MR-0134, 2x RS-232TXN 101 34
MR-0134, 2x RS232, with its own power supply, galvanic isolation
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 2x RS-232 |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
MR-0134, 2x RS-232 |
MR-0134 is a submodule, which is used to expand the number of serial channels directly in the basic modules of the Foxtrot 2 system, it contains 2x RS-232. The internal connection ensures galvanic separation of the interface from the system and power supply circuits. At the same time, the module contains identification circuits. The user has the ability to identify the type of submodule used from the development environment.
Order num. | TXN 101 34 |
---|---|
Teco code | TXN 101 34 |
Categories | Foxtrot 2 - Accessories for basic modules, TC800 - Positioning and counter modules |
Tags | - |
COM - Serial channels | |
---|---|
Number of internal RS-232 serial channels | 2 |
Max. baud rate (RS-232) | 200 kBd |
Receiver input resistance (RS-232) | min. 7 kOhm |
Signal output level (RS-232) | typ. ±8 V |
Max. length of connected line (RS-232) | 15 m |
Power supply | |
Maximum power input | 1,2 W |
Galvanic separation of power supply from internal circuits | No |
Insulation voltage of galvanic separation | 1 000 VDC |
Size and weight | |
Weight approx. | 25 g |
Product dimensions (width x height x depth) | 15,5 x 42 x 3,5 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Submodule |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating temperature maximum (° C) | +55°C |
Operating temperature minimum (° C) | -20°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Installation | |
Attention! | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to touch the printed circuit boards directly without protective measures. |
Connection | |
Description |
The communication interfaces of the end device where the submodule is put in are equipped typically with a screw connectors. The connection of connectors is mentioned in the manual of this end device. |
Module operation | |
Commissioning |
Submodules with RS-485 have soldering jumpers, that can be used to connect terminating resistor network to the transmission lines. They are labeled „BT1“ for first channel and „BT2“ for second channel. By default, submodules are delivered with these jumpers open. Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures. |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. Notice: Before turning on the system, all conditions of this documentation must be met. The system shall not be put into service unless it has been verified and confirmed that the machinery of which: included Foxtrot system, meets the requirements of Directive 89/392 / CEE if applicable. Documentation changes reserved. |
Warning | All conditions of this documentation must be met before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery of which the Foxtrot system is a part complies with the requirements of Directive 89/392 / EEC, in so far as it applies to them. Documentation subject to change. |
EC - Declaration of Conformity
Foxtrot 2 - EC Declaration of conformity (en)
590.59 kB, (EN, RU, DE, UA)
HW documentation
MR-0134 - Basic documentation
559.63 kB, (EN)
- Submodules MR-0130 - MR-0134 - serial channels - ...2x UART interface RS-485 galvanically isolated TXN 101 33 MR-0134 2x UART interface RS-232 galvanically isolated TXN 101 34...
- Communication interface submodule connector on the CP-8001 module - ...ally act as additional peripheral modules connected directly to the fast internal bus of the base module. Modules MR-0130 to MR-0134 complement the serial communication channels on the basic module CP-8001. Optional submodules to the bas...
No data available.