C-IB-1800MTXN 133 06

C-IB-1800M; CIB, 4x AI/DI universal inputs 14x DI including double balanced inputs, 4M

DI 14x DI
4x AI/DI
DO
AI 4x AI / DI see DI
AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-IB-1800M
C-IB-1800M is a module on the CIB bus, which contains a total of 18 inputs
  • 14 binary inputs - mainly for sensing potential-free contacts
  • These inputs can be switched to the so-called balanced input mode used for security sensors. In this mode, the inputs can also detect sensor disconnection as tamper
  • The module also has a power supply for security sensors requiring 12V DC
  • 4 combined AI / DI inputs not only for binary and balanced inputs, but also for measuring passive resistance / temperature sensors. These inputs can also be configured as fast pulse counters up to 1 kHz
Use:
  • In installations where a higher proportion of input signals is usually directly from contacts and temperature sensors without the need for outputs for control or regulation
Order num. TXN 133 06
Teco code TXN 133 06
Categories CFox - Modules on DIN rail
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 18
Number of groups of binary inputs 2
Organization of binary inputs into groups 4x (AI/DI1 - AI/DI4) + 14x (DI5-DI18)
Pulse counter up to 1kHz, standard S0
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals 4x (AI/DI1 - AI/DI4)
Number of inputs in group 4
Common wire GND - module ground
Combined input type DI / AI - measurement of resistance sensors, sensing of potential-free contacts and balanced loops
Galvanic isolation of inputs from internal/peripheral circuits No
Diagnostics indication of energized input by LED on module panel
DI - Parameters of DC binary inputs (group B)
Parameters valid for inputs on the terminals 14x (DI5-DI18)
Number of inputs in group 14
Common wire GND - module ground
Combined input type DI - Binary, balanced
Galvanic separation of inputs from internal circuits No
Diagnostics indication of energized input by LED on module panel
AI - Organization of analog inputs
Total number of analog inputs 4
Number of inputs per group 4
Number of analog input groups 1
Organization of analog inputs into groups 4x (AI/DI1 - AI/DI4)
Input type With common clamp
Galvanic separation from internal circuits No
Diagnostics yes, signaling on the module panel and in status
AI - Analog Input Ranges (Group A)
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input Yes
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Maximum power input 4,5 W
Module thermal/power loss 2 W
Maximum current consumption (mA) 250 mA
Power supply from CIB - maximum current consumption (mA) 160 mA
Galvanic separation of power supply from internal circuits No
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Internal protection Yes, PTC reversible fuse
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 150 g
Product dimensions (width x height x depth) 70 х 90 х 58 mm
Module width in multiples of M (17.5 mm) 4M
Module width 70 mm
Module height 90 mm
Module depth 58 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Mounting on DIN rail 35 / 7.5 (U) in the switchboard
Attention! The modules contain components sensitive to electrostatic charge, so we observe them principles for working with these circuits! We handle only on the module disconnected from the power supply! When replacing the submodules, the correctness of the deployment must be carefully checked of the submodule cavities against the tips on the motherboard. The tubes have no coding position and incorrect installation, may occur when the power is turned on again damage to the submodule or even the motherboard !!!
Connection
Connection of power and system communication connector with 2.5 mm2 screw terminal
Connection of inputs / outputs connector with screw terminal 2.5 mm2
CIB connection connector with 2.5 mm2 screw terminal
Connection description An example of module connection is shown in the following figure.
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IB-1800M - Basic documentation

1.29 MB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-IB-1800M - The C-IB-1800M is a module on a CIB bus; it has 14 binary inputs, which can be configured in the mode of the balanced loop evaluation (for ESS detectors ), and 4 universal AI/DI inputs, any of which can be adjusted to one of the followin...
  • The push-buttons scanned by the C-IB-1800M module in the control panel - ...meters, flowmeters, etc. For more information about powering, maximum power consumption, etc., see the article about the C-IB-1800M module.   Fig. 1. An example of connecting the push-buttons scanned by the C-IB-1800M module...
  • Connecting PIR detectors with double-balanced loop to the C-IB-1800M module - The C-IB-1800M module is suitable for installations where the customer prefers the star configuration of ECC detectors connection - i.e. a cable leads from each detector to the control panel for the power supply and evaluation of the detector...
  • Power dissipation of modules for calculation of switchboard heating - ...0008M; CIB, 8x RO, switching contact, 230V/16A C-OR-0008M 4,0 W TXN 133 06 C-IB-1800M; CIB, 4x AI/DI universal inputs, 14xDI including double-balanced, 4M C-IB-1800M 2,0 W...
  • CIB power supply – principles, optimization - ...the C-HM-1121M , which are powered from 230VAC, or the C-OR-0008M , C-OR-0011M-800 , C-JC-0006M and C-IB-1800M , which can be optionally powered from a 24 or 27 VDC external power supply, in which case they do not load the...
  • Metering the consumption, the Elster gas meters - ...around 0.25 s     Fig. .1 Wiring the IN-Z61 transmitter to the C-IB-1800M module   Notes: The transmitter is equipped with an RJ connector, where the cable...
  • The separate temperature sensor S-TS-01R, connected to the AI of the system - ...ure sensor can also be connected to any input of the system with an appropriate range, e.g. the AI1 to AI4 inputs of the C-IB-1800M module , the AI1 to AI3 inputs of the modules C-HM-0308M , C (R) -HM-1113M and C (R) -HM-1121M ....
  • Connecting an indoor siren - ...(here it is single balanced ), you should use a different DI system input, which supports balanced inputs (e.g. the C-IB-1800M module input), or you can also use the input to CP 1000 , which should be measured as AI; a 1 kΩ...
  • Emergency lighting - LED strip with module C-WG-0503S - For easy-to-implement emergency lighting, we can use the  C-WG-0503S , module, which will provide us with 12 VDC power supply and control (binary output) for LED strips, which can be fitted into a standard lamp. E.g. 5 cm of ordinary LED str...
  • Conection of the opening detectors - There are a number of devices available for monitoring of the opening of doors, which differ primarily in their mechanical design and the purpose. Some recommended types are described below.   When installing the detectors (magnetic conta...
  • Connecting the IMPAQ Glass Break detector to the C-WG-0503S module - The IMPAQ Glass Break detector can be used for the detection of breaking glass; it is manufactured by the TEXECOM . It is a digital acoustic glass break detector with digital sound processing, designed for sheet, laminated, hardened, tempered,...
  • Connecting exterior motion detectors (PIR) to the C-WG-0503S module - We recommend the basic variants of the Elite detectors, the TEXECOM and Tecnoalarm manufacturers  for outdoor applications of motion detectors (the perimeter protection). The Elite-EXT-TD-B detector is a PIR scanner with two...
  • Connecting interior motion detectors (PIR) to the C-WG-0503S module - The usage of interior motion detectors varies according to the type of protected areas, access of animals in the armed status, the size of the areas, etc. There are a number of manufacturers and types of detectors on the market. Possible recommende...

No data available.