TXN 133 16.11TXN 133 16.11
C-IT-0100H-P; CIB 1x outdoor temperature sensor -30 ° C to + 80 ° C, in plastic head, IP-65
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 1x CIB |
SENSOR | 1x Temperature in the stem 1x Internal temperature in the head |
Picture | Variant | Variant description |
---|---|---|
C-IT-0100H-P (120 mm) | ||
C-IT-0100H-P (180 mm) | ||
C-IT-0100H-P (240 mm) | ||
C-IT-0100H-P (300 mm) | ||
C-IT-0100H-P (360 mm) | ||
TXN 133 16.11 | ||
C-IT-0100H-P (attached) |
The C-IT-0100H-P module is a temperature sensor -50 ° C to + 250 ° C with IP65 protection, which can be connected directly to the CIB wiring bus.
- The main Pt1000 temperature sensor is in the stem.
- The information sensor measures the temperature inside the head.
- The resistance is measured and converted directly in the module to a numerical temperature value.
- The values are communicated to the basic module via the CIB Common Installation Bus®.
- The module thus eliminates measurement errors when connecting external sensors over long distances to common analog inputs.
Order num. | TXN 133 16.11 |
---|---|
Teco code | TXN 133 16.11 |
Categories | CFox - Outdoor modules, IP54 / 65 |
Tags | - |
COM - System buses | |
---|---|
CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
Parameter des Temperatursensors | |
Temperature - Description of measurements |
AI1 - Pt1000 temperature sensor in the stem for primary temperature measurement in the range -50 to + 200 ° C - Resolution 0.1 ° C - Measurement accuracy 0.5 °C AI2 - temperature measurement inside the head for information on operating conditions of the module (-25 to + 80 ° C). The temperature stabilization time is about 30 minutes |
Temperature - Sensor type | Pt1000 |
Temperature - Measurement range | –50 °C ÷ + 200 °C |
Temperature - Resolution | 0,1 °C |
Temperature - Measurement accuracy | typ. ±0,5 °C |
Temperature - Settling time | 30 min. |
Power supply | |
Power supply from CIB - voltage | 24/27 V DC |
Typical power input | 0,2 W |
Maximum power input | 0,3 W |
Power supply from CIB - maximum current consumption (mA) | 12 mA |
Power supply from CIB - Galvanic separation of power supply from internal circuits | No |
Power supply from CIB - internal protection | No |
Size and weight | |
Weight approx. | 150 g |
Product dimensions (width x height x depth) | max. 90 x 66 x 155 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2: 2005 (idt IEC61131-2: 2003) - Programmable control units |
Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP65 |
Operating areas | Normal, according to ČSN 33 2000-3: 1995 (mod IEC 364-3: 1993) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992) |
Type of device | On the wall, in the pit, in the air conditioning, attached |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | –25 °C o +80 °C |
Operating temperature maximum (° C) | +80°C |
Operating temperature minimum (° C) | -25°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55022: 1999 (mod CISPR22: 1997) |
Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description |
The sensor module is mounted in any position using a mounting fitting. The actual temperature sensor, which is located at the end of the stem, should be located so that it is maximally exposed to the measured medium. As a rule, the installation is performed perpendicularly or at an angle of 45 ° to the flow direction of the measured medium. The sensor stem can also be placed in a well, which in undesirable cases protects the sensor from the direct influence of the medium. When mounting and positioning the sensor, it is necessary to ensure that the operating conditions of the head are observed during the subsequent operation of the module. During operation, heat is also transferred along the stainless steel stem of the sensor, so it is necessary to ensure that the temperature is at The stem-head transition did not exceed the permitted head operating temperature. |
Connection | |
Connection description |
Sensors with a converter are implemented as standard units on a two-wire CIB bus, which ensures communication and power supply of the entire sensor. The bus wires are connected via a bushing on the terminal board, which is accessible after removing the head cover. Signaling After removing the head cover, it is possible to monitor the status of the module using the indicator LED. If the green indicator LED is lit, the module is connected to the CIB bus. In this case, however, there is no data exchange between the module and the TECOMAT FOXTROT PLC. If the indicator LED flashes, communication between the module and the PLC is faultless. |
Connection of power and system communication | terminal block with spring terminal 1.5 mm2, push-in |
Module operation | |
Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
C-IT-0100H-P- basic documentation
102.14 kB
User manuals
Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02
13.94 MB, (EN, RU, DE, UA)
Scheme
C-IT-0100H-P - electrical wiring diagram
23.38 kB
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- The outdoor temperature sensor CFox, C-IT-0100H-P - The outdoor temperature sensor on the CIB bus, the C-IT-P-0100, order number TXN 133 16.11, is designed for mounting on the wall. The module is placed in a box with extra protection, with a cable gland. The dimensions and other details are provid...
- C-IT-0100H-P - The C-IT-0100H-P module is a temperature sensor in a plastic head, which can be connected directly to the CIB bus. The module contains two measurement inputs. One input (the master) is permanently connected to the resistance temperature sensor in th...
- Air temperature measurement in the duct, sensor with CFox stem, C-IT-0100H-P - ...ducts and ventilation devices, is measured by a temperature sensor with a stem installed in the duct, we have a CFox module C-IT-0100H-P available, order no. TXN 133 16.0x (x - stem length). The module is placed in a plastic head with a termin...
- Measuring the temperature of water in the piping, the CFox, C-IT-0100H-P sensor with an imme - ...red by a temperature sensor with a stem in a stainless steel sleeve fitted in the piping; there is available the CFox module C-IT-0100H-P, the Order No. is TXN 133 16.0x (x - the stem length), and it is necessary to additionally order the appropriate...
- Measuring the temperature of water in the piping, the CFox C-IT-0100H-P contact sensor - ...emperature of water in the solar system, etc.) is measured by contact temperature sensors; the available CFox module is the C-IT-0100H-P , the Order No. is TXN 133 16.12. The module is designed to measure the surface temperature of piping. It is pla...
- Basic information about temperature sensors - ...sensor (except for the Time), it must be specified Outdoor temperature C-IT-0100H-P TXN 133 16.11 P11PA Sensor on th...
- Measuring the temperature of water in the piping, the CFox, C-IT-0100H-A sensor with an imme - ...emperature (the operating temperature of the head itself) at max. 80 °C. Fig. 1. An example of wiring the C-IT-0100H-P sensor Measurement range -30 ÷ +250 º...
- Measuring temperature – technology - ...peratures is listed in Table 10.1. Using directly the sensors on the CIB bus is another option. The C-IT-0100H-P variants: with the stem in the piping, with the immersion sleeve, the contact version on the piping and the out...
- The outdoor temperature sensors Pt1000, P11PA - ...side wall mount TXP 300 01 - the dimensions for wall mounting (for the P11PA sensor it is included in the delivery, for the C-IT-0100h-P sensor, order number 133 16.11 TXN it must be ordered separately....
- Measuring outdoor temperature - Various sensors and their design suitable for measuring the outdoor temperature. Sensors on the CIB bus, C-IT-0100H-P , can be used directly to measure the outdoor temperature. It is also possible to use directly a temperature sensor (Ni1...
- Air temperature measurement in HVAC ducts, sensor with Pt1000 stem, P12PA - The temperature of flowing air and other gaseous media, eg in ventilation ducts and ventilation devices, is measured by a temperature sensor with a stem mounted in the duct, we have an attached sensor equipped with a Pt1000 sensor, P12PA-length, whi...
- solar water heating - Solar thermal systems for heating water can be easily controlled directly by the Foxtrot system. No autonomous regulation is necessary; you can use directly the temperature sensors (collector, tank) connected to the analogue inputs of the Foxtrot sy...
No data available.