OS-1401TXN 114 01

OS-1401,12xDO 24 VDC, common pole, 8x0.5A, 4x 2A GO

DI
DO 12x DO
AI
AO
COM 1x TCL2 slave
SENSOR
Picture Variant Variant description
OS-1401
The IB-1301 expansion module is designed for the scanning of up to 12 binary signals 24 V DC with a common pole (minus or plus to way of connection), type 1 according to ČSN EN 61131. The module is equipped with removable screw-type connector. Inputs DI0 to DI3 allow to carry out a special functions conform to inputs on CP-1004 basic module. The inputs are galvanically isolated from the internal circuits (including power supply and communication) and groups of inputs are separated one from another. The status of each input is indicated by LED at the front module panel.
Order num. TXN 114 01
Teco code TXN 114 01
Categories Foxtrot - I / O Expansion Modules (TCL2)
Tags -
COM - System buses
TCL2 - system I/O bus 1x TCL2 slave
DO/RO - Organization of binary outputs
Total number of binary outputs 12
Organization of binary outputs into groups 4 (DO0-DO3) + 8 (DO4-DO11)
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals DO0-DO3
Number of output groups 2
Common group conductor plus
Output type transistor output
Galvanic separation from internal circuits Yes
Diagnostics indication of energized output by LED on module panel
Switching voltage 9,6 - 28.8 V DC
Switching current, output load 2 A max.
Group current 2,5 A max.
Switching time 400 μs max.
Opening time 400 μs max.
Residual current 300 μA max.
Short circuit protection Yes
Short-circuit current limitation typ. 4 A
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Reverse polarity protection Yes - The circuit will be inactive, the loads will be closed, current will flow through the protection diodes of the circuit.
Initial peak current limitation typ. 7,5 A
DO - Parameters of binary transistor outputs (group B)
Parameters valid for the terminals DO4-DO11
Number of transistor outputs 8
Common group conductor plus
Output type transistor output
Galvanic separation from internal circuits Yes
Diagnostics indication of energized output by LED on module panel
Switching current, output load 0,5A max.
Group current 4 A max.
Switching time 400 μs max.
Opening time 400 μs max.
Residual current 300 μA max.
Short circuit protection Yes - electronic
Short-circuit current limitation typ. 4 A
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Reverse polarity protection Yes - The circuit will be inactive, the loads will be closed, current will flow through the protection diode of the circuit.
Initial peak current limitation typ. 7,5 A
Initial peak current tripping time typ. 4 ms
Power supply
Nominal supply voltage (V) 24 V DC
Typical power input 1 W
Maximum power input 2 W
Module thermal/power loss 2,5 W
Maximum current consumption (mA) 100 mA
Galvanic separation of power supply from internal circuits No
Internal protection Yes, PTC reversible fuse
Size and weight
Weight approx. 100 g
Product dimensions (width x height x depth) 52 x 90 x 58 mm
Module width in multiples of M (17.5 mm) 3M
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992)
Type of device Module on DIN rail
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 55 ° C
Operating temperature minimum (° C) 0°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission A, according to EN 55022: 1999 (mod CISPR22: 1997)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Module is mounted in a vertical position on the U-rail ČSN EN 50022. Assembly installation (basic module and possibly peripheral modules) is performed according to TXV 004 10.01.
Connection
Connection of power and system communication connector with 2.5 mm2 screw terminal
Connection of inputs / outputs connector with screw terminal 2.5 mm2
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Commissioning The module is ready for operation after connecting the supply voltage. The MODE button is available on the module panel to display the currently set Ethernet IP address. The parameters of all interfaces are set in the Mosaic development environment.
Module diagnostics The basic diagnostic system of the module is a part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

OS-1401 - Basic documentation

1.24 MB, (EN)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.