C-WG-0503STXN 133 53

C-WG-0503S; CIB, 2x AI/DI/EZS, 3x DO (NPN), 1x Wiegand/3x DI(TTL), 12VDC/60mA power supply, for security detectors

DI
DO
AI 2x AI / DI (R, binary, balanced)
AO Power output 12V / 60mA
COM
SENSOR
Picture Variant Variant description
C-WG-0503S
Built-in module C-WG-0503S is designed for connection of devices communicating via Wiegand protocol, or for connection of analog or binary signals to the system via CIB Common Instalation Bus® and for excitation of LEDs, buzzer, etc., outputs with open NPN collectors .
Inputs DI1 to DI3 are designed as 5V TTL with internal pull up resistors. They can be read as binary inputs or evaluate signals from various readers with the Wiegand protocol, such as RFID card readers and the like.
Inputs DI / AI4 and DI / AI5 can be set as binary potential-free or balanced burglar alarm or as analog for temperature or resistance measurement.
The module contains a 12 V DC / 60 mA auxiliary voltage source, which is supplied directly from the CIB bus.
Order num. TXN 133 53
Teco code TXN 133 53
Categories CFox - Built-in modules
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 3
Number of groups of binary inputs 1
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals DI1-DI3
Number of inputs in group 3
Common wire +12V DC
Combined input type TTL 5V
Galvanic isolation of inputs from internal/peripheral circuits No
DO/RO - Organization of binary outputs
Total number of binary outputs 3
Number of binary output groups 1
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals DO1-DO3
Number of transistor outputs 3
Number of output groups 1
Number of outputs in group 3
Organization of transistor outputs into groups 3 (DO1-DO3)
Diagnostics No
Output current 30 mA
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Number of analog input groups 1
Organization of analog inputs into groups 2x (AI1, AI2)
Input type With common clamp
Common wire Minus
Galvanic separation from internal circuits No
Diagnostics overload signaling in status word
Digital resolution 10 bit
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals AI1, AI2
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-160 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Power supply
Power supply from CIB - voltage 24/27 V DC
Auxiliary power supply - voltage Power supply output 12 V DC; 60 mA max.
Power supply from CIB - typical current consumption (mA) 20 mA
Power supply from CIB - maximum current consumption (mA) 85 mA
Size and weight
Weight approx. 7 g
Module width 55 mm
Module height 26 mm
Module depth 15 mm
Product dimensions (width x height x depth) 55 × 26 × 16 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod)
Degree of pollution 1, according to ČSN EN 60664-1: 2004 (mod IEC 60664-1: 1992)
Overvoltage category installation II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992)
Type of device In the installation box, under the cover
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 70 ° C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) 0°C
Operating relative humidity from 10 % up to 95 % without condensation
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission ČSN EN 55022 ed2:2007 (mod CISPR22:2005)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The module C-DM-0001B-SL is mounted in arbitrary positioninto instalation box under a lid or under device located in box.
Connection
Connection of power and system communication Loose wires in the connector / 0.15-0.5 mm2
Connection of inputs / outputs Loose wires in the connector / 0.15-0.5 mm2
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-WG-0503S - Basic documentation

849.34 kB, (EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.