allows to connect a limited (appro...
  • Power dissipation of modules for calculation of switchboard heating - ...eter KMB, 230 V, 3x measurement input U and I) C-EM-0300M 3,0 W TXN 143 15 C-RF-0001M-A (CIB to RFox2 converter) C-RF-0001M-A 0,8 W...
  • Antennas for RFox2 in version A, 868 MHz - ...68 MHz ISM antenna suitable for RFox2 modules equipped with an SMA connector for connecting an external antenna (eg modules C-RF-0001M-A , R-EM-0300M-A and others). Standards ZigBee, ISM, SIGFOX, LoRa...

No data available.