C-ID-0011RTXN 143 05.90
C-ID-0011R; CIB, Touch wall controller, 8 buttons, 128x 64 dot display
DI | |
---|---|
DO | |
AI | 1x AI/DI |
AO | |
COM | 1x CIB slave |
SENSOR | Temperature Humidity Lighting |
Picture | Variant | Variant description |
---|---|---|
C-ID-0011R |
C-ID-0011R; CIB, Touch-Wand-Controller, 5 Tasten, 128 x 64-Punkt-Display
Order num. | TXN 143 05.90 |
---|---|
Teco code | TXN 143 05.90 |
Categories | CFox - C-ID-0011R Series Touch Controllers |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
AI - Organization of analog inputs | |
Total number of analog inputs | 1 |
Input type | AI / DI - combined |
Galvanic separation from internal circuits | No |
AI - Analog Input Ranges (Group A) | |
Voltage | 0-2 V |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-100 kOhm |
Passive sensor | KTY81-121; PTC thermistor (-55 to + 125 °C) |
Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
DI: Voltage-free contact | 0 when> 1.5 kOhm, 1 when <0.5 kOhm |
Parameter des Temperatursensors | |
Temperature - Sensor type | SHT40 |
Temperature - Measurement range | –20 °C ÷ +70 °C |
Temperature - Resolution | 0,1 °C |
Temperature - Measurement accuracy | typ. ±0,5 °C |
Humidity sensor parameters | |
Relative humidity - Sensor type | SHT40 |
Relative humidity - Resolution | 0,1 % RH |
Relative humidity - Measurement accuracy | ±4 % |
Lighting sensor parameters | |
Lighting - Sensor type | KPS-3227SP1C |
Lighting - Measuring range | 250 lx ÷ 1000 lx |
Lighting - Measurement accuracy | > 5% - informative |
Lighting - Measurement error | <5% of range |
Power supply | |
Supply voltage, tolerances | 24 V DC, +25%, -15%, SELV |
Maximum power input | 2 W |
Maximum current consumption (mA) | < 50 mA |
Galvanic separation of power supply from internal circuits | No |
Internal protection | No |
Size and weight | |
Product dimensions (width x height x depth) | 110 x 100 x27 |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes) |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP40 front, IP20 rear |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | On the wall |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Operating temperature maximum (° C) | +70°C |
Operating temperature minimum (° C) | -20°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 ° C to + 85 ° C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.3: 2012 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis . |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description | Indoor wall mounting |
Connection | |
Power connection | Via the system bus |
CIB connection | Push-In terminal 0.3 - 1 mm2 |
Module operation | |
Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-ID-0011R - Basic documentation
354.51 kB, (EN)
- Universal glass controller C-ID-0011R - C-ID-0011R is a universal graphic wall controller with capacitive buttons. It contains a temperature, humidity and light intensity sensor, a universal AI input for connecting other temperature sensors (e.g. floor temperature, outdoor temperature), w...
No data available.