C-JC-0006MTXN 133 68

C-JC-0006M; CIB, 6x blind actuator, (6x2 RO - dependent switching, local function), 230VAC / 5A

DI
DO 6x 2xRO
AI
AO
COM 1x CIB slave
SENSOR
Picture Variant Variant description
C-JC-0006M
C-JC-0006M; CIB, 6x blind actuator, (6x2 RO - dependent switching, local function), 230VAC / 5A
Order num. TXN 133 68
Teco code TXN 133 68
Categories CFox - Modules on DIN rail
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
RO - Parameters of binary relay outputs (group A)
Number of relay outputs 12
Number of output groups 6
Organization of relay outputs into groups 1(DO1)+1(DO2)+1(DO3)+1(DO4) +1(DO5)+1(DO6)
Output type electromechanical relay, unprotected output
Contact type Up-0-Down, three-state actuator
Diagnose Alarm signaling on panel module
Switching current 3 A max., 100 mA min.
Switching voltage 250 V AC max., 5 V AC min., 30V DC max.
Contact closing time typ. 15 ms
Contact opening time typ. 5ms
Mechanical life min. 5,000,000 cycles
Electrical life at maximum resistive load min. 200,000 cycles
Short-circuit protection No
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 3750 V AC
Insulation voltage between contacts 750 V AC
Notice! The outputs of DOxu and DOxd are blocked from each other
Power supply
Power supply from CIB - voltage 24/27 V DC
Maximum power input 2,5 W
Module thermal/power loss 1,8 W
Power supply from CIB - maximum current consumption (mA) 90 mA
Power supply from CIB - internal protection Yes, returnable fuse
Size and weight
Weight approx. 200 g
Product dimensions (width x height x depth) 70 х 90 х 58 mm
Module width in multiples of M (17.5 mm) 4M
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Blind module C-JC-0006M is mounted in a vertical position on the U-rail ČSN EN 50022. installation is performed according to TXV 004 13.
Connection
Connection of power and system communication connector with 2.5 mm2 screw terminal
Connection of inputs / outputs connector with screw terminal 2.5 mm2
Cross-section of connected wires fixed (min) 0,75 mm2
Cross-section of connected wires fixed (max) 2,5 mm2
Cross-section of connected wires stranded (min) 0,75 mm2
Cross-section of connected wires stranded (max) 2,5 mm2
Module installation tools (-) 3 mm, flat screwdriver
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-JC-0006M - Basic documentation

1.37 MB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-JC-0006M - The C-JC-0006M module is equipped with6 outputs designed for standard blinds control – i.e. the so-called three-point-control: opening-idle-closing. The module can also be used for three-point valve control, etc. The module is internall...
  • Control of asynchronous motors for blinds and awnings, the C-JC-0006M - ...ors reversed by switching the coil (like in the 3-position actuators for valves and dampers), there is a specialized module C-JC-0006M equipped with 6 outputs for controlling blinds. In this module, blocking simultaneous switching of both outputs i...
  • Power dissipation of modules for calculation of switchboard heating - ...switching contact, 230V/16A (inrush 800A) C-OR-0011M-800 5,0 W TXN 133 68 C-JC-0006M; CIB, 6x louver actuator, 6x 2RO - dependent switching, 230VAC/5A C-JC-0006M 1,8 W...
  • CIB power supply – principles, optimization - ...ere are modules, e.g. the C-HM-1121M , which are powered from 230VAC, or the C-OR-0008M , C-OR-0011M-800 , C-JC-0006M and C-IB-1800M , which can be optionally powered from a 24 or 27 VDC external power supply, in which case...
  • Valves for controlling water (the main water valve, etc.) - ...o use the same output connections with mechanical interlocking switches of the two outputs , or a specialized module C-JC-0006M ....
  • Control of ROTO roof windows - ...tacts of the system can be used, or the specialized blinds outputs. The following example shows the connection to the C-JC-0006M module; if the standard cable supplied with the ROTO unit is used, the example also lists the colours of the wi...
  • The control of venetian blinds and roller blinds - ...in 1ph asynchronous motor for blinds: a) The motor is inactive, both outputs (e.g. the DO1u and DO1d outputs in the C-JC-0006M module) are open. b) The motor is turning up, the DO1u output is switched to the phase of the 230VAC supply wi...

No data available.