C-WG-0503R-Decente, black mattTXN 133 53.01OD34

C-WG-0503R-T-Decente, black matt; CIB, Interior RFID reader, 2x LED, 1x buzzer, 1x temperature sensor, 1x DI TTL

DI 3x DI (5V TTL)
2x DI/AI see AI
DO 3x DO (NPN)
AI 2x DI / AI see DI
(R, binary, balanced)
AO Power output 12V / 60mA
COM 1x CIB slave
1x Wiegand
SENSOR 1x RFID
Picture Variant Variant description
C-WG-0503R-Decente, snow white Color: Snow white
C-WG-0503R-Decente, anthracite black Color: Anthracite black
C-WG-0503R-Decente, aluminum Color: Aluminum
C-WG-0503R-Decente, graphite Color: Graphit
C-WG-0503R-Decente, gold Color: Gold
C-WG-0503R-Decente, titanium Color: Titanium
C-WG-0503R-Decente, black matt Color: Black matt
C-WG-0503R-Decente, white matt Color: White matt
C-WG-0503R-Decente, snow white; CIB, Interior RFID reader, 2x LED, 1x buzzer, 1x temperature sensor, 1x DI TTL
Order num. TXN 133 53.01OD34
Teco code TXN 133 53.01OD34
Categories CFox - DECENTE, Covers and devices
Tags Temporarily unavailable
COM - Serial channels
Wiegand protocol - format 42 bits , 34bits , 26 bits , 40bits transparent
Wiegand protocol - number of bytes 5 , 4 , 3 , 5
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals DI1-DI3
Number of inputs in group 3
Common wire +12V DC
Input type TTL 5V
Galvanic separation of inputs from CIB bus No
Pull-up resistor 3,9 kΩ
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals DO1-DO3
Number of transistor outputs 3
Number of outputs in group 3
Organization of transistor outputs into groups 3 (DO1-DO3)
Common group conductor +12 V
Output type NPN open collector
Galvanic separation from internal circuits No
Diagnostics No
Output voltage 30 V DC, max., open collector NPN
Output current 30 mA
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Number of analog input groups 1
Organization of analog inputs into groups 2x (DI/AI4, DI/AI5)
Input type With common clamp
Common wire Minus
Galvanic separation from internal circuits No
Diagnostics overload signaling in status word
Digital resolution 10 bit
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals DI/AI4, DI/AI5
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input 2x 1k1 (tamper/0/1/tamper)
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Power supply from CIB - typical current consumption (mA) 20 mA
Power supply from CIB - maximum current consumption (mA) 85 mA
Power supply from CIB - internal protection No
Internal auxiliary power supply - voltage +12 V DC
Internal auxiliary power supply - current max. 60 mA
Size and weight
Weight approx. 75 g
Product dimensions (width x height x depth) 86 × 86 × 35mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod)
Degree of pollution 1, according to ČSN EN 60664-1: 2004 (mod IEC 60664-1: 1992)
Overvoltage category installation II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 55 ° C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) 0°C
Operating relative humidity from 10 % up to 95 % without condensation
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55022: 1999 (mod CISPR22: 1997)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Installation
Assembly description Indoor wall mounting
Connection
Warning All external circuits connected to the module must meet the conditions for SELV circuits!
Connection of power and system communication Loose wires in the connector / 0.15-0.5 mm2
Connection of inputs / outputs Loose wires in the connector / 0.15-0.5 mm2
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.

No data available.