C-RI-0401R-Time, ivory / ice whiteTXN 133 47.Ti21

C-RI-0401R-Time; CIB, Indoor IR receiver / transmitter, sensors: 1x light intensity, 1xtemperature, 1x AI / DI, ivory / ice white

DI 1x DI/AI
 
DO
AI 1x DI / AI see DI
AO
COM 1x CIB slave
1x IR receiver / transmitter
SENSOR 1x Temperature
 
Picture Variant Variant description
C-RI-0401R-Time, white / ice white Color: White / Ice white
C-RI-0401R-Time, white / white Color: White / White
C-RI-0401R-Time, white/ ice gray Color: White / Ice gray
C-RI-0401R-Time, titanium Color: Titanium
C-RI-0401R-Time, ivory / ice white Color: Ivory / ice white
C-RI-0401R-Time, coffee / ice opal Color: Coffee / ice opal
C-RI-0401R-Time, lungo / milky white Color: Lungo / milky white
C-RI-0401R-Time, antique silver Color: Old silver
C-RI-0401R-Time, champagne Color: Champagne
C-RI-0401R-Time, anthracite Color: Anthracite
C-RI-0401R-Time, steel Color: Steel
C-RI-0401R-Time; CIB, Indoor IR receiver / transmitter, sensors: 1x light intensity, 1xtemperature, 1x AI / DI, white / ice white
Order num. TXN 133 47.Ti21
Teco code TXN 133 47.Ti21
Categories CFox - Time, Covers and devices
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 1
DI - Parameters of binary inputs DC (group A)
Combined input type DI/AI Active, for sensing potential-free contacts and measuring resistance sensors
Galvanic isolation of inputs from internal/peripheral circuits No
Diagnostics signaling of excited input in Mosaic
Input current at log. 1 (typ.) 3,3 mA
Delay from log. 0 to log. 1 10 ms
Delay from log. 1 to log. 0 300 ms
The minimum width of the captured pulse 10 ms
Max. measuring voltage on the connected contact 3,3 V DC
AI - Organization of analog inputs
Total number of analog inputs 1
Common wire Plus
Galvanic separation from internal circuits No
External power supply No
Digital resolution 12 bit
Converter type Approximation
conversion time 500 μs
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals DI/AI1
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
Input impedance in signal range RTD > 1 kΩ
Resistance measurement error - maximum error at 25 ° C ± 2% of full scale
Resistance measurement error - temperature coefficient ± 0,1% of full scale
Resistance measurement error - non-linearity ± 0.2% of full scale
Resistance measurement error - repeatability at steady conditions 0.5% of full scale
Detection of disconnected sensor No
Lighting sensor parameters
Lighting - Sensor type Photodiode BPW21
Lighting - Measuring range 0 lx ÷ 50000 lx
Lighting - Measurement error <5% of range
Lighting - Linearity of measurements ± 0.2% of full scale
Lighting - Repeatability under steady state conditions 0.5% of full scale
IR receiver / transmitter parameters
Number of IR receivers 1
Number of IR transmitters 1
Demodulator carrier frequency 36 kHz
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Power supply from CIB - maximum current consumption (mA) 25 mA
Internal protection No
Size and weight
Weight approx. 75 g
Product dimensions (width x height x depth) 86 × 86 × 35 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device In the installation box on the wall
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 55 ° C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module, design part and mechanics are packed in bags. All parts are placed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport.

The product must not be exposed to direct weather conditions during transport and storage. The product may only be stored in clean rooms free of conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C.
Installation
Assembly description The C-RI-0401R module is mounted in a vertical position on
wall, above a standard installation box with a pitch
fixing screws 60 mm. Assembly installation
(basic module and possibly peripheral modules)
performed according to TXV 004 13.
Connection
Connection description The combined module is implemented as a CIB bus module, which provides communication and power supply to the module. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is a FOXTROT base unit or module, such as the CF-1141.

Further information can be found in the manual Peripheral modules on the CIB TXV 004 13.
Connection of power and system communication Ribbon flat conductors 0.15 / 0.5 mm2
Connection of inputs / outputs terminal block with spring clamp 0.15-0.5 mm2, push-in
Module operation
Module configuration The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-RI-0401R - Basic documentation

115.43 kB

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.