R-LC-0202B-A, relay moduleTXN 132 70.A

R-LC-0202B-A; RFox2, 2x DI/AI, 2x RO-800A switching contact, 1x PWM output, type A radio

DI 2x DI/AI
DO 2x RO
1x PWM
AI 2x DI/AI see DI
AO
COM 1x RFox2 slave
SENSOR
Picture Variant Variant description
R-LC-0202B-A, relay module
R-LC-0202B-A; RFox2, 2x DI, 2x RO-800A NO contact, radio type A
Order num. TXN 132 70.A
Teco code TXN 132 70.A
Categories RFox2 - Built-in Modules
Tags -
COM - Wireless network
RFox2 wireless network RFox2 Slave
Communication frequency band 868,1 MHz
Transmission power +14 dBm
Input sensitivity –108 dBm
Modulation type 2-GFSK
Communication speed 50 kbps
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals AI/DI1, AI/DI2
Number of inputs in group 2
Common wire minus
Combined input type DI/AI Active, for sensing potential-free contacts and measuring resistance sensors
Galvanic isolation of inputs from internal/peripheral circuits No
Max. measuring voltage on the connected contact 3,3 V DC
Internal input resistance 4,7 kΩ
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminals DO1, DO2
Number of relay outputs 2
Number of output groups 1
Number of outputs in group 2
Output type electromechanical relay, unprotected output
Switching current 16 A max., 100 mA min.
Switching voltage 300 V max., 5 V min.
Mechanical life min. 20 000 000 cycles
Electrical life at maximum load inductive DC13 min. 50,000 cycles
Short-circuit protection No
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 4000 V AC
Isolation voltage between groups of outputs to each other 4000 V AC
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals AI/DI1, AI/DI2
Voltage 0-3,3 V
Passive sensor Resistance transmitter 0-15 kOhm
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
Power supply
Nominal supply voltage (V) 230 V AC
Typical power input 3 W
Maximum power input 4,5 W
Maximum current consumption (mA) < 20 mA
Internal protection No
Size and weight
Weight approx. 50 g
Product dimensions (width x height x depth) 50 × 50 × 27 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Type of device In the installation box, under the cover
Working position marked on the cover
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Connection
Connection of power and system communication wires 2.5 mm2
Wireless network - antenna Built-in
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment. The module is ready for operation after connecting the supply voltage. The HW address is indicated on the label on the front panel.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Warning Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures.
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

R-LC-0202B-A - Basic documentation

111.25 kB

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

No data available.

No data available.