C-KY-0001RTXN 133 84

C-KY-0001R; CIB, OLED display, Touch Keypad 16x buttons, RFID card/tag reader

DI 2x AI/DI
DO
AI 2x AI / DI see DI
AO
COM 1x CIB slave
SENSOR
  • Temperature
  • RFID reader
  • 16 buttons,
  • OLED display - 128x64 px
Picture Variant Variant description
C-KY-0001R
C-KY-0001R is a universal wall controller on the CIB Common Installation Bus® with:
- glass face,
- OLED display,
- 16 touch capacitive buttons,
- RFID card / tag reader
- internal temperature sensor.
It contains 2 AI / DI inputs for external sensors or contacts.
Order num. TXN 133 84
Teco code TXN 133 84
Categories CFox - Teco, Touch control panels
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Common wire GND terminal
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals AI/DI1, AI/DI2
Voltage 0-2 V
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-100 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input 2x 1k1 (tamper/0/1/tamper)
Input impedance in signal range RTD > 2,0 kΩ
Resistance measurement error - maximum error at 25 ° C ± 2% of full scale
Parameter des Temperatursensors
Temperature - Measurement range 0°C ÷ 50°C
Temperature - Resolution 0,1 °C
Temperature - Measurement accuracy typ. ±0,4 °C
RFID reader parameters
Frequency 13.56 MHz
RFID card type ISO14473A
RFID card type ISO/IEC 15693
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Typical power input 2 W
Maximum power input 2 W
Module thermal/power loss 2 W
Power supply from CIB - maximum current consumption (mA) 50 mA
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Power supply from CIB - internal protection No
Size and weight
Weight approx. 200 g
Product dimensions (width x height x depth) 123,5 x 81,5 x 32 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP40 front, IP20 rear
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device On the wall
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 °C to + 55 °C
Operating temperature minimum (° C) 0°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The C-KY-0001R module is mounted vertically using a mounting frame (see the following figure) in an installation box with a hole spacing of 83.5 mm either:
1) into the installation box under the Bticino plaster type 503E 106x71x52 mm and the Italtronic frame type P14001305C
2) in the installation box in plasterboard Bticino type PB503 109x68x51 and frame Italtronic type P14001305C
3) into a hole 85x56 mm in a flat panel using the set TXF 790 29 containing attachments, washers and mounting screws.

Installation boxes, frames and kits are not included in the delivery, they must be ordered separately!
Connection
Connection of power and system communication connector with 1.5 mm2 screw terminal
Connection of inputs / outputs connector with screw terminal 1.5 mm2
Module connection An example of module connection is shown in the following figure.
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Instructions Cleaning of the glass panel is performed with means suitable for glass surfaces that do not contain any solvents.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

User manuals

PDF

C-KY-0001R - Basic documentation (en)

447.84 kB, (EN)
PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-KY-0001R - C-KY-0001R is a glass wall controller with capacitive buttons designed for PTZS system. It contains an RFID reader, temperature sensor, two universal inputs for connecting other temperature sensors (eg floor temperature, outdoor temperature), wind...