C-RI-0401ITXN 133 47.92
C-RI-0401I; CIB, Temperature, Light intensity - outdoor version, IP54
DI | |
---|---|
DO | |
AI | |
AO | |
COM | |
SENSOR | Lighting Temperature |
Picture | Variant | Variant description |
---|---|---|
C-RI-0401I |
C-RI-0401I is a combined
- temperature
- lighting
sensor on the CIB bus.
The module is in a plastic design with a cable gland and an increased degree of protection, designed for installation in an outdoor environment on a vertical support surface.
- temperature
- lighting
sensor on the CIB bus.
The module is in a plastic design with a cable gland and an increased degree of protection, designed for installation in an outdoor environment on a vertical support surface.
Order num. | TXN 133 47.92 |
---|---|
Teco code | TXN 133 47.92 |
Categories | CFox - Outdoor modules, IP54 / 65 |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
Parameter des Temperatursensors | |
Temperature - Sensor type | Pt1000 |
Temperature - Measurement range | -90°C ÷ 320°C |
Temperature - Measurement error | <2% of range |
Temperature - Conversion time | 500 μs |
Lighting sensor parameters | |
Lighting - Sensor type | Photodiode BPW21 |
Lighting - Measuring range | 0 lx ÷ 50000 lx |
Lighting - Measurement error | <5% of range |
Lighting - Temperature coefficient | ± 0.1% of full scale / ° C |
Lighting - Linearity of measurements | ± 0.2% of full scale |
Lighting - Repeatability under steady state conditions | 0.5% of full scale |
Power supply | |
Supply voltage, tolerances | 24/27 V DC from CIB bus |
Maximum power input | < 0,5 W |
Power supply from CIB - maximum current consumption (mA) | 25 mA |
Power supply from CIB - internal protection | No |
Size and weight | |
Weight approx. | 150 g |
Product dimensions (width x height x depth) | 74 × 125 × 39 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | II, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP54 |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Outdoor |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -10 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55022: 1999 (mod CISPR22: 1997) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description | The C-RI-0401I module is mounted in a vertical position on the support surface with the cable gland facing downwards. We recommend a place protected from direct sunlight, the sensor is not intended for measuring direct sunlight. Installation of the assembly (basic module and possibly peripheral modules) is performed according to TXV 004 13. |
Connection | |
Connection description |
The combined module is implemented as a CIB bus module, which provides communication and power supply to the module. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the FOXTROT base unit or module, for example CF-1141. Further information can be found in the manual Peripheral modules on the CIB TXV 004 13. |
Connection of power and system communication | 2 wire cable 4.5 - 7mm, PG9 bushing |
Module connection |
Description of signals red (yellow) wire + CIB black (green) wire - CIB |
Module operation | |
Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-RI-0401I
89.10 kB, (CS, EN)
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- Measuring the intensity of outdoor lighting - ...ction is enabled by the output of the C-RI-0401S module with a terminal block. Fig. 1. A view the C-RI-0401I module (on the left is the module itself with the temperature sensor and a gland for the CIB cable, on the right i...
- Measuring the lighting - ...r lighting and indoor illumination is measured by the C-RI-0401S module, or its variants, e.g. the C-RI-0401R-design, or the C-RI-0401I....
- Measuring outdoor temperature - ...ble measuring range. The outdoor temperature can also be measured with a combined sensor with the outdoor lighting level C-RI-0401I , or with the relative humidity C-RQ-0400I....