C-IT-0200STXN 133 29

C-IT-0200S, CIB, 2x AI/DI RTD or contact

DI 2x AI/DI
DO
AI 2x AI/DI see DI
AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-IT-0200S
The C-IT-0200S module is intended for connection of two passive temperature sensors or binary signals from contacts and their conversion to the CIB wiring bus.

The resistance from the optional Pt1000, Ni1000, NTC 12k, KTY81-121 sensors against the common GND conductor is linearized in the module and converted directly to a numerical temperature value and then transferred to the basic module via the CIB bus. It is possible to choose the measurement of other resistances in the range of 0 to 160 kΩ, but the conversion to temperature and linearization must be performed in the control panel at the level of the application program.
Order num. TXN 133 29
Teco code TXN 133 29
Categories CFox - Built-in modules
Tags Sales and production discontinued
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 2
Number of groups of binary inputs 1
Organization of binary inputs into groups 2x DI (DI/AI1, DI/AI2)
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals DI/AI1, DI/AI2
Number of inputs in group 2
Common wire GND - module ground
Combined input type DI/AI Active, for sensing potential-free contacts and measuring resistance sensors
Galvanic isolation of inputs from internal/peripheral circuits No
Max. measuring voltage on the connected contact 3,3 V DC
Internal input resistance 2 kΩ
Max. resistance for closed contact, log. 1 < 0,5 kΩ
Min. resistance for open contact, log. 0 > 1,5 kΩ
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Number of analog input groups 1
Organization of analog inputs into groups 2x AI (DI/AI1, DI/AI2)
Input type With common clamp
Common wire GND terminal
Galvanic separation from internal circuits No
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals DI/AI1, DI/AI2
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input 2x 1k1 (tamper/0/1/tamper)
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Power supply from CIB - typical current consumption (mA) 10 mA
Power supply from CIB - maximum current consumption (mA) 12 mA
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 7 g
Product dimensions (width x height x depth) 55 x 26 x 16 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 55 ° C
Operating temperature maximum (° C) +70°C
Operating temperature minimum (° C) -25°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description Модуль упакован в антистатический пакет. Эта документация также является частью пакета. Внешняя упаковка осуществляется в соответствии с объемом заказа и способом транспортировки в транспортной упаковке, снабженной этикетками и другими данными, необходимыми для транспортировки. Продукт не должен подвергаться воздействию прямых погодных условий во время транспортировки и хранения. Соложение продукта разрешено только в чистых помещениях. без токопроводящей пыли, агрессивных газов и паров. Наиболее подходящая температура хранения - 20 ° C.
Installation
Assembly description The module is inserted freely into the installation box or attached with a suitable cable tie inside the device. The supply wires can be separated and shortened as required. However, to prevent interference problems, the active conductors must be routed together with the common GND conductor to the sensor so that no interference loops form between the conductors. Best with twisted pair cables.
Connection
Connection of power and system communication Ribbon flat conductors 0.15 / 0.5 mm2
Module connection Sensors with a converter are implemented as standard units on a two-wire CIB bus, which ensures communication and power supply of the entire sensor.

For more information, see the Peripheral Modules on the CIB TXV 004 13 manual. An example of the module connection is shown in the following figure.
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IT-0200S - Basic documentation

593.60 kB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-IT-0200S - The C-IT-0200S module (order number TXN 133 29) is used for connecting two temperature sensors or binary signals directly on the CIB bus. The signals from the module are brought by a strip conductor. The Pt1000 or Ni1000 resistance sensors can b...
  • Wall push-buttons scanned by the input module C-IT-0200S - ...ers push-buttons without adjustment and mount them onto the CIB module with digital inputs. It is advantageous to use the C-IT-0200S module for controllers with one or two push-buttons, as it can be placed directly into the flush box under the con...
  • Connecting a PIR detector with a double-balanced loop to C-IT-0200S module - ...box (e.g. directly under the detector), a variety of modules with double balanced inputs is available, such as the C-IT-0200S module. Here you have to provide a 12 V power supply for the detectors, unlike with the C-WG-0503S module...
  • Binary inputs – voltage levels DI/AI, the requirements for the switching circuit - ...1. The binary input circuit – measuring the parameters   Notes: The module in the figure is C-IT-0200S. The same connection applies to all modules that have the DI inputs switched against the ground terminal GND, i.e....
  • Wall push-buttons scanned by the input module C-IT-0504S - The built-in C-IT-0504S module can be used in a similar way as the C-IT-0200S ; it can scan e.g. 4 push-buttons of the controller, measure the interior temperature, and it can also control up to 4 LEDs, if the controller is equipped with...
  • Conection of the opening detectors - ...  Fig. 1. An example of connecting 2 and 4-wire contacts to the C-IT-0200S module   Notes: The example shows the wiring of the contact and the tamper loops i...
  • Control push-buttons on the wall (control of lighting, blinds, etc.) - Control units on the wall (a replacement of conventional switches) can be designed or integrated into the system in several ways, depending on the comfort, options, price and assortment. The first one is a controller as the bus element of...