C-WS-0400R-LogusTXN 133 57

C-WS-0400R-Logus; CIB, Control device with short-path control, 4x button, 2x LED red / green, 2x AI / DI, 1x internal temperature

DI 2x AI / DI
4x button
DO 2x green LED
2x LED red
AI 2x AI / DI see DI
AO
COM 1x CIB slave
SENSOR 1x temperature
Picture Variant Variant description
C-WS-0400R-Logus
C-WS-0400R-Logus is a wall controller with
- 2 short way buttons
- 2x red LED
- 2x green LED
- 1x internal temperature sensor
on the CIB Common Instalation Bus®, to which 2 external temperature sensors or contacts can be connected.
Order num. TXN 133 57
Teco code TXN 133 57
Categories CFox - LOGUS, Covers and devices
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 2
Number of groups of binary inputs 1
Organization of binary inputs into groups 2x AI/DI (DI/AI1, DIAI2)
DI - Parameters of binary inputs DC (group A)
Input type microswitch button
DO/RO - Organization of binary outputs
Organization of binary outputs into groups 2x green LED
2x red LED
AI - Analog Input Ranges (Group A)
Voltage 0-2 V
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-100 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
Temperature measurement error ± 1°C
AI recovery period 5 s typically
Parameter des Temperatursensors
Temperature - Sensor type NTC 12k
Temperature - Measurement range -10 ÷ +55 °C
Temperature - Settling time 150 min.
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Maximum power input < 0,5 W
Power supply from CIB - typical current consumption (mA) 15 mA
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Internal protection No
Size and weight
Weight approx. 75 g
Product dimensions (width x height x depth) 86 × 86 × 38 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Type of device On the wall
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55022: 1999 (mod CISPR22: 1997)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The sensor module is mounted in a vertical position on a standard installation box with a spacing of fixing screws of 60 mm.
Method:
1. Connect the wires to the next wiring
2. Screw the switch module to the installation box (pay attention to the position)
3. Click the box
4. Slide on and snap the fingerboard
Connection
Connection description The controller with short-path control with the possibility of connecting external sensors is implemented as a standard unit on a two-wire CIB bus, which ensures communication and power supply of the entire sensor. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the basic unit FOXTROT or an external module, for example CF-1141. Further information can be found in the manual “Peripheral modules on the CIB bus” TXV 004 13.
Connection of power and system communication terminal block with screw terminal 1.5 mm2
Connection of inputs / outputs terminal block with screw terminal 1.5 mm2
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Instructions The module does not require any maintenance if the general conditions for installation are observed. The tasks that require the module to be assembled or disassembled are always performed with the CIB bus switched off.

Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-WS-0400R-Logus - Basic documentation

123.72 kB

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-WS-0x00R-Logus - ...bus are available in two versions: The C-WS-0200R-Logus with one fingerboard (2 push-buttons – up and down). The C-WS-0400R-Logus with two fingerboards (4 push-buttons – each fingerboard has a push-button up and down).  ...
  • Controllers on the CIB bus, the Logus design - ...ons using the control unit C-WS-0200R-Logus with one fingerboard (2 buttons - one at the top and one below), or the C-WS-0400R-Logus with two fingerboards (4 buttons - each fingerboard has a button at the top and below). Both types of dri...

No data available.