C-RS-0200R-LOGUS, ivory, TMFTXN 133 79.LTMF

C-RS-0200R-LOGUS ivory; CIB, device rotary knob + button, temperature sensor, 2x AI

DI 2x AI/DI
1x Button
DO
AI 2x AI / DI see DI
AO
COM 1x CIB slave
SENSOR Rotary bidirectional incremental encoder
C-RS-0200R is a rotary knob with the function of a confirmation button with connection to the CIB Common Installation Bus®, to which 2 external temperature sensors or 2 contacts can be connected.
Order num. TXN 133 79.LTMF
Teco code TXN 133 79.LTMF
Categories CFox - LOGUS, Covers and devices
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Parameters of binary inputs DC (group A)
Number of inputs in group 2
Common wire GND - module ground
Combined input type DI/AI Active, for sensing potential-free contacts and measuring resistance sensors
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals AI0/DI0, AI1/DI1
Voltage 0-2 V
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-100 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact 0 when> 1.5 kOhm, 1 when <0.5 kOhm
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Power supply from CIB - voltage 24/27 V DC
Typical power input 0,2 W
Maximum power input 0,3 W
Power supply from CIB - typical current consumption (mA) 8 mA
Power supply from CIB - maximum current consumption (mA) 13 mA
Power supply from CIB - internal protection No
Size and weight
Weight approx. 75 g
Product dimensions (width x height x depth) 70 × 70 × 25 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP40 front, IP20 rear
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Type of device In the installation box on the wall
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -10°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.3: 2012
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Installation
Assembly description The module is mounted in a vertical position on a standard installation box with a spacing of fixing screws of 60 mm.

Method:
  1.      connect the wires to the next wiring
  2.      screw the driver module to the installation box (pay attention to the position)
  3.      assemble the covers as shown in the following figure and secure with a clip
  4.      slide in the rotary fingerboard
Connection
Connection description The controller module with rotary control with the possibility of connecting external sensors is implemented as a standard unit on a two-wire CIB bus, which ensures communication and power supply of the entire module. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the FOXTROT basic unit with the internal module CF-1140 or the external module CF-1141, with version FW 1.8 and higher. Further information can be found in the manual “Peripheral modules on the CIB bus” TXV 004 13.
Connection of power and system communication Loose wires in the connector / 0.15-0.5 mm2
Connection of inputs / outputs Loose wires in the connector / 0.15-0.5 mm2
Cross-section of connected wires fixed (max) 0,5 mm2
Module operation
Module configuration SW configuration, operation and diagnostics of the C-RS-0200R-ABB module are performed from the MOSAIC programming environment. The module is ready for operation after connecting the CIB supply voltage. The HW address of the respective module is indicated on the type plate on the board.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-RS-0200R - Basic documentation

128.96 kB

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • C-RS-0200R - ...00-270xx (Variant and Elegant). The frame in the selected design and colour. The body proper of the C-RS-0200R-Logus or C-RS-0200R-Obzor module.   Mounting of the module: Screw the C-RS-0200R-Logus...
  • A rotary controller on the CIB, the C-RS-0200R - The C-RS-0200R-Logus is a rotary interior controller with the function of one button with a connection to the CIB. At the same time it is fitted with two universal inputs terminated in the terminal block on the rear side of the module, e.g. f...

No data available.