PS2-60/27TXN 070 40

PS2-60 / 27 Two-level backup power supply with battery charger (with UPS function) 230VAC / 27.2VDC, 2.2A; 12VDC 0.3A in 6M case

DI
DO
AI
AO
COM
SENSOR
Picture Variant Variant description
PS2-60/27
PS2-60/27 Power supply 230VAC/27,2VDC, 2,2A; 12VDC 0,3A in 6M housing
Order num. TXN 070 40
Teco code TXN 070 40
Categories Foxtrot - Power Modules
Tags -
Power supply
Nominal supply voltage (V) 230 V AC
Input voltage frequency 47 - 63 Hz
Maximum power input 106 W
Module thermal/power loss 10 W
Bridging a power failure 40 ms max. (Ui=170 V AC, Io=2.2 A)
Power supply efficiency type. 87% (Ui = 230 V AC)
Output voltage 27,2 V DC ±0,5 % / 12 V DC ±0,5 % SELV
Continuous output current 2,2 A/0,3 A (27,2/12V DC)
Output power continuous 60 W
Size and weight
Product dimensions (width x height x depth) 105 × 92 × 58 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2: 5.2008, ČSN EN 61558-1 ed.2: 6.2006
Electromagnetic compatibility, Mechanical endurance
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)

HW documentation

PDF

PS2-60/27

313.44 kB

Files for designers

DXF

PS2-60/27

284.54 kB
DXF

PS2-60/27

61.77 kB
DWG

PS2-60/27

106.91 kB
DWG

PS2-60/27

48.27 kB
  • Backup power supply CP-1004, the PS2-60/27 source - ...LV requirements, and it must be designated for charging the connected batteries; as a standard it is recommended to use the PS2-60/27 . The batteries are sealed 12 V lead-acid type (2 pcs connected in series) with a capacity of 1.3 to...
  • The power supply PS2-60/27 - The power supply PS2-60/27 (order. no.: TXN 070 40) is a mains switch-mode power supply with stabilized output voltage at 27.2VDC/2.2A and 12VDC/0.3A with a total power output of 60 W. It is designed to supply power to the Foxtrot control...
  • Power dissipation of modules for calculation of switchboard heating - ...order number name type power loss max. TXN 070 40 PS2-60/27 Power supply 230VAC/27,2VDC, 2,2A; 12VDC 0,3A PS2-60/27 10,0 W TXN 105 52...
  • CF-1141 external CIB master - ...ule from the output BACKUP (terminals B8 and B9), but only if the total power consumption of the assembly conforms to the PS2-60/27 source. It is also possible to power and provide backup to the CF-1141 module and the Foxtrot basic module...
  • CIB power supply – principles, optimization - ...1000 ) and an external decoupling module,the C-BS-0001M , should be connected directly in the power supply output ( PS2-60/27 or e.g the DR-60-24 ).   No element must be inserted between the supply source output and...
  • CP-1000, a power supply with a backup - ...n all its modes for the required time, while the power supply must provide charging of the connected backup batteries. The PS2-60/27 power supply with 27.2 VDC output voltage is specified to power the whole system and to charge the backup batterie...
  • CP-1000, power supply without a backup - ...backup Notes: We recommend a stabilized 24 VDC power supply, complying with SELV requirements, and the PS2-60/27 is our standard recommendation. Power consumption of the CP-1000 is the sum of its own power (typically 3 W) and th...
  • Foxtrot basic module power supply - ...wer supply. If a battery backup is required, the system can be supplied from a 27.2 VDC source. It is recommended to use the PS2-60/27 power supply. For detailed information regarding the source, see Chapter 2.1.1 The PS2-60/27 power supply . Maxim...
  • System power supply – power sources - ...p ) we recommend the DR-60-24 or the DR-100-24 sources, and as to the power supply from a backup battery we recommend the PS2-60/27 supply (see Chap. 2.2.2.Power supply with a backup ).   Protection of power supply: The power...
  • Connecting the SSA-R2000V keypad to the C-WG-0503S module - ...the C-WG-0503S module, so the sensor must be powered from an external source (e.g. from the 12 V output level of the PS2-60/27 power supply, or from the DR-15-12 supply). The distance is only valid for cards and identifiers suppli...
  • Connecting the SSA-R1000/1001 sensor to the C-WG-0503S module - ...the C-WG-0503S module, so the sensor must be powered from an external source (e.g. from the 12 V output level of the PS2-60/27 power supply, or from the DR-15-12 supply). The distance is only valid for cards and identifiers suppli...
  • Connecting an indoor siren - ...he connection of the SA-913 T internal siren to the CP-1000 basic module with a standard power supply with a backup - the PS2-60/27  power supply and 2 x 12 V batteries. The siren is triggered by the DO1 relay output; any relay output of t...

No data available.