C-IT-0202STXN 133 66

C-IT-0202S; CIB, 2x AI / DI Temperature / contact, 2x AO (0-10V)

DI 2x DI/AI
DO
AI 2x DI/AI see DI
AO 2x AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-IT-0202S
The C-IT-0202S module is a dimensionally minimized module on the CIB bus for control by two independent analog outputs.
At the same time, it is intended for connection of two passive temperature sensors or binary signals from contacts and their conversion into data for the CIB wiring bus.

- The resistance from the optional Pt1000, Ni1000, NTC 12k, KTY81-121 sensors against the common GND conductor is linearized in the module and converted directly to a numerical temperature value and then transferred to the basic module via the CIB bus. It is possible to choose the measurement of other resistances in the range of 0 to 160 kΩ, but the conversion to temperature and linearization must be performed in the control panel at the level of the application program.
- Binary signals are connected to the inputs only as a free contact against the common GND conductor.
- The voltage of the analog output 0 - 10 V is connected on the conductor against the common conductor GND.
Order num. TXN 133 66
Teco code TXN 133 66
Categories CFox - Built-in modules
Tags Sales and production discontinued
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 2
Number of groups of binary inputs 1
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals DI/AI1, DI/AI2
Number of inputs in group 2
Common wire GND - module ground
Combined input type DI/AI Active, for sensing potential-free contacts and measuring resistance sensors
Galvanic separation of inputs from CIB bus No
Max. measuring voltage on the connected contact 3,3 V DC
Internal input resistance 2,2 kΩ
Max. resistance for closed contact, log. 1 < 0,5 kΩ
Min. resistance for open contact, log. 0 > 1,5 kΩ
Balanced resistance input 2× 1k1 (tamper/0/1/tamper)
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals DI/AI1, DI/AI2
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input 2x 1k1 (tamper/0/1/tamper)
Input impedance in signal range RTD > 2,2 kΩ
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
AO - Analog output parameters
The number of groups of analogue outputs 1
Parameters valid for the terminals AO1, AO2
Common wire of group GND terminal
Galvanic isolation from internal circuits No
Output type active voltage output
Voltage output - voltage 0 - 10 V
Voltage output - Minimum resolution 1 %
Voltage output - Adjustable range 0 ÷ 130 % Ujm
Voltage output - Load resistance >1 kΩ
Voltage output - Load capacity 50 nF
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Power supply from CIB - typical current consumption (mA) 8 mA
Power supply from CIB - maximum current consumption (mA) 10 mA
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 15 g
Product dimensions (width x height x depth) 35 × 30 × 20 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 70 ° C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Connection
Connection of power and system communication terminal block with spring clamp 1 mm2, push-in
Connection of inputs / outputs terminal block with spring clamp 1 mm2, push-in
Module connection An example of module connection is shown in the following figure. A terminal block with pen terminals is intended for connecting the CIB bus, inputs and analog outputs. These are intended for the connection of a rigid conductor. If it is necessary to connect a stranded wire, it is necessary to crimp a suitable cable gland at its end. The wire is connected by inserting it into the oval hole. The wire is released by pushing the tip of a flat-blade screwdriver (0.4 mm x 2 mm) into the rectangular hole above the wire hole.
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IT-0202S- Basic documentation

206.83 kB
PDF

C-IT-0202S - Basic Documentation

1.00 MB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

DWG

C-IT-0202S - Technical drawing M01 DWG

42.87 kB
DWG

C-IT-0202S - Technical drawing S01 DWG

45.22 kB
DXF

C-IT-0202S - Technical drawing M01 DXF

38.32 kB
DXF

C-IT-0202S - Technical drawing S01 DXF

43.61 kB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.

No data available.