CP-2091.11NDNNTXN 120 91.11NDNN

CP-2091; CPU, 2xETH100/10, 128kB dbox, LCD, 1x RS-485, 1xCIB, CH1-4, 8xAI/DI, 2xAI/DI/AO, 1x DI(230VAC), 2xAO/DO (PWM), 3xDO (PWM), 6xRO, 24VDC/230VAC

DI 6x DI/AI (HSC)
2x DI/AI
2x DI/AI/AO
1x DI (230 V AC)
DO 6x RO
3x DO (PWM)
2x DO/AO (PWM)
AI 6 AI/DI (HSC) see DI
2x AI/DI see DI
2x AI/DI/AO see AO
AO 2x DO/AO see DO
2x DI/AI/AO see DI
COM 2x ETH
4x CH1-4, slot for 2x submodule
1x RS-485 master
1x USB device
1x USB host
1x CIB master
SENSOR
Picture Variant Variant description
CP-2091.11NDNN Databox: 128 kB
Processor: 1 core, ARMv7 792 MHz
Display: OLED display large 55 x 13 mm
Basic modules CP-2091 are from the assortment of basic modules (ZM) of modular programmable automata of the Foxtrot 2 series.
    Basic modules CP-2091,
- 8x multi-purpose inputs, each of which can be used either as an analog input or as a binary potential-free contact,
- 2x multi-purpose binary outputs (24V DC) / analog outputs (0-10V)
- one binary input 230 V AC,
- 3x binary outputs 24 V 0.5 A with optional PWM function
- 3x separate relay outputs 230 V AC/5A.
- 3x separate relay outputs 230 V AC/16A


The following interfaces are also available:
2x Ethernet,
up to 4x serial channels
1x master CIB installation bus for connecting external peripherals
2x master system buses TCL2 (SE-0140) intended for connecting expansion I/O modules that increase the total number of I/O


The CP-2091 basic module contains a basic LCD display with 4 x 20 characters and 6 user buttons.
Order num. TXN 120 91.11NDNN
Teco code TXN 120 91.11NDNN
Categories Foxtrot 2 - Basic modules
Tags -
System parameters of the central unit
Row of central unit I
User program memory 1 MB
Memory for user variables / including RETAIN variables 320 kB/48 kB
Instruction length 4 Byte
Backup of program source code in PLC Yes, optional in Mosaic
On-line program change in PLC Yes, including I / O configuration change
DataBox - additional internal data memory 128/257 kB, optional
Memory for I / O data 64 KB / 64 KB
File system - Internal Drive in PLC 128 MB, journaling file system
File system - RAM disk PLC 16 MB
File System - USB Flash Drive Supported
File system - Micro SD card supported (except for variants with WLAN1)
Optional memory card slot microSD - Card Slot (<= 1TB)
Cycle time per 1k of logic instructions 0,036 ms
Cycle time for 1k integer operations 0,044 ms
Cycle time for 1k floating point operations 0,043 ms
Development environment Mosaic v2018.2 or higher
Programming languages ST, IL, LD, FBD, SFC, CFC
RTC - Real time circuit Yes
RTC - Backup time typ. 500 hours
Integrated Web server Yes
Integrated Datalogger Yes
Access to PLC variables via web API Yes
COM - Communication - IP/Ethernet
Ethernet 10/100 Mb (ETHx) 2
WLAN2 (external via USB host, optional) 1
LTE interface (LTEx, optional) 1
Available system modes on ETH and WLAN UNI
   data exchange via UDP, TCP and SSL / TLS encryption support;
PC
   EPSNET UDP / EPSNET TCP;
PLC
   data sharing between PLCs (including CP-1xxx and CP-7xxx);
PLD
   data sharing between PLC CP-2xxx and CP-8xxx including encryption
Available system modes on LTE UNI
   data exchange via UDP, TCP and SSL / TLS encryption support;
   EPSNET UDP / EPSNET TCP
TCP / IP protocol Yes
UDP protocol Yes
HTTPS protocol Yes
HTTP protocol Yes
WebSocket protocol Yes
Protocol MODBUS/TCP Yes
SMTP protocol Yes
IEC 60870-5-104 protocol Yes
REST API Yes
COM - USB
USB devices interface 1x micro-USB
USB host interface 1x USB-A
Available system modes on USB PC
COM - Serial channels
max. number of serial channels that can be serviced at one time 10
max. number of internal serial channels 1
max. number of optional serial channels in the basic module 4
number of slots for optional submodules with interface (MR-013x) 2
max. number of expanding serial channels on the TCL2 bus 6 times on each TCL2 line
COM - Internal serial channels
Number of internal serial channels 1x RS-485
Available system modes on the internal serial channel UNI
    general channel with any asynchronous communication
PC
    communication with superior systems via EPSNET protocol
MAS
    communication with EPSNET subordinate systems
Available communication speeds of system modes 1200 Bd, 2400 Bd, 4800 Bd, 9600 Bd, 14 400 Bd, 19 200 Bd, 28 800 Bd, 38 400 Bd, 57 600 Bd, 76 800 Bd, 115 200 Bd, 172 800 Bd, 230 400 Bd, 345 600 Bd
Galvanic separation of the internal serial channel No
Receiver sensitivity min. ±200 mV
Signal output level typ. 3 V
Max. length of connected line 1200 m
Note on cable length The maximum length applies to twisted and shielded cable and communication speed max. 120 kBd.
COM - Submodules with serial channels and optional interface
Number of slots for submodules with optional interface (MR-013x) 2
RS-232 serial channel on submodules 1x on MR-0130, 2x on MR-0134
Available communication speeds of modes on the RS-232 interface 1200 Bd, 2400 Bd, 4800 Bd, 9600 Bd, 14 400 Bd, 19 200 Bd, 28 800 Bd, 38 400 Bd, 57 600 Bd, 76 800 Bd, 115 200 Bd, 172 800 Bd
RS-485 serial channel on submodules 1x on MR-0131, 2x on MR-0133
Available communication speeds of modes on the RS-485 interface 1200 Bd, 2400 Bd, 4800 Bd, 9600 Bd, 14 400 Bd, 19 200 Bd, 28 800 Bd, 38 400 Bd, 57 600 Bd, 76 800 Bd, 115 200 Bd, 172 800 Bd, 230 400 Bd, 345 600 Bd
Available system modes on submodules MR-0130..MR-0134 UNI, PC, MAS
Profibus DP serial channel on submodules 1x on MR-0135
Available communication speeds of the PFB system mode 9600 Bd, 19 200 Bd, 93 750 Bd, 187 500 Bd
Profibus DP master protocol (<180 kbit/s) PFB - Profibus DP Master (<180 kbit / s)
COM - Expansion communication modules on the TCL2 bus
RS-232 serial channel on modules 1x on SC-1101 (either RS-232 or RS-485)
RS-485 serial channel on modules 1x on SC-1101 (either RS-485 or RS-232)
Wireless M-Bus wireless communication channel on modules 1x on SC-1112.T
RFox2 wireless communication channel on modules 1x on SC-1111
Available communication modes on modules SC-1101, SC-1111, SC-1112 UNI - universal
Modbus RTU / ASCII master / slave protocol available on mode modules UNI - Universal
CAN serial channel on modules 1x on SC-1102
Available communication modes on SC-1102 modules CSJ - CAN bus connection
OpenTherm communication channel on modules 1x on UC-12044
MP-Bus communication channel on the modules 1x on UC-1203
COM - Expansion communication modules on the CIB bus - Common Installation Bus (R)
RFox2 wireless communication channel on modules 1x to C-RF-0001M-A; 1x RFox2 master, max. 10 addresses
DALI Communication interface on modules 1x and C-DL-0064M; 1x Master for 64 addresses
Wiegand communication interface on modules 1x on C-WG-0503S; 1x Master, formats 42 bits, 34bits, 26 bits, 40bits transparent
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB master (100 mA)
CIB - Address range of one branch of the installation bus 32 CFox I/O modules
ITCL - internal system bus Yes
ITCL - number of exchangeable submodules 2
ETCL - external system bus 1 (ETH1 or ETH2)
DI - Organization of binary inputs
Total number of binary inputs 11
Number of groups of binary inputs 2
Organization of binary inputs into groups 4x DI/AI (DI0/AI0-DI7/AI7)
6x DI/AI (HSC) (DI0/AI0-DI5/AI5)
2x DI/AI/AO (DI8/AI8/AO0-DI9/AI9/AO1)
1x DI 230 V AC (DI10)
 
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals DI0-DI9
Number of inputs in group 10
Common wire minus
Input type active (for dry contacts connection)
Combined input type DI/AI Active, for sensing potential-free contacts and measuring resistance sensors
Galvanic isolation of inputs from internal/peripheral circuits No
Diagnostics indication of energized input by LED on module panel
Pulse input overload capacity max. 30 V (t < 10 ms)
Input voltage for log. 0 +3 V DC min.
Input voltage for log. 1 1 V DC max.
Input current at log. 1 (typ.) -1 mA
Delay from log. 0 to log. 1 500 μs
Delay from log. 1 to log. 0 500 μs
The minimum width of the captured pulse 500 μs
DI - Parameters of binary AC inputs
Parameters valid for AC inputs on the terminals DI10
Total number of binary AC inputs 1
Number of groups of AC inputs 1
Number of AC inputs in group 1
Organization of binary inputs into groups 1x DI  (DI10)
Diagnostics Alarm of excited input on the panel
Input type conventional switch
Galvanic isolation of internal circuits Yes
Insulation voltage 3750 V AC
Input voltage for log. 0 0 v AC min., 50 V AC max.
Input voltage for log. 1 230 V AC typ. 95 V AC min., 260 V AC max.
Input current at log. 1 (typ.) 5 mA typ.
Delay from log. 0 to log. 1 max. 20 ms
Delay from log. 1 to log. 0 max. 20 ms
HSC - Counter input parameters
The parameters are valid for inputs DI0-DI5
Special input functions one-way counter
Counter: Input frequency / resolution 1 kHz
Pulse width min. 500 μs
Delay from log. 0 per log. 1 500 μs
Delay from log. 1 per log. 0 500 μs
Range of registers up to 32 bits, 0 to 4 294 967 296
HSC - PWM input parameters
Frequency range 10 Hz - 1 kHz
PWM input error <1% (at 1 kHz)
Input resolution 10,4 μs (DI0), 0,2 μs (DI1)
DO/RO - Organization of binary outputs
Total number of binary outputs 11
Number of binary output groups 4
Organization of binary outputs into groups 6x RO (DO3-DO5, DO6-DO8
3x DO (PWM) (DO0-DO2)
2x DO/AO (DO9/AO2 - DO10/AO3)
DO - Parameters of binary transistor outputs (group A)
Parameters valid for the terminals DO0-DO2, DO9-DO10
Number of transistor outputs 5
Number of output groups 2
Number of outputs in group 5
Organization of transistor outputs into groups 3x DO (DO0-DO2) + 2x DO (DO9-DO10)
Common group conductor minus
Output type MOSFET (Low-side switch)
Galvanic separation from internal circuits No
Diagnostics indication of energized output by LED on module panel
Switching voltage 5 - 30 V DC
Switching current, output load 0,5 A max.
Short-term output overload capacity 3 A max.
Output resistance typ. 0,16 Ω, max. 0,4 Ω
Switching time typ. 9 μs
Opening time typ. 13 μs
Internal protection overvoltage, short circuit and overheating protection
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminals DO3-DO5
Number of relay outputs 3
Number of output groups 1
Number of outputs in group 3
Organization of relay outputs into groups 3x RO (DO3-DO5)
Output type electromechanical relay, unprotected output
Contact type NO - Normally Open
Galvanic separation from internal circuits Yes
Diagnose Alarm signaling on panel module
Switching current 3 A max., 100 mA min.
Switching voltage 250 V AC max., 5 V AC min., 30V DC max.
Switching power 1250 VA max. for AC, 90 W max. for DC
Short-term output overload - inrush 4 A max.
Current through common clamp 10 A max.
Contact closing time typ. 10 ms
Contact opening time typ. 4 ms
Limit values of switched resistive load max. 3A at 30 V DC or 230 V AC
Switching inductive load limits DC13 max. 3 A at 30 V DC
Switching inductive load limits AC15 max. 3 A at 230 V AC
Switching frequency without load max. 300 switching / min.
Switching frequency with rated load max. 20 switching / min.
Mechanical life min. 5,000,000 cycles
Electrical life at maximum resistive load min. 100,000 cycles
Electrical life at maximum load inductive DC13 min. 100,000 cycles
Electrical life at maximum load inductive AC15 min. 100,000 cycles
Short-circuit protection No
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 3750 V AC
Isolation voltage between groups of outputs to each other 3750 V AC
RO - Parameters of binary relay outputs (group B)
Parameters valid for the terminals DO6-DO8
Number of relay outputs 3
Number of output groups 3
Number of outputs in group 1
Organization of relay outputs into groups 1x RO (DO6) + 1x RO (DO7) +1x RO (DO8)
Output type electromechanical relay, unprotected output
Contact type NO - Normally Open
Galvanic separation from internal circuits Yes
Galvanic isolation between groups Yes
Diagnose Alarm signaling on panel module
Switching current 10 A max., 100 mA min.
Switching voltage max. 250 V AC; max. 30 V DC; min. 5 V
Short-circuit protection No
Short-term output overload 10A max.
Current through common clamp 10 A max.
Contact closing time typ. 10 ms
Contact opening time typ. 4 ms
Limit values of switched resistive load max. 10A at 30 V DC or 230 V AC
Switching inductive load limits DC13 max. 10 A at 30 V
Switching inductive load limits AC15 max. 10 A at 230 V AC
Switching frequency without load max. 300 switching / min.
Switching frequency with rated load max. 6 switching / min
Mechanical life min. 5,000,000 cycles
Electrical life at maximum resistive load min. 100,000 cycles
Electrical life at maximum load inductive DC13 min. 100,000 cycles
Electrical life at maximum load inductive AC15 min. 100,000 cycles
Treatment of inductive load External RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits 3750 V AC
Isolation voltage between groups of outputs to each other 3750 V AC
AI - Organization of analog inputs
Total number of analog inputs 10
Number of inputs per group 10
Number of analog input groups 1
Organization of analog inputs into groups 10 (DI0/AI0-DI9/AI9)
Input type With common clamp
Common wire Minus
Galvanic separation from internal circuits No
Diagnostics overload signaling in status word
External power supply No
Digital resolution 12 bit
Converter type Approximation
conversion time 20 μs
Operating modes periodic input sensing
Filtration low pass filter, digital comb filter 50/60 Hz
Insulation potential 500 V DC between input and internal circuits
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals DI0/AI0 - DI9/AI9
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-2 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Input impedance in signal range RTD > 4 kΩ
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Resistance measurement error - temperature coefficient ± 0.05% of full scale / K
Resistance measurement error - non-linearity ± 0.09% of full scale
Resistance measurement error - repeatability at steady conditions 0.07% of full scale
Max. permissible permanent overload of analog input (without damage) –20 to +30 V (each AI terminal against AGND)
Open input detection No
Detection of disconnected sensor yes, in status word, range overflow
AO - Analog output parameters
The number of groups of analogue outputs 1
Number of outputs in group 4
Organization of outputs in groups 2x (DI8/AI8/AO0-DI9/AI9/AO1) + 2x AO (DO9/AO2-DO10/AO3)
Parameters valid for the terminals AO0-AO3
Common wire of group minus
Galvanic isolation from internal circuits No
Output type active voltage output
Max. permissible permanent overload (without damage) ± 20 V, each terminal against AGND
Converter resolution 12 bit
conversion time 10 μs
Analog output error - maximum error at 25 ° C ± 2% of full scale
Analog output error - temperature coefficient ± 0.3% of full scale / K
Analog output error - linearity ± 0.7% of full scale
Analog output error - repeatability under steady state conditions ± 0.5% of full scale
External power supply No
Voltage output - voltage 0 - 10,5 V
Voltage output - Resolution 1 LSB 20,5 mV
Voltage output - maximum output current 10 mA
Power supply
Supply voltage, tolerances 24 V DC, +25%, -15%, SELV
Auxiliary power supply - voltage Optional: from 230 V AC mains, 40-60 Hz
Maximum power input 10 W
Module thermal/power loss 12 W
Internal protection Yes, PTC reversible fuse
Power supply from ETH, passive PoE - input (appliance) ETH1/Power In
Power supply from ETH, passive PoE - output (source) ETH2 / Power out, jumper configuration
Power supply from ETH, passive PoE - injector parameters 24 V DC, 1A
Size and weight
Weight approx. 300 g
Product dimensions (width x height x depth) 158 x 90 x 58 mm
Module width in multiples of M (17.5 mm) 9M
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box according to the internal packing instructions. The package includes the following documentation. The outer packaging is carried out according to the scope of the order and the method of transport to the transport a package bearing the transport labels and other particulars necessary for transport. Transport from the manufacturer is carried out in the manner agreed upon when ordering. Product transport the customer's own means must be carried out by covered means of transport, in the specified position label on the packaging. The box must be stowed so as to prevent spontaneous movement a damage to the outer packaging. The product must not be exposed to direct weathering during transport and storage influences. Transport is allowed at temperatures from -25 ° C to +70 ° C, relative humidity 10% up to 95% (non-condensing) and a minimum atmospheric pressure of more than 70 kPa. Storage of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Switchboard mounting
Assembly description The basic module is mounted vertically on the U-rail ČSN EN 50022. The installation of the assembly (basic module and peripheral modules, if applicable) is performed according to TXV 004 50.
Exchangeable submodules The optional MR-013x submodules of the serial interface are mounted in the base module CP-2091 on the bottom plate, which is accessible after removing the bottom of the housing. We only handle the module without power supply!
Connection
Connection of power and system communication connector with 2.5 mm2 screw terminal
Connection of inputs / outputs connector with screw terminal 2.5 mm2
Ethernet RJ-45
Serial channels screw-type connector 9x 1.5 mm2
USB device connection type micro B
USB host connection type A
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Module diagnostics The basic diagnostic system of the module is a part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled
Maintenance
Description The module does not require any maintenance under general installation conditions.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

Basic documentation - en

2.34 MB, (EN)

User manuals

PDF

Foxtrot 2 - Serial communication (en)

2.25 MB, (EN, RU, DE)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.59 kB, (EN, RU, DE, UA)

No data available.

No data available.