IB-8305TXN 183 05

IB-8305, 12x DI, 230 V AC, type 1

DI 12xDI
DO
AI
AO
COM 1x TCL3
SENSOR
Picture Variant Variant description
IB-8305
The IB-8305 module is intended for sensing 12 binary signals of 230 V AC with a common terminal, type 1. The module is equipped with a connector with screwless terminals.
Order num. TXN 183 05
Teco code TXN 183 05
Categories TC800 - I / O expansion modules
Tags -
COM - System buses
TCL3 - system I/O bus 1x TCL3 slave
DI - Organization of binary inputs
Total number of binary inputs 12
Organization of binary inputs into groups 3x (DI0-DI2); 3x (DI3-DI5); 3x (DI6-DI8); 3x (DI9-DI11)
DI - Parameters of binary AC inputs
Parameters valid for AC inputs on the terminals DI0-DI11
Total number of binary AC inputs 12
Number of groups of AC inputs 4
Number of AC inputs in group 3
Organization of binary inputs into groups 3x (DI0-DI2); 3x (DI3-DI5); 3x (DI6-DI8); 3x (DI9-DI11)
Input type Typ 1 (IEC)
Galvanic isolation of internal circuits Yes
Power supply
Supply voltage UVM, UVIO, nominal value 24 V DC
Supply voltage UVM, UVIO, allowed range 20 - 30 V DC
Size and weight
Weight approx. 150 g
Product dimensions (width x height x depth) 24 x 118 x 97 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 2, according to ČSN EN 60664-1 ed.2: 2008 (idt IEC 60664-1: 2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Built-in
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Storage relative humidity Max. 80% without vapor condensation
Storage environment Dry, clean areas without conductive dust, aggressive gases or acid vapors for a period not exceeding the warranty period.
Transport temperatures -25°C to -70°C
Transport environment Covered means of transport, transport packaging must not be exposed to the effects of rain and snow
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis .
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The installation of the TC800 system module is carried out by sliding it perpendicularly onto the DIN rail ČSN EN 50022 with busbar and locking latch in the lower part of the module. A more detailed description and mechanical drawings with dimensions are given in the documentation TXV 004 72.
Connection
Warning All external circuits connected to the module must meet the conditions for SELV circuits!
Connection description The module is equipped with a screwless removable connector with 17 terminals with locking after insertion into the module.
Power connection Via the system bus
Connection of inputs / outputs Connector with screwless terminals 0.2 ~ 1.5 mm2
Module installation tools (-) 2 mm, flat screwdriver
Connection description An example of module connection is shown in the following figure.
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

Files for designers

ZIP

TC800 - library of elements in DXF and DWG formats, v. 2024/01

487.65 kB
KNI

TC800 - element library for SchemataCAD, v. 2024/01

116.21 kB

EC - Declaration of Conformity

PDF

TC800 - CE declaration of conformity (cs)

292.20 kB
PDF

TC800 - CE Declaration of Conformity (en)

709.29 kB

No data available.