C-RC-0011RTXN 133 77.01

C-RC-0011R CIB, wall room controller, white/white

DI
DO
AI 1x AI for NTC 12k
AO
COM 1x CIB slave
SENSOR Temperature
Humidity
5x capacitive button
C-RC-0011R is a programmable interior wall controller for controlling heating (air conditioning), ventilation, etc. It allows you to set the heating time program throughout the week, change the heating mode, measure room temperature and humidity and measure the external temperature with an NTC sensor.
It is connected via the CIB Common Installation Bus® to the control unit, which can provide the module with additional measured values for display.
The display allows you to display 53 icons 1 main and 1 secondary value and their units. At the bottom of the display there are 5 capacitive buttons.

The module is designed for operation in a normal, chemically non-aggressive environment. It consists of two parts: the bottom and the cover with a printed circuit board, terminals and display. It is fixed with 2 or 4 screws to the installation box 60 mm diameter flush-mounted box or to the wall.

The module is designed as a standard unit on the CIB bus, integrated into the Mosaic environment.
Order num. TXN 133 77.01
Teco code TXN 133 77.01
Categories CFox - Teco, Touch control panels
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
Parameter des Temperatursensors
Temperature - Sensor type SI 7020
Temperature - Measurement range 0°C ÷ 50°C
Temperature - Resolution 0,1 °C
Temperature - Measurement accuracy typ. ±0,4 °C
Humidity sensor parameters
Relative humidity - Sensor type SI 7020
Relative humidity - Measurement range 0 ÷ 100 %RH
Relative humidity - Resolution 1 % RH
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Maximum power input 0,15 W
Power supply from CIB - maximum current consumption (mA) 10 mA
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Power supply from CIB - internal protection No
Size and weight
Weight approx. 125 g
Product dimensions (width x height x depth) 109 × 99 × 19,8 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 3:2012 (mod IEC 60730-1:2010)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device On the wall
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 °C to + 55 °C
Operating temperature minimum (° C) 0°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Indoor wall mounting
Assembly description The module is mounted in a vertical position on a standard installation box with a spacing of fixing screws of 60 mm or directly on the wall. Mounting holes are pre-molded in the bottom of the C-RC-0011R. The lower part should be screwed to the wall in a position where the inscription "LOWER" is legible. The lower part and the upper part (with display) are snapped in by latches, by slightly pressing the sides of the box and by light pulling both parts can be separated from each other.
Connection
Connection of power and system communication terminal block with screw terminal 1.5 mm2
Module connection The module is implemented as a CIB bus module, which provides communication and power supply to the module. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the FOXTROT basic unit with an internal module or the external module CF-1141 with FW version 1.8 and higher. For more information, see the manual Peripheral modules on the CIB bus TXV 004 13.
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

Files for designers

PDF

C-RC-0011R- Basic documentation

190.67 kB
ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)
  • C-RC-0011R - The C-RC-0011R interior control unit with an LCD display and 5 touch buttons is designed primarily for local control of heating, cooling and ventilation systems for office buildings, such as remote control for heating systems, etc. The disp...
  • TCIB_CRC011R_ICO Structure - Hello, I have bought a C-RC-0011R device and I use it in Display only mode. I would like to load the Icon structure on the device but I didn't find the TCIB_CRC011R_ICO structure in the libraries. I made a structure with the same fields but it does...
  • TCIB_CRC011R_ICO Structure - ...l. You can define the structure with the same name which is compiled conditionally. Then it doesn't depend if the module C-RC-0011R is added into the project. If yes, it will be used a structure defined in CONFIG.ST file. If no then it will be us...