CF-2142TXN 121 42

CF-2142; CIB; 2x CIB master bus with power supply, for a total of 64 slaves, communication with CP: Ethernet -for Foxtrot2 only

DI
DO
AI
AO
COM 1x ETH
1x CIB master
SENSOR
Picture Variant Variant description
CF-2142
CF-2141; Single-channel external CIB bus master, communication with CP-Ethernet
Order num. TXN 121 42
Teco code TXN 121 42
Categories CFox - System Modules
Tags -
COM - Communication - IP/Ethernet
Ethernet 10/100 Mb (ETHx) 2
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 2x CIB master (2x 1 A)
CIB - Address range of one branch of the installation bus 32 CFox I/O modules
Power supply
Supply voltage, tolerances 24 V DC, +25%, -15%, SELV
Typical power input 52 W
Maximum power input 52 W
Module thermal/power loss 6 W
Internal protection Yes
Size and weight
Weight approx. 150 g
Module width in multiples of M (17.5 mm) 3M
Product dimensions (width x height x depth) 23 × 100 × 60 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Connection
Ethernet 2x RJ-45 (internal switch)
CIB connection connector with 2.5 mm2 screw terminal
Module operation
Commissioning Set the correct address on the module. Communication on the CIB line is indicated by a flashing green LED. The absence of a configured module on the CIB bus is indicated by a flashing red LED.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)

No data available.

No data available.