C-WS-1804R-TG2-1W-RC-WS-1804R-TG2-1W-R

C-WS-1804R-TG2-1W-R; CIB, Touch control glass, 18 buttons, temperature and humidity sensor, 6xAI / DI, 3xDO, 1x white display, RFID reader

DI max. 8x AI/DI, according to configuration
max. 24 touch buttons, according to configuration
DO max. 4x DO, according to configuration
max. 24x signaling LED R/G/B, according to configuration
AI max. 8x AI see DI, according to configuration
AO
COM 4x CIB slave
SENSOR 1x Temperature
1x Moisture
1x CO2 - according to configuration
1x RFID - according to configuration
Picture Variant Variant description
C-WS-2404R-TG2-0D Number of buttons: 24
Number of displays: No display
C-WS-2404R-TG2-1W Number of buttons: 24
Number of displays: 1x white display
C-WS-2404R-TG2-1B Number of buttons: 24
Number of displays: 1x display blue
C-WS-2404R-TG2-2W Number of buttons: 24
C-WS-2404R-TG2-2B Number of buttons: 24
C-WS-2404R-TG2-3W Number of buttons: 24
C-WS-2404R-TG2-3B Number of buttons: 24
C-WS-2404R-TG2-4W Number of buttons: 24
C-WS-2404R-TG2-4B Number of buttons: 24
C-WS-1804R-TG2-0D-R Number of buttons: 18
Number of displays: No display
Sensor: RFID
C-WS-1804R-TG2-1W-R Number of buttons: 18
Number of displays: 1x white display
Sensor: RFID
C-WS-1804R-TG2-1B-R Number of buttons: 18
Number of displays: 1x display blue
Sensor: RFID
C-WS-1804R-TG2-2W-R Number of buttons: 18
Sensor: RFID
C-WS-1804R-TG2-2B-R Number of buttons: 18
Sensor: RFID
C-WS-1804R-TG2-3W-R Number of buttons: 18
Sensor: RFID
C-WS-1804R-TG2-3B-R Number of buttons: 18
Sensor: RFID
C-WS-1804R-TG2-0D-C Number of buttons: 18
Number of displays: No display
Sensor: CO2
C-WS-1804R-TG2-1W-C Number of buttons: 18
Number of displays: 1x white display
Sensor: CO2
C-WS-1804R-TG2-1B-C Number of buttons: 18
Number of displays: 1x display blue
Sensor: CO2
C-WS-1804R-TG2-2W-C Number of buttons: 18
Sensor: CO2
C-WS-1804R-TG2-2B-C Number of buttons: 18
Sensor: CO2
C-WS-1804R-TG2-3W-C Number of buttons: 18
Sensor: CO2
C-WS-1804R-TG2-3B-C Number of buttons: 18
Sensor: CO2
C-WS-xxx4R-TG2-yy
Wall-mounted glass touch controller with four basic square modules with a final dimension of 307 x 94 mm for installation in multiple instrument boxes for combined frames with a pitch of 71 mm.
This double controller requires 4 addresses and 4 modules on the CIB bus.
It is delivered as a complete set with an individual configuration of each of the four modules, including a cover glass with individual printing of icons, texts and backgrounds. The web configurator at:
https://touchatglass.com/eng/configurator.html
The glass can also be ordered separately as a spare.
Order num. 8020104491
Teco code C-WS-1804R-TG2-1W-R
Categories CFox - Touch@Glass, devices
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 4x CIB slave
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals 2(AI/DI1, AI/DI2)
+2(AI/DI1, AI/DI2)
+2(AI/DI1, AI/DI2)
+2(AI/DI1, AI/DI2)
Number of inputs in group 2
Common wire GND - module ground
Combined input type DI/AI Active, for sensing potential-free contacts and measuring resistance sensors
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals 1x DO for each module with buttons or CO2, 3x DO for module with RFID sensor
Number of transistor outputs 1
Output type MOSFET (Low-side switch)
Switching voltage 27 V DC
Switching current, output load 3 A max.
Short-term output overload capacity 3 A max.
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 1
Number of analog input groups 2
Organization of analog inputs into groups 2x (AI/DI1, AI/DI2) for each module,
max. 8x for the entire controller
Input type AI / DI - combined
AI - Analog Input Ranges (Group A)
Voltage 0-2 V
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-100 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
Temperature measurement error ± 1°C
Parameter des Temperatursensors
Temperature - Measurement range 0°C ÷ 50°C
Temperature - Measurement accuracy typ. ±0,5 °C
Humidity sensor parameters
Relative humidity - Measurement range 0 ÷ 100 %RH
Relative humidity - Measurement accuracy typ. ±2 %RH
Power supply
Supply voltage, tolerances 24 V DC, +25%, -15%, SELV
Maximum power input 0,7 W
Power supply from CIB - typical current consumption (mA) 28 mA
Power supply from CIB - Galvanic separation of power supply from internal circuits No
Internal protection No
Size and weight
Weight approx. 140 g
Product dimensions (width x height x depth) 94 x 94 x 10 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 2, according to ČSN EN 60664-1 ed.2: 2008 (idt IEC 60664-1: 2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Built-in
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 55 ° C
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Storage relative humidity Max. 80% without vapor condensation
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis .
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The module is mounted in a vertical position on the U-rail ČSN EN 50022. Installation of the assembly (basic module and possibly peripheral modules) is performed according to TXV 004 13.
Assembly description 1. screw the mounting frame to the installation box
(pay attention to the orientation)
2. connect the electronics module to the other wiring
3. insert the electronics module into the installation box
4. snap the glass fingerboard onto the mounting frame
Connection
Connection of power and system communication connector with 1.5 mm2 screw terminal
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

No data available.

No data available.

No data available.