SC-1102TXN 111 02

SC-1102; 1x CAN interface

DI
DO
AI
AO
COM 1x CAN
1x TCL2 slave
SENSOR
Picture Variant Variant description
SC-1102
SC-1102; 1x CAN interface
The SC-1102 module is a system communication module enabling the expansion of the central unit by another serial channel supporting the CSJ mode.
A more detailed description of serial communications and their use is given in a separate manual Serial communication of TECOMAT programmable controllers - 32-bit model (order no. TXV 004 03.01).
Communication parameters are set in the Mosaic development environment within the project.
TECOMAT FOXTROT central units allow the connection of up to 6 system communication modules SC-1101 and SC-1102, which occupy channels CH5 - CH10. It should be borne in mind that due to the transmission capacity of the TCL2 bus, these serial channels are suitable for data- and time-consuming communications.
The SC-1102 module contains 1 CAN bus controller operated in CSJ mode.
Order num. TXN 111 02
Teco code TXN 111 02
Categories Foxtrot - Communication Modules (TCL2)
Tags -
COM - Serial channels
Number of internal CAN ports 1
COM - System buses
TCL2 - system I/O bus 1x TCL2 slave
Power supply
Supply voltage, tolerances 24 V DC, +25%, -15%, SELV
Maximum power input 0,8 W
Module thermal/power loss 0,8 W
Galvanic separation of power supply from internal circuits Yes
Insulation voltage of galvanic separation 1 000 VDC
Internal protection Yes
Size and weight
Weight approx. 75 g
Product dimensions (width x height x depth) 18 x 90 x 58 mm
Module width in multiples of M (17.5 mm) 1M
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object I, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1: 2004 (mod IEC 60664-1: 1992)
Overvoltage category installation II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992)
Type of device Module on DIN rail
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 70 ° C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Module is mounted in a vertical position on the U-rail ČSN EN 50022. Assembly installation (basic module and possibly peripheral modules) is performed according to TXV 004 10.01.
Connection
Connection of power and system communication terminal block with screw terminal 2.5 mm2
Module installation tools (-) 2 mm, flat screwdriver
Module connection An example of module connection is shown in the following figure. The RS-485 line is terminated by switching both BT switches on the front panel of the module to the ON position (right). The CAN line must be terminated at a device located at each of the two ends of the line. If the device is connected in the middle of the line, termination is not performed. In this case, both BT switches will be to the left.
Module operation
Commissioning The module is operated as a system serial port, the settings are made in the Project Manager of the Mosaic programming environment, see the TXV 004 12 manual.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

SC-1102 - Basic documentation

926.98 kB, (EN)

User manuals

PDF

Foxtrot 2 - Serial communication (en)

2.25 MB, (EN, RU, DE)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • SC-1102, an additional interface CAN module - The SC-1102 module is a system communication module for expansion of the central unit by an additional port with CAN interface; the module contains one CAN bus control unit operating in the CSJ mode. A more detailed description of CAN s...
  • Power dissipation of modules for calculation of switchboard heating - ...11 01 SC-1101 1x RS-232/RS-485 interface SC-1101 0,8 W TXN 111 02 SC-1102; 1x CAN interface SC-1102 0,8 W TXN 111 11.A SC-1111-A; RF interfac...
  • Communication interface CH2 ÷ CH4, using multiple submodules - ...modules have three) are not enough, it is possible to add several serial channels RS-232, RS-485 or CAN via the SC-1101 and SC-1102 external communication modules.     Table.1: Interface combination for individual channels in ac...
  • SC-1101, an additional RS-232 and RS-485 interfaces - ...No. TXV 004 03.01). The Foxtrot basic module allows the connection of up to 6 system communication modules SC-1101 and SC-1102, which occupy the CH5 - CH10 channels. One should bear in mind that due to the transmission capacity of the TCL2 bus,...

No data available.