C-RI-0401ITXN 133 47.92

C-RI-0401I; CIB, Temperature, Light intensity - outdoor version, IP54

DI
DO
AI
AO
COM
SENSOR Lighting
Temperature
Picture Variant Variant description
C-RI-0401I
C-RI-0401I is a combined
- temperature
- lighting
sensor on the CIB bus.

The module is in a plastic design with a cable gland and an increased degree of protection, designed for installation in an outdoor environment on a vertical support surface.
Order num. TXN 133 47.92
Teco code TXN 133 47.92
Categories CFox - Outdoor modules, IP54 / 65
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
Parameter des Temperatursensors
Temperature - Sensor type Pt1000
Temperature - Measurement range -90°C ÷ 320°C
Temperature - Measurement error <2% of range
Temperature - Conversion time 500 μs
Lighting sensor parameters
Lighting - Sensor type Photodiode BPW21
Lighting - Measuring range 0 lx ÷ 50000 lx
Lighting - Measurement error <5% of range
Lighting - Temperature coefficient ± 0.1% of full scale / ° C
Lighting - Linearity of measurements ± 0.2% of full scale
Lighting - Repeatability under steady state conditions 0.5% of full scale
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Maximum power input < 0,5 W
Power supply from CIB - maximum current consumption (mA) 25 mA
Power supply from CIB - internal protection No
Size and weight
Weight approx. 150 g
Product dimensions (width x height x depth) 74 × 125 × 39 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object II, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP54
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Outdoor
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -10 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55022: 1999 (mod CISPR22: 1997)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The C-RI-0401I module is mounted in a vertical position on the support surface with the cable gland facing downwards. We recommend a place protected from direct sunlight, the sensor is not intended for measuring direct sunlight. Installation of the assembly (basic module and possibly peripheral modules) is performed according to TXV 004 13.
Connection
Connection description The combined module is implemented as a CIB bus module, which provides communication and power supply to the module. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the FOXTROT base unit or module, for example CF-1141.
Further information can be found in the manual Peripheral modules on the CIB TXV 004 13.
Connection of power and system communication 2 wire cable 4.5 - 7mm, PG9 bushing
Module connection Description of signals

red (yellow) wire            + CIB
black (green) wire          - CIB
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-RI-0401I

89.10 kB, (CS, EN)

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)
  • Measuring the intensity of outdoor lighting - ...ction is enabled by the output of the C-RI-0401S module with a terminal block.   Fig. 1. A view the C-RI-0401I module (on the left is the module itself with the temperature sensor and a gland for the CIB cable, on the right i...
  • Measuring the lighting - ...r lighting and indoor illumination is measured by the C-RI-0401S module, or its variants, e.g. the C-RI-0401R-design, or the C-RI-0401I....
  • Measuring outdoor temperature - ...ble measuring range. The outdoor temperature can also be measured with a combined sensor with the outdoor lighting level C-RI-0401I , or with the relative humidity C-RQ-0400I....

No data available.