OS-8401TXN 184 01

OS-8401; 16x DO, GO, 24 V DC, CP, 0.5 A, transistor

DI
DO 16x DO
AI
AO
COM 1x TCL3
SENSOR
Picture Variant Variant description
OS-8401
The OS-8401 peripheral module contains 16 transistor outputs with a maximum load of 0.5 A per output. The module is galvanically isolated from other PLC circuits.
The module is equipped with a screwless removable connector of 17 terminals with locking after insertion into the module.
The output circuits of the module require a 24 V DC power supply, which is connected (alone or together with the main power supply) to the power supply module of the PLC assembly.
Order num. TXN 184 01
Teco code TXN 184 01
Categories TC800 - I / O expansion modules
Tags -
COM - System buses
TCL3 - system I/O bus 1x TCL3 slave
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals DO0 - DO15
Number of transistor outputs 16
Number of output groups 1
Number of outputs in group 16
Organization of transistor outputs into groups 16x (DO0-DO15)
Common group conductor VDO+
Output type transistor output
Galvanic separation from internal circuits Yes
Diagnostics indication of energized output by LED on module panel
Switching voltage 20 – 30V DC
Minimum voltage of the switched-off output (Vcl) VVDO+ - 47V
Switching current, output load 0.5 A max, up to 4 outputs can be connected in parallel to achieve a higher output current. Outputs combined into 1 signal must always be from the same eight (from group 0-7 or 8-15)
Group current 8 A max.
Switching time 400 μs max.
Opening time 400 μs max.
Residual current 70 μA max.
Short circuit protection Yes
Short-circuit current limitation typ. 1.1 A
Treatment of inductive load internal: 0.6J max (each output)
external - RC element, diode
The module can switch an inductive load without external protection if the energy stored in it does not exceed the specified value. Otherwise, you need to use external protection sized so that when the load is turned off, the voltage at the output does not fall below Vcl, i.e. ‑23V in the case of power supply VVDO+ = +24 V.
Reverse polarity protection Yes - The circuit will be inactive, the loads will be closed, current will flow through the protection diodes of the circuit.
Initial peak current limitation typ. 1.4 A
Power supply
Supply voltage UVM, UVIO, nominal value 24 V DC
Supply voltage UVM, UVIO, allowed range 20 - 30 V DC
IVM supply current at UVM = 24 V 8 mA
Max. power consumption at the VM level 0,2 W
Module thermal/power loss 1,8 W
Galvanic separation of power supply from internal circuits Yes
Galvanic separation of power supply from peripheral circuits No, power to the output circuits from VDO+ is terminated via the system bus and the system power supply module (terminal VIO-).
Size and weight
Weight approx. 85 g
Product dimensions (width x height x depth) 12 x 118 x 97 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 2, according to ČSN EN 60664-1 ed.2: 2008 (idt IEC 60664-1: 2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Built-in
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Storage relative humidity Max. 80% without vapor condensation
Storage environment Dry, clean areas without conductive dust, aggressive gases or acid vapors for a period not exceeding the warranty period.
Transport temperatures -25°C to -70°C
Transport environment Covered means of transport, transport packaging must not be exposed to the effects of rain and snow
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis .
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The installation of the TC800 system module is carried out by sliding it perpendicularly onto the DIN rail ČSN EN 50022 with busbar and locking latch in the lower part of the module. A more detailed description and mechanical drawings with dimensions are given in the documentation TXV 004 72.
Connection
Warning All external circuits connected to the module must meet the conditions for SELV circuits!
Power connection Via system bus + I/O connector
Connection of inputs / outputs Connector with screwless terminals 0.2 ~ 1.5 mm2
Connector coding The connector can be provided with a code to prevent its insertion into another type of module. Modules with connectors are delivered without coding, coding elements can be ordered separately.
Connection description An example of module connection is shown in the following figure.
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Commissioning On the module, the DIP switch in the left part of the case sets a unique address within one frame. The module is fully ready for operation after inserting it into the frame and turning on the power supply.
Module diagnostics The basic diagnostic system of the module is part of its standard software. It has been in operation since the module power was turned on and works independently of the user. Diagnosed error states of the module and connected peripheral modules of the assembly are signaled in the status word of the module and on the module panel
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

OS-8401 - Basic documentation

1.27 MB, (EN)

Files for designers

ZIP

TC800 - library of elements in DXF and DWG formats, v. 2024/01

487.65 kB
KNI

TC800 - element library for SchemataCAD, v. 2024/01

116.21 kB

EC - Declaration of Conformity

PDF

TC800 - CE Declaration of Conformity (en)

709.29 kB
PDF

TC800 - CE declaration of conformity (cs)

292.20 kB
  • Binary output module OS-8401 - The binary output module OS-8401 contains 16 transistor outputs, max. 0.5 A per output. The outputs are organized into one group of 16. The module is galvanically separated from other PLC circuits. The outputs are realized by semiconductor switche...
  • Examples of power connections for TC800 modules - ...ot be connected with an external wire (an unwanted ground loop would occur) The internal circuits of the outputs of the OS-8401 module are powered from the VIO level (terminals A3 and A4 of the PW-8901 module), terminal A1 on the OS-8401 module...
  • TC800 power supply sizing calculation and heat loss - ...nbsp;             OS-8401 TXN 184 01 1 0,2 W 0,0 W 1,8 W 1,8 W OS-...
  • TECOMAT TC800 SYSTEM FEATURES - ...pply modules PW-8901 and PW-8902 Binary input module IB-8302 Binary input module IB-8310 Binary output module OS-8401 Binary output module OS-8402 Binary output module OS-8410 Binary output module OR-8450 TC800 syst...