C-RQ-0400I-10 (cable)TXN 133 62.04
C-RQ-0400I-10; CIB, temperature and humidity sensor, 2x AI / DI, IP54, 1,0m cable
DI | 2x AI/DI |
---|---|
DO | |
AI | 2x AI / DI see DI |
AO | |
COM | 1x CIB slave |
SENSOR | 1x Temperature 1x Relative humidity |
Picture | Variant | Variant description |
---|---|---|
C-RQ-0400I (on the wall) | Designed for: On the wall | |
C-RQ-0400H-P-180 | Designed for: To the ventilation duct | |
C-RQ-0400H-P-240 | Designed for: To the ventilation duct | |
C-RQ-0400I-10 (cable) | Designed for: On the cable |
Relative humidity and temperature measurement module. It connects a relative humidity and temperature sensor to the CIB bus (the design of the sensor is determined by the part number). It also allows you to connect two universal inputs that can be used separately as binary or analog.
The module is designed for measuring relative humidity and air temperature without aggressive additives
The module is designed for measuring relative humidity and air temperature without aggressive additives
- indoors,
- exteriors
- and in ventilation ducts.
Order num. | TXN 133 62.04 |
---|---|
Teco code | TXN 133 62.04 |
Categories | CFox - Outdoor modules, IP54 / 65 |
Tags | - |
AI - Analog Input Ranges (Group A) | |
---|---|
Passive sensor | Pt1000, W100 = 1,385 (-90 to +400 ° C) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Passive sensor | Ni1000, W100 = 1,500 (–60 to +200 ° C) |
Passive sensor | Ni1000, W100 = 1.617 (-60 to +200 ° C) |
Passive sensor | Resistance transmitter 0-160 kOhm |
Passive sensor | KTY81-121; PTC thermistor (-55 to + 125 °C) |
Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
DI: Voltage-free contact | 0 when> 1.5 kOhm, 1 when <0.5 kOhm |
DI: Balanced resistance input | 2x 1k1 (tamper/0/1/tamper) |
Resistance measurement error - maximum error at 25 ° C | ± 0.5% of full scale |
Parameter des Temperatursensors | |
Temperature - Measurement range | –40 °C ÷ +125 °C |
Temperature - Resolution | 0,1 °C |
Temperature - Measurement accuracy | typ. ±0,3 °C |
Humidity sensor parameters | |
Relative humidity - Measurement range | 0 ÷ 100 %RH |
Relative humidity - Resolution | 1 % RH |
Relative humidity - Measurement accuracy | typ. ±2 %RH |
Power supply | |
Power supply from CIB - voltage | 24/27 V DC |
Power supply from CIB - maximum current consumption (mA) | 12 mA |
Power supply from CIB - internal protection | Yes, returnable fuse |
Size and weight | |
Weight approx. | 200 g |
Product dimensions (width x height x depth) | See pictures |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP54 |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Outdoor |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | Модуль упакован в антистатический пакет. Эта документация также является частью пакета. Внешняя упаковка осуществляется в соответствии с объемом заказа и способом транспортировки в транспортной упаковке, снабженной этикетками и другими данными, необходимыми для транспортировки. Продукт не должен подвергаться воздействию прямых погодных условий во время транспортировки и хранения. Соложение продукта разрешено только в чистых помещениях. без токопроводящей пыли, агрессивных газов и паров. Наиболее подходящая температура хранения - 20 ° C. |
Installation | |
Assembly description | Individual module variants can be mounted in any position. The dimensions and location of the mounting holes are shown in the following figures. The TXN 133 62.01 and .04 modules are mounted on a level surface. Mounting holes are accessible after removing the box lid. The TXN 133 62.02 and .03 modules are mounted in air ducts, and a plastic sleeve is supplied with them for easier mounting. |
Connection | |
Connection description | The relative humidity and temperature sensor is located in the unscrewable plastic end of the pipe (in variants TXN 133 62.01 to .03), where it is protected by a dust filter, or in a non-removable plastic block (variant TXN 133 62.04) at the end of the cable with a filter preventing the ingress of solid particles. larger than 0.1 μm. |
Connection of power and system communication | terminal block with spring terminal 1.5 mm2, push-in |
Connection of inputs / outputs | terminal block with spring terminal 1.5 mm2, push-in |
Module installation tools | (-) 3 mm, flat screwdriver |
Module operation | |
Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-RQ-0400I - Basic documentation
599.58 kB
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- C-RQ-0400I-xx - ...The sensor for measuring humidity in an environment with the risk of water flowing down, condensation of humidity, etc., the C-RQ-0400I-05 (05 - the cable length 0.5 m) consists of a box (like the C-RQ-0400I sensor) and an external sensor, which is l...
- C-RQ-0400I - Measuring outdoor relative humidity and temperature can be done using the C-RQ-0400I sensor. The actual temperature and humidity sensor is located in a plastic ABS stem, which is terminated with a dust filter. The electronic component, including...
- Measuring outdoor relative humidity and temperature , CFox module C-RQ-0400I - Measurement of outdoor humidity and temperature can be done by the C-RQ-0400I sensor. The module is also equipped with two universal inputs allowing connection of e.g. an additional temperature sensor, a button (for digital input), etc....
- The spring terminal blocks "Push In" 5.08 mm - The terminal blocks used e.g. by the modules with a higher protection - the C-RQ-0400I , and some other peripheral modules, are screwless (with springs) fixed terminals with a 5mm spacing and the Push-In technology. The technology allows inserti...
- C-RQ-0400H-P - ...rature and humidity sensor, especially with regard to adverse climatic conditions, are listed in the section describing the C-RQ-0400I module. Mounting and connecting the sensor The sensor should be mounted using a holder (on the r...
- Measurement of outdoor relative humidity and temperature with a detached sensor - Measuring humidity in the environment with the risk of flowing water, condensation, etc., can be done by the C-RQ-0400I-xx sensor (xx - the cable length in dm), with the sensor mounted on the cable of the given length (max. 2m). The sensor c...
- Measuring outdoor temperature - ...ture can also be measured with a combined sensor with the outdoor lighting level C-RI-0401I , or with the relative humidity C-RQ-0400I....
No data available.