C-IT-0202STXN 133 66
C-IT-0202S; CIB, 2x AI / DI Temperature / contact, 2x AO (0-10V)
DI | 2x DI/AI |
---|---|
DO | |
AI | 2x DI/AI see DI |
AO | 2x AO |
COM | 1x CIB slave |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
C-IT-0202S |
The C-IT-0202S module is a dimensionally minimized module on the CIB bus for control by two independent analog outputs.
At the same time, it is intended for connection of two passive temperature sensors or binary signals from contacts and their conversion into data for the CIB wiring bus.
- The resistance from the optional Pt1000, Ni1000, NTC 12k, KTY81-121 sensors against the common GND conductor is linearized in the module and converted directly to a numerical temperature value and then transferred to the basic module via the CIB bus. It is possible to choose the measurement of other resistances in the range of 0 to 160 kΩ, but the conversion to temperature and linearization must be performed in the control panel at the level of the application program.
- Binary signals are connected to the inputs only as a free contact against the common GND conductor.
- The voltage of the analog output 0 - 10 V is connected on the conductor against the common conductor GND.
At the same time, it is intended for connection of two passive temperature sensors or binary signals from contacts and their conversion into data for the CIB wiring bus.
- The resistance from the optional Pt1000, Ni1000, NTC 12k, KTY81-121 sensors against the common GND conductor is linearized in the module and converted directly to a numerical temperature value and then transferred to the basic module via the CIB bus. It is possible to choose the measurement of other resistances in the range of 0 to 160 kΩ, but the conversion to temperature and linearization must be performed in the control panel at the level of the application program.
- Binary signals are connected to the inputs only as a free contact against the common GND conductor.
- The voltage of the analog output 0 - 10 V is connected on the conductor against the common conductor GND.
Order num. | TXN 133 66 |
---|---|
Teco code | TXN 133 66 |
Categories | CFox - Built-in modules |
Tags | Sales and production discontinued |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
DI - Organization of binary inputs | |
Total number of binary inputs | 2 |
Number of groups of binary inputs | 1 |
DI - Parameters of binary inputs DC (group A) | |
Parameters valid for inputs on the terminals | DI/AI1, DI/AI2 |
Number of inputs in group | 2 |
Common wire | GND - module ground |
Combined input type | DI/AI Active, for sensing potential-free contacts and measuring resistance sensors |
Galvanic separation of inputs from CIB bus | No |
Max. measuring voltage on the connected contact | 3,3 V DC |
Internal input resistance | 2,2 kΩ |
Max. resistance for closed contact, log. 1 | < 0,5 kΩ |
Min. resistance for open contact, log. 0 | > 1,5 kΩ |
Balanced resistance input | 2× 1k1 (tamper/0/1/tamper) |
AI - Analog Input Ranges (Group A) | |
Parameters valid for inputs on the terminals | DI/AI1, DI/AI2 |
Passive sensor | Pt1000, W100 = 1,385 (-90 to +400 ° C) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Ni1000, W100 = 1.617 (-60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-160 kOhm |
Passive sensor | KTY81-121; PTC thermistor (-55 to + 125 °C) |
Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
DI: Voltage-free contact | 0 when> 1.5 kOhm, 1 when <0.5 kOhm |
DI: Balanced resistance input | 2x 1k1 (tamper/0/1/tamper) |
Input impedance in signal range RTD | > 2,2 kΩ |
Resistance measurement error - maximum error at 25 ° C | ± 0.5% of full scale |
AO - Analog output parameters | |
The number of groups of analogue outputs | 1 |
Parameters valid for the terminals | AO1, AO2 |
Common wire of group | GND terminal |
Galvanic isolation from internal circuits | No |
Output type | active voltage output |
Voltage output - voltage | 0 - 10 V |
Voltage output - Minimum resolution | 1 % |
Voltage output - Adjustable range | 0 ÷ 130 % Ujm |
Voltage output - Load resistance | >1 kΩ |
Voltage output - Load capacity | 50 nF |
Power supply | |
Supply voltage, tolerances | 24/27 V DC from CIB bus |
Power supply from CIB - typical current consumption (mA) | 8 mA |
Power supply from CIB - maximum current consumption (mA) | 10 mA |
Power supply from CIB - internal protection | Yes, returnable fuse |
Size and weight | |
Weight approx. | 15 g |
Product dimensions (width x height x depth) | 35 × 30 × 20 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | In the installation box, under the cover |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 ° C to + 70 ° C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 ° C to + 85 ° C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | ČSN EN 55022 ed2:2007 (mod CISPR22:2005) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Connection | |
Connection of power and system communication | terminal block with spring clamp 1 mm2, push-in |
Connection of inputs / outputs | terminal block with spring clamp 1 mm2, push-in |
Module connection | An example of module connection is shown in the following figure. A terminal block with pen terminals is intended for connecting the CIB bus, inputs and analog outputs. These are intended for the connection of a rigid conductor. If it is necessary to connect a stranded wire, it is necessary to crimp a suitable cable gland at its end. The wire is connected by inserting it into the oval hole. The wire is released by pushing the tip of a flat-blade screwdriver (0.4 mm x 2 mm) into the rectangular hole above the wire hole. |
Module operation | |
Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-IT-0202S- Basic documentation
206.83 kB
C-IT-0202S - Basic Documentation
1.00 MB, (EN)
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
C-IT-0202S - Technical drawing M01 DWG
42.87 kB
C-IT-0202S - Technical drawing S01 DWG
45.22 kB
C-IT-0202S - Technical drawing M01 DXF
38.32 kB
C-IT-0202S - Technical drawing S01 DXF
43.61 kB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
No data available.