CF-2141TXN 121 41
CF-2141; CIB; 1x CIB master bus with power supply, for a total of 32 slaves, communication with CP: Ethernet - for Foxtrot2 only
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 1x ETH 1x CIB master |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
CF-2141 |
CF-2141; Single-channel external CIB bus master, communication with CP-Ethernet
Order num. | TXN 121 41 |
---|---|
Teco code | TXN 121 41 |
Categories | CFox - System Modules |
Tags | - |
COM - Communication - IP/Ethernet | |
---|---|
Ethernet 10/100 Mb (ETHx) | 1 |
COM - System buses | |
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB master (1x 1 A) |
CIB - Address range of one branch of the installation bus | 32 CFox I/O modules |
Power supply | |
Supply voltage, tolerances | 24 V DC, +25%, -15%, SELV |
Typical power input | 27 W |
Maximum power input | 27 W |
Module thermal/power loss | 1 W |
Internal protection | Yes |
Size and weight | |
Weight approx. | 75 g |
Module width in multiples of M (17.5 mm) | 1,5M |
Product dimensions (width x height x depth) | 23x90x58 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Module on DIN rail |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Connection | |
Ethernet | RJ-45 |
CIB connection | connector with 2.5 mm2 screw terminal |
Module operation | |
Commissioning | Set the correct address on the module. Communication on the CIB line is indicated by a flashing green LED. The absence of a configured module on the CIB bus is indicated by a flashing red LED. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
CF-2141 - Basic documentation
1.41 MB, (EN)
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot 2 - EC Declaration of conformity (en)
590.59 kB, (EN, RU, DE, UA)
- Connecting multiple CF-2141s to a single CP-2005 - The following example shows the data connection of several CF-2141 master modules to one Foxtrot 2 basic module using the SX-1161 Ethernet switch . The example does not show the power connection. It depends on the location of individual CF-21...
- CF-2141 CIB master for Foxtrot 2 - The CF-2141 module is a CIB bus master for the Foxtrot 2 system (CP-2xxx central units), which allows the connection of one CIB line (up to 32 CIB units). The CF-2141 module provides internally a full-fledged power supply for CIB lines (it contain...
- TC800 CENTRAL MODULES - ...sed to connect CFox family modules. Both data communication and power supply of modules are realized by two wires. Up to 7 CF-2141 external CIB masters can be connected to the TC800 system via the ETCL bus via the ETH1 or ETH2 Ethernet interface. C...
- Power dissipation of modules for calculation of switchboard heating - ...kB databox, LCD-7mm, CH1-4, 1xCIB, 1x TCL2 CP-2090, 8,0 W TXN 121 41 Modul CF-2141 (single-channel external bus master CIB; 1,5M) CF-2141 4,0 W TXN 133 03...
No data available.