C-RQ-0600S-SHSTXN 133 61.S

C-RQ-0600S-SHS; CIB, built-in module for connection of temperature, humidity, motion and CO2 sensors, 2x AI / DI, (DI / AI2 input intended for dew sen

DI 2x AI/DI
DO
AI 2x AI / DI see DI
AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-RQ-0600S
C-RQ-0600S-SHS
The C-RQ-0600S module is the basis for several variants of modules designed for the connection of a humidity and temperature sensor, or a CO2 sensor, or an infrared motion sensor and universal analog or binary signals.
Universal AI / DI inputs can be set to binary or analog with the possibility of measuring temperature sensors: support sensors PT1000, Ni1000, or a sensor with a NTC12k or KTY81-121 thermistor against a common GND wire. For another type of resistance sensor, a resistance measurement range of 0 to 160 kΩ can be selected, but the conversion to temperature and linearization must be performed in the user program.
The binary signals are connected to the inputs only as a potential-free contact against the common GND conductor. The binary input can also operate in balanced input mode.
Order num. TXN 133 61.S
Teco code TXN 133 61.S
Categories CFox - Built-in modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals DI/AI1, DI/AI2
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input 2x 1k1 (tamper/0/1/tamper)
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Power supply from CIB - typical current consumption (mA) 15 mA
Power supply from CIB - maximum current consumption (mA) 20 mA
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 7 g
Product dimensions (width x height x depth) 55 × 27 × 20 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 70 ° C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The module C-DM-0001B-SL is mounted in arbitrary positioninto instalation box under a lid or under device located in box.
Connection
Connection description An example of module connection is shown in the following figure.
Connection of power and system communication terminal block with spring terminal 0.15-0.5 mm2, push-in
Connection description An example of module connection is shown in the following figure.
Module operation
Commissioning The module is operated, set and diagnosed by the MOSAIC or FoxTool programming environment.

Further information can be found in the manual Peripheral modules on the CIB TXV 004 13.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-RQ-0600S - Basic documentation

1.59 MB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB
  • C-RQ-0600S - The C-RQ-0600S module is a basis for several versions of modules designed to connect temperature and humidity sensors, CO2 sensors, infrared motion sensors and universal analogue or binary signals. The universal AI/DI inputs can be set to binary...
  • C-RQ-0600R-RHT - ...HT module is fitted with a combined temperature and relative humidity sensor. The module consists of the inbuilt bus part C-RQ-0600S and the design part, which includes the mechanical segment (a dummy plate) in a specific design and a mounted s...
  • C-RQ-0600R-PIR - ...sensor or a combined temperature and humidity sensor can be added on request. The module consists of the inbuilt bus part C-RQ-0600S and the design part, which includes the mechanical segment (a dummy plate) in a specific design and a mounted s...
  • Controlling lights by a CFox C-RQ-0600R-PIR detector - ...of two parts, which are supplied already connected – see the figure. The terminals at both ends of the C-RQ-0600S module are shown in the bottom right corner of the picture....