C-RQ-0600R-CO2-LOGUS goldTXN 133 61.05LTDU
C-RQ-0600R-CO2-LOGUS gold; CIB, Interior CO2 sensor, 1x AI / DI
DI | 2x AI/DI |
---|---|
DO | |
AI | 2x AI / DI see DI |
AO | |
COM | 1x CIB slave |
SENSOR | 1x CO2 |
Picture | Variant | Variant description |
---|---|---|
C-RQ-0600R-CO2-LOGUS, white, TBR | Color: White | |
C-RQ-0600R-CO2-LOGUS, ivory, TMF | Color: Ivory | |
C-RQ-0600R-CO2-LOGUS, ice, TGE | Color: Ice | |
C-RQ-0600R-CO2-LOGUS, pearl, TPE | Color: Pearl | |
C-RQ-0600R-CO2-LOGUS, aluminum, TAL | Color: Aluminum | |
C-RQ-0600R-CO2-LOGUS, gray, TIS | Color: Grey | |
C-RQ-0600R-CO2-LOGUS černý | Color: Black | |
C-RQ-0600R-CO2-LOGUS gold | Color: Gold |
C-RQ-0600R-CO2-LOGUS; CIB, Interior CO2 sensor, 1x AI / DI, white
Order num. | TXN 133 61.05LTDU |
---|---|
Teco code | TXN 133 61.05LTDU |
Categories | CFox - LOGUS, Covers and devices |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
AI - Analog Input Ranges (Group A) | |
Parameters valid for inputs on the terminals | DI/AI1, DI/AI2 |
Passive sensor | Pt1000, W100 = 1,385 (-90 to +400 ° C) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Ni1000, W100 = 1.617 (-60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-160 kOhm |
Passive sensor | KTY81-121; PTC thermistor (-55 to + 125 °C) |
Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
DI: Voltage-free contact | 0 when> 1.5 kOhm, 1 when <0.5 kOhm |
DI: Balanced resistance input | 2x 1k1 (tamper/0/1/tamper) |
Resistance measurement error - maximum error at 25 ° C | ± 0.5% of full scale |
CO2 sensor parameters | |
CO2 - Sensor type | infrared radiation (NDIR) |
CO2 - Measurement range | 0 ÷ 2000 ppm / 0 ÷ 5000 ppm |
CO2 - Resolution | 1 ppm |
CO2 - Measurement error | <5% of range |
Power supply | |
Supply voltage, tolerances | 24/27 V DC from CIB bus |
Size and weight | |
Weight approx. | 75 g |
Product dimensions (width x height x depth) | 55 × 27 × 20 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | In the installation box on the wall |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | ČSN EN 55022 ed2:2007 (mod CISPR22:2005) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description | The module C-DM-0001B-SL is mounted in arbitrary positioninto instalation box under a lid or under device located in box. |
Connection | |
Connection description | An example of module connection is shown in the following figure. |
Module operation | |
Commissioning |
The module is operated, set and diagnosed by the MOSAIC or FoxTool programming environment. Further information can be found in the manual Peripheral modules on the CIB TXV 004 13. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
No data available.
No data available.